PIPING MANIFOLDS AND HOSE SYSTEMS FOR FUEL GASES AND OXYGEN

3509.1 General.

The use of piping manifolds and hose systems shall be in accordance with Section 3509.2 through 3509.7, Chapter 53 and Chapter 5 of NFPA 51.

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

WELDING AND OTHER HOT WORK

Exceptions & meaning →

3509.2 Protection. Piping shall be protected against physical

damage.

Exceptions & meaning →

3509.3 Signage. Signage shall be provided for piping and

hose systems as follows:

  1. Above-ground piping systems shall be marked in accordance with ASME A13.1.

  2. Station outlets shall be marked to indicate their intended usage.

  3. Signs shall be posted, indicating clearly the location and identity of section shutoff valves.

Exceptions & meaning →

3509.4 Manifolding of cylinders. Oxygen manifolds shall

not be located in an acetylene generator room. Oxygen manifolds shall be located not less than 20 feet (6096 mm) away from combustible material such as oil or grease, and gas cylinders containing flammable gases, unless the gas cylinders are separated by a fire partition.

Exceptions & meaning →

3509.5 Identification of manifolds. Signs shall be posted for

oxygen manifolds with service pressures not exceeding 200 psig (1379 kPa). Such signs shall include the words:

LOW-PRESSURE MANIFOLD

DO NOT CONNECT HIGH-PRESSURE CYLINDERS

MAXIMUM PRESSURE 250 PSIG

Exceptions & meaning →

3509.6 Clamps. Hose connections shall be clamped or otherwise securely fastened.

Exceptions & meaning →

3509.7 Inspection. Hoses shall be inspected frequently for

leaks, burns, wear, loose connections or other defects rendering the hose unfit for service.

Exceptions & meaning →