6306.1 General. The storage and use of liquid oxygen (LOX)

in home health care in Group I-4 and R occupancies shall comply with Sections 6306.2 through 6306.6, or shall be stored and used accordance with Chapter 50.

Exceptions & meaning →

6306.2 Information and instructions to be provided. The

seller of liquid oxygen shall provide the user with information in written form that includes, but is not limited to, the following:

  1. Manufacturer’s instructions and labeling for safe storage and use of the containers.

  2. Locating containers away from ignition sources, exits, electrical hazards and high-temperature devices in accordance with Section 6306.3.3.

  3. Restraint of containers to prevent falling in accordance with Section 6306.3.4.

STORAGE CONFIGURATION LIMITS
STORAGE CONFIGURATION Control
area
storage
Group H
occupancy
storage
Detached
storage
Piles
Maximum width
Maximum height
Maximum distance to aisle
Minimum distance to next pile
Minimum distance to walls
12 feet
Note a
8 feet
Note b
4 feet
16 feet
Note a
10 feet
Note b
4 feetc
20 feet
Note a
10 feet
Note b
4 feetc
Maximum quantity per pile NA 30 tons 100 tons
Maximum quantity per building MAQ 1200 tons No
Limit

For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 ton = 0.907185 metric ton. a. Maximum storage height in nonsprinklered buildings is limited to 6 feet.

In sprinklered buildings see NFPA 400 for storage heights based on ceiling sprinkler protection. b. The minimum aisle width shall be equal to the pile height, but not less

than 4 feet and not greater than 8 feet. c. For protection level and detached storage under 2,300 pounds, there shall

not be a minimum separation distance between the pile and any wall.

TABLE 6304.1.5(3) STORAGE OF CLASS 4 OXIDIZER LIQUIDS AND SOLIDS

STORAGE CONFIGURATION LIMITS (feet)
Piles
Maximum length
Maximum width
Maximum height
Minimum distance to next pile
10
4
8
8
Maximum quantity per building No Limit

For SI: 1 foot = 304.8 mm.

6304.1.6 Separation of Class 4 oxidizers from other materials. In addition to the requirements in Section 5003.9.8, Class 4 oxidizer liquids and solids shall be separated from other hazardous materials by not less than a 1hour fire barrier or stored in hazardous materials storage cabinets.

6304.1.7 Contamination. Liquid and solid oxidizers shall not be stored on or against combustible surfaces. Liquid and solid oxidizers shall be stored in a manner to prevent contamination.

6304.1.8 Detached storage. Storage of liquid and solid oxidizers shall be in detached buildings where required by Section 5003.8.2.

6304.1.8.1 Separation distance. Detached storage buildings for Class 4 oxidizer liquids and solids shall be located not less than 50 feet (15 240 mm) from other hazardous materials storage.