Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES
Section 3107
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
3107.1 General.¶
Temporary and permanent tents and membrane structures shall comply with this section.
3107.2 Combustible materials.¶
Hay, straw, shavings or similar combustible materials shall not be located within any tent or membrane structure containing an assembly occupancy, except the materials necessary for the daily feeding and care of animals. Sawdust and shavings utilized for a public performance or exhibit shall not be prohibited provided that the sawdust and shavings are kept damp. Combustible materials shall not be permitted under stands or seats at any time.
[California Code of Regulations, Title 19, Division 1, §315.(b)] Flame Resistance Standards.
(b) Sawdust, shavings, or other combustible material used on the floor or ground shall be made flame resistant or when approved by the enforcing authority shall be kept adequately damp when tent is occupied.
[California Code of Regulations, Title 19, Division 1, §326.(b)] Hazard Abatement.
(b) Hay, straw, trash and other similar flammable mate- rial shall be stored more than 50 feet from any tent except upon approval of the enforcing authority.
Exception: Tents to which the public is not admitted.
430 2019 CALIFORNIA FIRE CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTHER MEMBRANE STRUCTURES
3107.10 Fire protection equipment. Fire hose lines, water¶
supplies and other auxiliary fire equipment shall be maintained at the site in such numbers and sizes as required by the fire code official.
[California Code of Regulations, Title 19, Division 1, §319.(d) and (e)] Fire Extinguishers and Other Fire Protec- tion Equipment.
(d) Tents having a capacity of 1,000 or more persons shall be protected on each of the long sides with fire hose lines of at least 1 1 /2-inch internal diameter and of sufficient length to reach either end of the tent. The water supply shall be either from the public water mains or from tanks having a capacity of not less than 500 gallons. There shall be at least 65 pounds of flowing pressure at the nozzle of the hose line when a 1 /2-inch tip is used.
(e) The enforcing authority may modify or waive any of the requirements of this section [Title 19, Division 1, Sec- tion 319] and may accept other types of fire extinguishing equipment in lieu of that required by Title 19, Division 1 regulations if, in the authorities’ opinion, reasonable and adequate protection will be afforded.
3107.11 Occupant load factors. The occupant load allowed¶
in an assembly structure, or portion thereof, shall be determined in accordance with Chapter 10.
3107.12 Heating and cooking equipment. Heating and¶
cooking equipment shall be in accordance with Sections 3107.12.1 through 3107.12.7.
3107.12.1 Installation. Heating or cooking equipment, tanks, piping, hoses, fittings, valves, tubing and other related components shall be installed as specified in the California Mechanical Code and the California Fuel Gas Code, and shall be approved by the fire code official.
3107.12.2 Venting. Gas, liquid and solid fuel-burning equipment designed to be vented shall be vented to the outside air as specified in the California Fuel Gas Code and the California Mechanical Code . Such vents shall be equipped with approved spark arresters where required. Where vents or flues are used, all portions of the tent or membrane structure shall be not less than 12 inches (305 mm) from the flue or vent.
3107.12.3 Location. Cooking and heating equipment shall not be located within 10 feet (3048 mm) of exits or combustible materials.
3107.12.4 Operations. Operations such as warming of foods, cooking demonstrations and similar operations that use solid flammables, butane or other similar devices that do not pose an ignition hazard, shall be approved.
3107.12.5 Cooking tents. Tents with sidewalls or drops where cooking is performed shall be separated from other tents or membrane structures by not less than 20 feet (6096 mm).
3107.12.6 Outdoor cooking. Outdoor cooking that produces sparks or grease-laden vapors shall not be performed within 20 feet (6096 mm) of a tent or membrane structure.
3107.12.7 Electrical heating and cooking equipment. Electrical cooking and heating equipment shall comply with the California Electrical Code.
3107.13 LP-gas. The storage, handling and use of LP-gas and¶
LP-gas equipment shall be in accordance with Sections 3107.13.1 through 3107.13.3.
