B104.1 General. The fire-flow calculation area shall be the

total floor area of all floor levels within the exterior walls,

and under the horizontal projections of the roof of a building, except as modified in Section B104.3.

Exceptions & meaning →

B104.2 Area separation.

Portions of buildings that are separated by fire walls without openings, constructed in accordance with the California Building Code, are allowed to be considered as separate fire-flow calculation areas.

Exceptions & meaning →

B104.3 Type IA and Type IB construction. The fire-flow

calculation area of buildings constructed of Type IA and Type IB construction shall be the area of the three largest successive floors.

Exception: Fire-flow calculation area for open parking garages shall be determined by the area of the largest floor.