L104.1 Design and installation. A FARS shall be designed

and installed in accordance with Sections L104.2 through L104.15.3.

Exceptions & meaning →

L104.2 Standards. Fire fighter air replenishment systems

shall be in accordance with Sections L104.2.1 and L104.2.2.

L104.2.1 Pressurized system components. Pressurized system components shall be designed and installed in accordance with ASME B31.3.

L104.2.2 Air quality. The system shall be designed to convey breathing air complying with NFPA 1989.

Exceptions & meaning →

L104.3 Design and operating pressure. The minimum

design pressure shall be 110 percent of the fire department’s normal SCBA fill pressure. The system design pressure shall be marked in an approved manner at the supply connections, and adjacent to pressure gauges on any fixed air supply components. Pressure shall be maintained in the system within 5 percent of the design pressure.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

APPENDIX L—REQUIREMENTS FOR FIRE FIGHTER AIR REPLENISHMENT SYSTEMS

Exceptions & meaning →

L104.4 Cylinder refill rate. The FARS shall be capable of

refilling breathing air cylinders of a size and pressure used by the fire department at a rate of not less than two empty cylinders in 2 minutes.

Exceptions & meaning →

L104.5 Breathing air supply. Where a fire department

mobile air unit is available, the FARS shall be supplied by an external mobile air connection in accordance with Section L104.14. Where a fire department mobile air unit is not available, a stored pressure air supply shall be provided in accordance with Section L104.5.1. A stored pressure air supply shall be permitted to be added to a system supplied by an external mobile air connection provided that a means to bypass the stored pressure air supply is located at the external mobile air connection.

L104.5.1 Stored pressure air supply. A stored pressure air supply shall be designed based on Chapter 24 of NFPA 1901 except that provisions applicable only to mobile apparatus or not applicable to system design shall not apply. A stored pressure air supply shall be capable of refilling not less than 50 empty breathing air cylinders of a size and pressure used by the fire department.

L104.5.2 Retrofit of external mobile air connection. A FARS not initially provided with an external mobile air connection due to the lack of a mobile air unit shall be retrofitted with an external mobile air connection where a mobile air unit becomes available. Where an external mobile air connection is provided, a means to bypass the stored pressure air supply shall be located at the external mobile air connection. The retrofit shall be completed not more than 12 months after notification by the fire code official.

Exceptions & meaning →

L104.6 Isolation valves. System isolation valves that are

accessible to the fire department shall be installed on the system riser to allow piping beyond any air cylinder refill panel to be blocked.

Exceptions & meaning →

L104.7 Pressure relief valve. Pressure relief valves shall be

installed at each point of supply and at the top or end of every riser. The relief valve shall meet the requirements of CGA S1.3 and shall not be field adjustable. Pressure relief valves shall discharge in a manner that does not endanger personnel who are in the area. Valves, plugs or caps shall not be installed in the discharge of a pressure relief valve. Where discharge piping is used the end shall not be threaded.

Exceptions & meaning →

L104.8 Materials and equipment. Pressurized system

components shall be listed or approved for their intended use and rated for the maximum allowable design pressure in the system. Piping and fittings shall be stainless steel.

Exceptions & meaning →

L104.9 Welded connections. Piping connections that are

concealed shall be welded.

Exceptions & meaning →

L104.10 Protection of piping. System piping shall be

protected from physical damage in an approved manner.

Exceptions & meaning →

L104.11 Compatibility. Fittings and connections intended to

be used by the fire department shall be compatible with the fire department’s equipment.

Exceptions & meaning →

L104.12 Security.

Connections to a FARS shall be safeguarded from unauthorized access in an approved manner.

Exceptions & meaning →

L104.13 Fill stations. Fire fighter air replenishment fill

stations shall comply with Section L104.13.1 through L104.13.3.

L104.13.1 Location. Fill stations for refilling breathing air cylinders shall be located as follows:

  1. Fill stations shall be provided at the fifth floor above and below the ground level floor and every third floor level thereafter.
  2. On floor levels requiring fill stations, one fill station shall be provided adjacent to a required exit stair at a location designated by the fire code official. In buildings required to have three or more exit stairs, additional fill stations shall be provided at a ratio of one fill station for every three stairways.

L104.13.2 Design. Fill stations for breathing air cylinders shall be designed to meet the following requirements:

  1. A pressure gauge and pressure-regulating devices and controls shall be provided to allow the operator to control the fill pressure and fill rate on each cylinder fill hose.
  2. Valves controlling cylinder fill hoses shall be slowoperating valves.
  3. A separate flow restriction device shall be provided on each fill hose.
  4. A method shall be provided to bleed each cylinder fill hose.
  5. The fill station shall be designed to provide a containment area that fully encloses any cylinder being filled and flexible cylinder fill hoses, and directs the energy from a failure away from personnel. Fill stations shall be designed to prohibit filling of cylinders that are not enclosed within the containment area.

Exception: Where required or approved by the fire chief, fill stations providing for the direct refilling of the fire fighters’ breathing air cylinders using Rapid Intervention Crew/Company Universal Air Connection (RIC/UAC) fittings shall be used in lieu of cylinder fill stations that utilize containment areas.

L104.13.3 Cylinder refill rate. Fill stations shall be capable of simultaneously filling two or more empty breathing air cylinders equivalent to those used by the fire department to the cylinders’ design pressure within 2 minutes.

Exceptions & meaning →

L104.14 External mobile air connection. An external

mobile air connection shall be provided for fire department mobile air apparatus where required by Section L104.5 to supply the system with breathing air.

L104.14.1 Location. The location of the external mobile air connection shall be accessible to mobile air apparatus and approved by the fire code official.

L104.14.2 Protection from vehicles. A means of vehicle impact protection in accordance with Section 312 shall be provided to protect mobile air connections that are subject to vehicular impact.

APPENDIX L-4 2022 CALIFORNIA FIRE CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

APPENDIX L—REQUIREMENTS FOR FIRE FIGHTER AIR REPLENISHMENT SYSTEMS

L104.14.3 Clear space around connections. A working space of not less than 36 inches (914 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided and maintained in front of and to the sides of external mobile air connections.

Exceptions & meaning →

L104.15 Air-monitoring system.

An approved air-monitoring system shall be provided. The system shall automatically monitor air quality, moisture and pressure on a continual basis. The air-monitoring system shall be equipped with not less than two content analyzers capable of detecting carbon monoxide, carbon dioxide, nitrogen, oxygen, moisture and hydrocarbons.

L104.15.1 Alarm conditions. The air-monitoring system shall transmit a supervisory signal when any of the following levels are detected:

  1. Carbon monoxide exceeds 5 ppm.
  2. Carbon dioxide exceeds 1,000 ppm.
  3. An oxygen level below 19.5 percent or above 23.5 percent.
  4. A nitrogen level below 75 percent or above 81 percent.
  5. Hydrocarbon (condensed) content exceeds 5 milligrams per cubic meter of air.
  6. The moisture concentration exceeds 24 ppm by volume.
  7. The pressure falls below 90 percent of the maintenance pressure specified in Section L104.3.

L104.15.2 Alarm supervision, monitoring and notifica- tion. The air-monitoring system shall be electrically supervised and monitored by an approved supervising station, or where approved, shall initiate audible and visual supervisory signals at a constantly attended location.

L104.15.3 Air quality status display. Air quality status shall be visually displayed at the external mobile air connection required by Section L104.14.

Exceptions & meaning →