TEMPORARY STORAGE OF

CONSUMER FIREWORKS

working days following an incident giving rise to a verbal report, the licensed pyrotechnician in charge of the activity shall submit a complete, accurate and factual report directly to the State Fire Marshal on the event. (c) Unfired Shells. Unfired shells shall either be removed fol- lowing the display and returned directly to the wholesaler or supplier or stored in a manner approved by the authority hav- ing jurisdiction until such time as the shells can be trans- ported directly to the wholesaler or supplier.

§1006. Smoking. No person shall smoke in any area where fireworks are handled or stored.

ported directly to the wholesaler or supplier.

§1010. General. This article applies to all rockets except

§1006. Smoking. No person shall smoke in any area where approved model rockets as defined in Article 14 and experi- fireworks are handled or stored. mental high power rockets and experimental high power

rocket motors as defined in Article 2.

56-32 2022 CALIFORNIA FIRE CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

§1011. Test Areas.

(a) Experimental rockets unlimited shall not be launched within this State from any site other than test areas approved for such purpose by the fire authority having jurisdiction.

(b) These test areas shall meet the following minimum requirements:

(1) Test areas shall consist of a launching site and an

impact range.

(2) The launching site is that area immediately surround-

ing the launching devices, including positions to pro- tect all personnel.

(3) The impact range is that area over which rockets may

travel by design or accident and upon which they fall. Its length should be not less than the maximum calcu- lated ideal ballistic range of any rocket to be fired from its launching site and extends as the radius of a circular sector 90 from the launching site apex into the prevailing wind. (c) Test areas should include no dwellings or structures other than those provided for operating and nonoperating person- nel protection and loading rockets.

(d) Operating personnel protection shall consist of a bunker, blockhouse or similar protection designed to withstand shrapnel and mass impact equal to the potential created by the heaviest rocket intended to be fired, and falling from its zenith or exploding at any point. This bunker when located not less than 50 feet distant from the launching device shall afford minimum protection equal to a 2-foot wide slit trench not less than 5 feet deep and parapet observation ports with protection equal to a double thickness of sand bags. Over- head protection should consist of substantial structural mate- rials, and these materials shall be covered to afford protection equivalent to that of a double layer of filled sand bags. Non-operating personnel minimum protection when located not less than 250 feet distant from the launching device shall consist of construction at least equal to the slit trench shelter described above.

(e) Rocket loading facilities shall be housed in a lightly con- structed and covered structure located not less than 100 feet distant from any other structure including any launching device. Within this State, all fuel or propellant compounding or loading of experimental rockets unlimited shall be per- formed by licensed pyrotechnic operators or by experienced persons directly supervised by these pyrotechnic operators.

§1012. Rocket Launchers. Rocket launchers shall have a length sufficient to ensure stabilization to any rocket fired from them and shall be constructed of appropriate material such as metal or rigid flame-resistant plastic and designed for the specific intended purpose and use. Special protection shall be provided for persons setting and arming all rockets. The use of any two rail, “V” or “U” trough launcher, which depends solely on gravity to control the rocket during launch- ing is prohibited.

§1013. Setting Rocket Launchers. All adjustments and align- ments of the rocket launcher and connections shall be com- pleted before the rocket is armed. Final rocket launcher

EXPLOSIVES AND FIREWORKS

adjustments shall be checked by the licensed pyrotechnic operator in charge.

§1014. Firing Procedure. A definite ordered firing proce- dure shall be established by the licensed pyrotechnic opera- tor in charge. Both visible and audible signals shall be used to alert all persons in the test area. Any launch or firing code used shall be reduced to writing and posted conspicuously in the test area.

§1015. Launching Rockets.

(a) Rockets may not be armed or launched except by an expe- rienced pyrotechnic operator, who, if he or she is not licensed, shall be directly responsible to the licensed pyro- technic operator in charge. The actual arming operation shall be accomplished by a competent person. During all arming operations all personnel shall take shelter when launching, excepting only the individual arming the rocket and his or her necessary assistants.

All internal self-contained firing circuits (within the rocket) including, but not by way of limitation, multiple stage ignition, parachute releases, bursting charges, etc., shall be provided with an arming and disarming device operable remotely from without the assembled rocket in the launching position.

(b) The firing circuit shall be shunted at both the control cen- ter and the launching site by the pyrotechnic operator assigned to arm the rocket. Both shunts shall be in place and he or she shall test them to ensure that the firing circuit is effectively short circuited, before the rocket is set in the launching position.

(c) The single special key, which removes the launching site shunt from the firing circuit, shall be the sole means for com- pleting the firing circuit at the control center. The arming operator shall retain the shunt key in his or her personal pos- session from the time the circuit is initially shunted until the arming operations are completed and he or she removes the last shunt in the control center and establishes a ready firing circuit. (d) No other means or device than a remotely controlled elec- tric circuit of an approved design may be used to launch sin- gle stage rockets or the first stage of multistage rockets.