Section R503 — FLOOR SHEATHING
2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
R503.1 Lumber sheathing. ¶
Maximum allowable spans for lumber used as floor sheathing shall conform to Tables R503.1, R503.2.1.1(1) and R503.2.1.1(2).
TABLE R503.1—MINIMUM THICKNESS OF LUMBER FLOOR SHEATHING
| JOIST OR BEAM SPACING (inches) |
MINIMUM NET THICKNESS | MINIMUM NET THICKNESS |
|---|---|---|
| JOIST OR BEAM SPACING (inches) |
Perpendicular to joist | Diagonal to joist |
| 24 | 11/16 | 3/4 |
| 16 | 5/8 | 5/8 |
| 48a | 11/2 T & G | N/A |
| 54b | 54b | 54b |
| 60c | 60c | 60c |
| For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa. N/A = Not Applicable. a. For this support spacing, lumber sheathing shall have a minimum_Fb_ of 675 and minimum E of 1,100,000 (see ANSI AWC NDS). b. For this support spacing, lumber sheathing shall have a minimum_Fb_ of 765 and minimum E of 1,400,000 (see ANSI AWC NDS). c. For this support spacing, lumber sheathing shall have a minimum_Fb_ of 855 and minimum E of 1,700,000 (see ANSI AWC NDS). |
R503.1.1 End joints. End joints in lumber used as subflooring shall occur over supports unless end-matched lumber is used, in which case each piece shall bear on not less than two joists. Subflooring shall be permitted to be omitted where joist spacing does not exceed 16 inches (406 mm) and a 1-inch (25 mm) nominal tongue-and-groove wood strip flooring is applied perpendicular to the joists.
R503.2 Wood structural panel sheathing. ¶
R503.2.1 Identification and grade. Wood structural panel sheathing used for structural purposes shall conform to CSA O325, CSA O437 DOC PS 1 or DOC PS 2. Panels shall be identified for grade, bond classification and Performance Category by a grade mark or certificate of inspection issued by an approved agency. The Performance Category value shall be used as the “nominal panel thickness” or “panel thickness” wherever referenced in this code.
R503.2.1.1 Subfloor and combined subfloor underlayment. Where used as subflooring or combination subfloor underlayment, wood structural panels shall be of one of the grades specified in Table R503.2.1.1(1). Where sanded plywood is used as combination subfloor underlayment, the grade, bond classification, and Performance Category shall be as specified in Table R503.2.1.1(2).
5-12 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FLOORS
TABLE R503.2.1.1(1)—ALLOWABLE SPANS AND LOADS FOR WOOD STRUCTURAL
PANELS FOR ROOF AND SUBFLOOR SHEATHING AND COMBINATION SUBFLOOR UNDERLAYMENTa, b, c
| SPAN RATING |
MINIMUM NOMINAL PANEL THICKNESS (inch) |
ALLOWABLE LIVE LOAD (psf)h, I |
ALLOWABLE LIVE LOAD (psf)h, I |
MAXIMUM SPAN (inches) |
MAXIMUM SPAN (inches) |
LOAD (pounds per square foot, at maximum span) |
LOAD (pounds per square foot, at maximum span) |
MAXIMUM SPAN (inches) |
|---|---|---|---|---|---|---|---|---|
| SPAN RATING |
MINIMUM NOMINAL PANEL THICKNESS (inch) |
Span @ 16″ o.c. |
Span @ 24″ o.c. |
With edge supportd |
Without edge support |
Total load | Live load | Live load |
| Sheathinge | Sheathinge | Rooff | Rooff | Rooff | Rooff | Subfloorj | ||
| 16/0 | 3/8 | 30 | — | 16 | 16 | 40 | 30 | 0 |
| 20/0 | 3/8 | 50 | — | 20 | 20 | 40 | 30 | 0 |
| 24/0 | 3/8 | 100 | 30 | 24 | 20g | 40 | 30 | 0 |
| 24/16 | 7/16 | 100 | 40 | 24 | 24 | 50 | 40 | 16 |
| 32/16 | 15/32, 1/2 | 180 | 70 | 32 | 28 | 40 | 30 | 16h |
| 40/20 | 19/32, 5/8 | 305 | 130 | 40 | 32 | 40 | 30 | 20h, i |
| 48/24 | 23/32, 3/4 | — | 175 | 48 | 36 | 45 | 35 | 24 |
| 60/32 | 7/8 | — | 305 | 60 | 48 | 45 | 35 | 32 |
| Underlayment, C-C plugged, single floore |
Underlayment, C-C plugged, single floore |
Rooff | Rooff | Rooff | Rooff | Combination subfloor underlaymentk |
||
| 16 o.c. | 19/32, 5/8 | 100 | 40 | 24 | 24 | 50 | 40 | 16i |
| 20 o.c. | 19/32, 5/8 | 150 | 60 | 32 | 32 | 40 | 30 | 20i, j |
| 24 o.c. | 23/32, 3/4 | 240 | 100 | 48 | 36 | 35 | 25 | 24 |
| 32 o.c. | 7/8 | — | 185 | 48 | 40 | 50 | 40 | 32 |
| 48 o.c. | 13/32, 11/8 | — | 290 | 60 | 48 | 50 | 40 | 48 |
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa.
a. The allowable total loads were determined using a dead load of 10 psf. If the dead load exceeds 10 psf, then the live load shall be reduced accordingly.
b. Panels continuous over two or more spans with long dimension (strength axis) perpendicular to supports. Spans shall be limited to values shown because of possible effect of
concentrated loads.
