San Francisco Building Inspection Commission Codes § 706.0 Changes in Direction of Drainage Flow

San Francisco Building Inspection Commission Codes · 2026-08 edition · updated 2026-09-23 · San Francisco

Cite as: San Francisco Building Inspection Commission Codes § 706.0 · Text as of 2026-09-23

706.4 Revise this section as follows:

706.4 Vertical to Horizontal. Vertical drainage lines connecting with horizontal drainage lines shall enter through 45 degree (0.79 rad) wye branches, combination wye and one-eighth bend branches, or other approved fittings of equivalent sweep. Branches or offsets of 60 degrees (1.05 rad) shall be permitted to be used where installed in a true vertical position. In buildings more than three stories in height, any fixture within 10 feet (304 mm) of the connection of the vertical to horizontal change shall enter the horizontal drainage line at least 10 feet (304 mm) downstream from the change or may connect into the next vertical downstream line.