Chapter 62 — ORGANIC PEROXIDES
Section 6204
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
6204.1 Indoor storage. Indoor storage of organic peroxides¶
in amounts exceeding the maximum allowable quantity per control area indicated in Table 5003.1.1(1) shall be in accordance with Sections 5001, 5003, 5004 and this chapter.
Indoor storage of unclassified detonable organic peroxides that are capable of detonation in their normal shipping con
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ORGANIC PEROXIDES
tainers under conditions of fire exposure shall be stored in accordance with Chapter 56.
6204.1.1 Detached storage. Storage of organic peroxides shall be in detached buildings where required by Section 5003.8.2.
6204.1.2 Distance from detached buildings to expo- sures. In addition to the requirements of the California Building Code, detached storage buildings for Class I, II, III, IV and V organic peroxides shall be located in accordance with Table 6204.1.2. Detached buildings containing quantities of unclassified detonable organic peroxides in excess of those set forth in Table 5003.8.2 shall be located in accordance with Table 5604.5.2(1).
6204.1.3 Liquid-tight floor. In addition to the requirements of Section 5004.12, floors of storage areas shall be of liquid-tight construction.
6204.1.4 Electrical wiring and equipment. In addition to the requirements of Section 5003.9.4, electrical wiring and equipment in storage areas for Class I or II organic peroxides shall comply with the requirements for electrical Class I, Division 2 locations.
6204.1.5 Smoke detection. An approved supervised smoke detection system in accordance with Section 907 shall be provided in rooms or areas where Class I, II or III
organic peroxides are stored. Activation of the smoke detection system shall sound a local alarm.
Exception: A smoke detection system shall not be required in detached storage buildings equipped throughout with an approved automatic fire-extinguishing system complying with Chapter 9.
6204.1.6 Maximum quantities. Maximum allowable quantities per building in a mixed occupancy building shall not exceed the amounts set forth in Table 5003.8.2. Maximum allowable quantities per building in a detached storage building shall not exceed the amounts specified in Table 6204.1.2.
6204.1.7 Storage arrangement. Storage arrangements for organic peroxides shall be in accordance with Table 6204.1.7 and shall comply with all of the following:
Containers and packages in storage areas shall be closed.
Bulk storage shall not be in piles or bins.
A minimum 2-foot (610 mm) clear space shall be maintained between storage and uninsulated metal walls.
Fifty-five-gallon (208 L) drums shall not be stored more than one drum high.
TABLE 6204.1.2 ORGANIC PEROXIDES—DISTANCE TO EXPOSURES FROM DETACHED STORAGE BUILDINGS OR OUTDOOR STORAGE AREAS
| ORGANIC PEROXIDE CLASS |
MAXIMUM STORAGE QUANTITY (POUNDS) AT MINIMUM SEPARATION DISTANCE | |||||
|---|---|---|---|---|---|---|
| ORGANIC PEROXIDE CLASS |
Distance to buildings, lot lines, public streets, public alleys, public ways or means of egress |
Distance to buildings, lot lines, public streets, public alleys, public ways or means of egress |
Distance to buildings, lot lines, public streets, public alleys, public ways or means of egress |
Distance between individual detached storage buildings or individual outdoor storage areas |
Distance between individual detached storage buildings or individual outdoor storage areas |
Distance between individual detached storage buildings or individual outdoor storage areas |
| ORGANIC PEROXIDE CLASS |
50 feet | 100 feet | 150 feet | 20 feet | 75 feet | 100 feet |
| I | 2,000 | 20,000 | 175,000 | 2,000 | 20,000 | 175,000 |
| II | 100,000 | 200,000 | No Limit | 100,000a | No Limit | No Limit |
| III | 200,000 | No Limit | No Limit | 200,000a | No Limit | No Limit |
| IV | No Limit | No Limit | No Limit | No Limit | No Limit | No Limit |
| V | No Limit | No Limit | No Limit | No Limit | No Limit | No Limit |
For SI: 1 foot = 304.8 mm, 1 pound = 0.454 kg. a. Where the amount of organic peroxide stored exceeds this amount, the minimum separation shall be 50 feet.
| TABLE 6204.1.7 STORAGE OF ORGANIC PEROXIDES | |||||
|---|---|---|---|---|---|
| ORGANIC PEROXIDE CLASS |
PILE CONFIGURATION | PILE CONFIGURATION | PILE CONFIGURATION | PILE CONFIGURATION | MAXIMUM QUANTITY PER BUILDING |
| ORGANIC PEROXIDE CLASS |
Maximum width (feet) |
Maximum height (feet) |
Minimum distance to next pile (feet) |
Minimum distance to walls (feet) |
Minimum distance to walls (feet) |
| I | 6 | 8 | 4a | 4b | Note c |
| II | 10 | 8 | 4a | 4b | Note c |
| III | 10 | 8 | 4a | 4b | Note c |
| IV | 16 | 10 | 3a, d | 4b | No Requirement |
| V | No Requirement | No Requirement | No Requirement | No Requirement | No Requirement |
For SI: 1 foot = 304.8 mm. a. Not less than one main aisle with a minimum width of 8 feet shall divide the storage area. b. Distance to noncombustible walls is allowed to be reduced to 2 feet. c. See Table 6204.1.2 for maximum quantities. d. The distance shall be not less than one-half the pile height.
676 2019 CALIFORNIA FIRE CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ORGANIC PEROXIDES
Get a plain-English answer with a citation back to this text.
Ask AI about this code