R506 Concrete Floors (on Ground) — 2025 California Residential Code

California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-09-26 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Do I need a vapor barrier under my slab?

Minimum 6 mil vapor retarder with 6-inch laps is required under slabs; not required for garages, unheated accessory buildings, unheated storage under 70 sq ft, carports, or outdoor flatwork.

Cite as: 2025 California Residential Code (Title 24, Part 2.5) § R506 · Effective January 1, 2026 · Official source: Building Standards Commission

R506.1 General.

Concrete slab-on-ground floors shall be designed and constructed in accordance with the provisions of this section or ACI 332. Such floors shall be not less than 3 1/2 inches (89 mm) thick (for expansive soils, see Section R403.1.8). The specified compressive strength of concrete shall be as set forth in Section R402.2.

Exceptions & meaning →

R506.2 Post-tensioned slab-on-ground floors.

Post-tensioned concrete slabs-on-ground floors placed on expansive or stable soils shall be designed in accordance with PTI DC10.5.

Exceptions & meaning →

R506.3 Site preparation.

The area within the foundation walls shall have all vegetation, topsoil and foreign material removed.

R506.3.1 Fill. Fill material shall be free of vegetation and foreign material. The fill shall be compacted to ensure uniform support of the slab, and except where approved, the fill depths shall not exceed 24 inches (610 mm) for clean sand or gravel and 8 inches (203 mm) for earth.

R506.3.2 Base. A 4-inch-thick (102 mm) base course consisting of clean graded sand, gravel, crushed stone, crushed concrete or crushed blast-furnace slag passing a 2-inch (51 mm) sieve shall be placed on the prepared subgrade where the slab is below grade.

Exception: A base course is not required where the concrete slab is installed on well-drained or sand-gravel mixture soils classified as Group I according to the United Soil Classification System in accordance with Table R401.4.1(2).

R506.3.3 Vapor retarder. A minimum 6 mil (0.006 inch; 152 μ m) polyethylene or approved vapor retarder with joints lapped not less than 6 inches (152 mm) shall be placed between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist.

Exception: The vapor retarder is not required for the following:

  1. Garages, utility buildings and other unheated accessory structures.
  2. For unheated storage rooms having an area of less than 70 square feet (6.5 m [2] ) and carports.
  3. Driveways, walks, patios and other flatwork not likely to be enclosed and heated at a later date.
  4. Where approved by the building official, based on local site conditions.

R506.3.3.1 Capillary break. When a vapor retarder is required, a capillary break shall be installed in accordance with the Califor- nia Green Building Standards Code, Chapter 4, Division 4.5.

R506.3.4 Reinforcement support. Where provided in slabs-on-ground, reinforcement shall be supported to remain in place from the center to upper one-third of the slab for the duration of the concrete placement.