Chapter 7 — Special Conditions
San Francisco Building Inspection Commission Codes Art. 700 Emergency Systems
San Francisco Building Inspection Commission Codes · 2026-08 edition · updated 2026-09-23 · San Francisco
Cite as: San Francisco Building Inspection Commission Codes Article 700 · Text as of 2026-09-23
700.12(H)(2) Revise item (2) and (5) of this section as follows:
700.12(H)(2) Installation [ ← ]
The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.
of Unit Equipment. Unit equipment shall be installed in accordance with the following:
(2) [ ← ]
The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.
Unit equipment shall be permanently fixed (i.e., not portable) in place and shall have all wiring to each unit installed in accordance with the requirements of any of the wiring methods in Chapter 3. [ ← ]
The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.
Flexible cord-and-plug connection shall not be permitted. [ ← ]
The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.
(5) Emergency luminaires (illumination fixtures) that obtain power from a unit equipment and are not part of the unit equipment shall be wired to the [ ← ]
The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.
unit equipment as required [ ← ]
The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.
by 700.10 and by one of the wiring methods of Chapter 3.
700.16(A) Revise this section as follows:
700.16(A) Emergency Illumination. Emergency illumination shall include means of egress lighting, illuminated exit signs, and all other luminaires specified as necessary to provide required illumination. Emergency illumination shall be provided at the location of transfer switches, switchboards and panelboards that supply emergency and legally required stand-by loads.