Chapter 35 — WELDING AND OTHER HOT WORK
Section 3505
California Fire Code (Title 24, Part 9) · 2022 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
3505.1 General. Devices or attachments mixing air or¶
oxygen with combustible gases prior to consumption, except at the burner or in a standard torch or blow pipe, shall not be allowed unless approved.
3505.2 Cylinder and container storage, handling and use.¶
Storage, handling and use of compressed gas cylinders,
35-4 2022 CALIFORNIA FIRE CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
containers and tanks shall be in accordance with this section and Chapter 53.
3505.2.1 Cylinders connected for use. The storage or use of a single cylinder of oxygen and a single cylinder of fuel gas located on a cart shall be allowed without requiring the cylinders to be separated in accordance with Section 5003.9.8 or 5003.10.3.6 when the cylinders are connected to regulators, ready for service, equipped with apparatus designed for cutting or welding and all of the following:
Carts shall be kept away from the cutting or welding operation in accordance with Section 3505.5 or fireresistant shields shall be provided.
Cylinders shall be secured to the cart to resist movement.
Carts shall be in accordance with Section 5003.10.3.
Cylinder valves not having fixed hand wheels shall have keys, handles or nonadjustable wrenches on valve stems while the cylinders are in service.
Cylinder valve outlet connections shall conform to the requirements of CGA V-1.
Cylinder valves shall be closed when work is finished.
Cylinder valves shall be closed before moving the cart.
3505.2.1.1 Individual cart separation. Individual carts shall be separated from each other in accordance with Section 5003.9.8.
3505.3 Precautions. Cylinders, valves, regulators, hose and¶
other apparatus and fittings for oxygen shall be kept free from oil or grease. Oxygen cylinders, apparatus and fittings shall not be handled with oily hands, oily gloves, or greasy tools or equipment.
3505.4 Acetylene gas. Acetylene gas shall not be piped¶
except in approved cylinder manifolds and cylinder manifold connections, or utilized at a pressure exceeding 15 pounds per square inch gauge (psig) (103 kPa) unless dissolved in a suitable solvent in cylinders manufactured in accordance with DOTn 49 CFR Part 178. Acetylene gas shall not be brought in contact with unalloyed copper, except in a blowpipe or torch.
3505.5 Remote locations. Oxygen and fuel-gas cylinders and¶
acetylene generators shall be located away from the hot work area to prevent such cylinders or generators from being heated by radiation from heated materials, sparks or slag, or misdirection of the torch flame.
3505.6 Cylinders shutoff. The torch valve shall be closed¶
and the gas supply to the torch completely shut off when gas welding or cutting operations are discontinued for a period of 1 hour or more.
3505.7 Prohibited operation. Welding or cutting work shall¶
not be held or supported on compressed gas cylinders or containers.
3505.8 Tests.¶
Tests for leaks in piping systems and equipment shall be made with soapy water. The use of flames shall be prohibited for leak testing.