c. Applies to panels 24 inches or wider.
d. Lumber blocking, panel edge clips (one midway between each support, except two equally spaced between supports where span is 48 inches), tongue-and-groove panel
edges, or other approved type of edge support.
e. Includes Structural I panels in these grades.
f. Uniform load deflection limitation:1/180 of span under live load plus dead load,1/240 of span under live load only.
g. Maximum span 24 inches for15/32- and1/2-inch panels.
h. Maximum span 24 inches where3/4-inch wood finish flooring is installed at right angles to joists.
i. Maximum span 24 inches where 1.5 inches of lightweight concrete or approved cellular concrete is placed over the subfloor.
j. Unsupported edges shall have tongue-and-groove joints or shall be supported with blocking unless minimum nominal1/4-inch-thick wood panel-type underlayment, fiber-
cement underlayment with end and edge joints offset not less than 2 inches or 11/2 inches of lightweight concrete or approved cellular concrete is placed over the subfloor, or
3/4-inch wood finish flooring is installed at right angles to the supports. Fiber-cement underlayment shall comply with ASTM C1288 or ISO 8336 Category C. Allowable uniform
live load at maximum span, based on deflection of1/360 of span, is 100 psf.
k. Unsupported edges shall have tongue-and-groove joints or shall be supported by blocking unless nominal1/4-inch-thick wood panel-type underlayment, fiber-cement under-
layment with end and edge joints offset not less than 2 inches or3/4-inch wood finish flooring is installed at right angles to the supports. Fiber-cement underlayment shall
comply with ASTM C1288 or ISO 8336 Category C. Allowable uniform live load at maximum span, based on deflection of1/360 of span, is 100 psf, except panels with a span rating
of 48 on center are limited to 65 psf total uniform load at maximum span.
l. Allowable live load values at spans of 16 inches on center and 24 inches on center taken from referenced standard APA E30,APA Engineered Wood Construction Guide. Refer to
referenced standard for allowable spans not listed in the table.
TABLE R503.2.1.1(2)—ALLOWABLE SPANS FOR SANDED PLYWOOD COMBINATION SUBFLOOR UNDERLAYMENTa
| ** IDENTIFICATION** | ** SPACING OF JOISTS** (inches) |
** SPACING OF JOISTS** (inches) |
** SPACING OF JOISTS** (inches) |
|---|---|---|---|
| ** IDENTIFICATION** | ** 16** | ** 20** | ** 24** |
| Species groupb | — | — | — |
| 1 | 1/2 | 5/8 | 3/4 |
| 2, 3 | 5/8 | 3/4 | 7/8 |
| 4 | 3/4 | 7/8 | 1 |
| For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa. a. Plywood continuous over two or more spans and face grain perpendicular to supports. Unsupported edges shall be tongue-and-groove or blocked except where nominal1/4- inch-thick wood panel-type underlayment, fiber-cement underlayment or3/4-inch wood finish floor is used. Fiber-cement underlayment shall comply with ASTM C1288 or ISO 8336 Category C. Allowable uniform live load at maximum span based on deflection of1/360 of span is 100 psf. b. Applicable to all grades of sanded exterior-type plywood. |
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FLOORS
R503.2.2 Allowable spans. The maximum allowable span for wood structural panels used as subfloor or combination subfloor underlayment shall be as set forth in Table R503.2.1.1(1), or APA E30. The maximum span for sanded plywood combination subfloor underlayment shall be as set forth in Table R503.2.1.1(2).
R503.2.3 Installation. Wood structural panels used as subfloor or combination subfloor underlayment shall be attached to wood framing in accordance with Table R602.3(1) and shall be attached to cold-formed steel framing in accordance with Table R505.3.1(2).
R503.3 Particleboard. ¶
R503.3.1 Identification and grade. Particleboard shall conform to ANSI A208.1 and shall be so identified by a grade mark or certificate of inspection issued by an approved agency. R503.3.2 Floor underlayment. Particleboard floor underlayment shall conform to Type PBU and shall be not less than [1] / 4 inch (6.4 mm) in thickness.
R503.3.3 Installation. Particleboard underlayment shall be installed in accordance with the recommendations of the manufacturer and attached to framing in accordance with Table R602.3(1).
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Residential Code (Title 24, Part 2.5)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — BUILDING PLANNING
- Chapter 4 — FOUNDATIONS
-
▸ Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AA — BOARD OF APPEALS
- Appendix AB — PERMIT FEES
- Appendix AC — RESERVED
- Appendix BA — RESERVED
- Appendix BB — TINY HOUSES
- Appendix BC — RESERVED
- Appendix BD — RESERVED
- Appendix BE — RADON CONTROL METHODS
- Appendix BF — PATIO COVERS
- Appendix BG — SOUND TRANSMISSION
- Appendix BH — AUTOMATIC VEHICULAR GATES
- Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
- Appendix BJ — STRAWBALE CONSTRUCTION
- Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
- Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
- Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
- Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
- Appendix BO — EXISTING BUILDINGS AND STRUCTURES
- Appendix CA — RESERVED
- Appendix CB — RESERVED
- Appendix CC — RESERVED
- Appendix CD — RESERVED
- Appendix CE — RESERVED
- Appendix CF — RESERVED
- Appendix CG — NONSEWERED SANITATION SYSTEMS
- Appendix CH — PRIVATE SEWAGE DISPOSAL
- Appendix CI — SWIMMING POOL SAFETY ACT
- Appendix CJ — EMERGENCY HOUSING
- Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…