9.4.3.

When fire sprinkler systems are installed in shell buildings of undetermined use (Spec Buildings) other than warehouses (S occupancies), fire sprinklers of the quick-response type shall be used. Use is considered undetermined if a specific tenant/occupant is not identified at the time the fire sprinkler plan is submitted.

Sprinklers in light hazard occupancies shall be one of the following:

(1) Quick-response type as defined in Section 3.6.4.8

(2) Residential sprinklers in accordance with the requirements of Section 8.4.5

(3) Standard spray sprinklers used for modifications or additions to existing light hazard systems equipped with standard spray sprinklers

(4) Standard spray sprinklers used where individual standard spray sprinklers are replaced in existing light hazard systems

Section 16.12.5.7 is hereby amended to read as follows: