Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
Section 701
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
701.1 Scope. The provisions of this chapter shall govern the¶
inspection and maintenance of the materials, systems and assemblies used for structural fire resistance, fire-resistancerated construction separation of adjacent spaces and construction installed to resist the passage of smoke to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings. New buildings shall comply with the California Building Code .
701.2 Fire-resistance-rated construction.¶
The fire-resistance rating of the following fire-resistance-rated construction shall be maintained:
Structural members.
Exterior walls.
Fire walls, fire barriers, fire partitions.
Horizontal assemblies.
Shaft enclosures.
701.2.1 Hanging displays. The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated horizontal assembly shall be prohibited.
701.3 Smoke barriers.¶
The fire-resistance rating and smokeresistant characteristics of smoke barriers shall be maintained.
701.4 Smoke partitions. The smoke-resistant characteristics¶
of smoke partitions shall be maintained.
701.5 Maintaining protection. Materials, systems and¶
devices used to repair or protect breaches and openings in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be maintained in accordance with Sections 703 through 707.
701.6 Owner’s responsibility. The owner shall maintain an¶
inventory of all required fire-resistance-rated construction, construction installed to resist the passage of smoke and the construction included in Sections 703 through 707. Such construction shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated. Records of inspections and repairs shall be maintained. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or
movement of a panel, access door, ceiling tile or similar movable entry to the space.
701.7 Unsafe conditions. Where any components in this¶
chapter are not maintained and do not function as intended or do not have the fire resistance or the resistance to the passage of smoke required by the code under which the building was constructed, remodeled or altered, such component(s) or portion thereof shall be deemed an unsafe condition, in accordance with Section 111.1.1. Components or portions thereof determined to be unsafe shall be repaired or replaced to conform to that code under which the building was constructed, remodeled, altered or this chapter, as deemed appropriate by the fire code official.
Where the condition of components is such that any building, structure or portion thereof presents an imminent danger to the occupants of the building, structure or portion thereof, the fire code official shall act in accordance with Section 111.2.