Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL,
Section 2806
California Fire Code (Title 24, Part 9) · 2022 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
2806.1 General. Log storage areas shall comply with¶
Sections 2806.2 and 2806.3.
2806.2 Cold decks. Cold decks shall not exceed 500 feet¶
(152.4 m) in length, 300 feet (91 440 mm) in width and 20 feet (6096 mm) in height. Cold decks shall be separated from adjacent cold decks or other exposures by not less than 100 feet (30 480 mm).
Exception: The size of cold decks shall be determined by the fire code official where the decks are protected by special fire protection including, but not limited to, additional fire flow, portable turrets and deluge sets, and hydrant hose houses equipped with approved fire-fighting equipment capable of reaching the entire storage area in accordance with Chapter 9.
2806.3 Pile stability. Log and pole piles shall be stabilized¶
by approved means.