3107.13.1 General. LP-gas equipment such as containers, tanks, piping, hoses, fittings, valves, tubing and other related components shall be approved and in accordance with Chapter 61 and with the California Plumbing Code .
[California Code of Regulations, Title 19, Division 1, §325] Liquefied Petroleum Gas.
Liquefied petroleum gas shall not be stored or used in connection with any tent unless the storage containers, equip- ment, fittings, appliances, placement, use and operation com- plies with the provisions of California Code of Regulations, Title 8, Article 5, Subchapter 1, Chapter 4.
3107.13.2 Location of containers. LP-gas containers and tanks shall be located outside in accordance with Table 6104.3. Pressure relief devices shall be pointed away from the tent or membrane structure.
3107.13.3 Protection and security. Portable LP-gas containers, tanks, piping, valves and fittings that are located outside and are being used to fuel equipment inside a tent or membrane structure shall be adequately protected to prevent tampering, damage by vehicles or other hazards and shall be located in an approved location. Portable LPgas containers shall be secured to prevent unauthorized movement.
3107.14 Flammable and combustible liquids. The storage¶
of flammable and combustible liquids and the use of flammable-liquid-fueled equipment shall be in accordance with Sections 3107.14.1 through 3107.14.3.
3107.14.1 Use. Flammable-liquid-fueled equipment shall not be used in tents or membrane structures.
3107.14.2 Flammable and combustible liquid storage. Flammable and combustible liquids shall be stored outside in an approved manner not less than 50 feet (15 240 mm) from tents or membrane structures. Storage shall be in accordance with Chapter 57.
[California Code of Regulations, Title 19, Division 1, §324.(a) and (b)] Flammable and Combustible Liquids.
(a) Liquids having a flash point below 200°F shall not be stored in any tent nor less than 50 feet from any tent.
(b) Flammable or combustible liquids shall be stored and dispensed in accordance with the provisions of the Cali- fornia Fire Code. The enforcing authority may permit lim- ited quantities of flammable or combustible liquids required for display and normal merchandising.
3107.14.3 Refueling. Refueling shall be performed in an approved location not less than 20 feet (6096 mm) from tents or membrane structures.
3107.15 Display of motor vehicles. Liquid- and gas-fueled¶
vehicles and equipment used for display within tents or mem
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTHER MEMBRANE STRUCTURES
brane structures shall be in accordance with Sections 3107.15.1 through 3107.15.5.3.
3107.15.1 Batteries. Batteries shall be disconnected in an appropriate manner.
3107.15.2 Fuel. Vehicles or equipment shall not be fueled or defueled within the tent or membrane structure.
3107.15.2.1 Quantity limit. Fuel in the fuel tank shall not exceed one-quarter of the tank capacity or 5 gallons (19 L), whichever is less.
3107.15.2.2 Inspection. Fuel systems shall be inspected for leaks.
3107.15.2.3 Closure. Fuel tank openings shall be locked and sealed to prevent the escape of vapors.
3107.15.3 Location. The location of vehicles or equipment shall not obstruct means of egress.
3107.15.4 Places of assembly. When a compressed natural gas (CNG) or liquefied petroleum gas (LP-gas) powered vehicle is parked inside a place of assembly, all the following conditions shall be met:
The quarter-turn shutoff valve or other shutoff valve on the outlet of the CNG or LP-gas container shall be closed and the engine shall be operated until it stops. Valves shall remain closed while the vehicle is indoors.
The hot lead of the battery shall be disconnected.
Dual-fuel vehicles equipped to operate on gasoline and CNG or LP-gas shall comply with this section and Sections 3107.15.1 through 3107.15.3 for gasoline-powered vehicles.
3107.15.5 Competitions and demonstrations. Liquid and gas-fueled vehicles and equipment used for competition or demonstration within a tent or membrane structure shall comply with Sections 3107.15.5.1 through 3107.15.5.3.
3107.15.5.1 Fuel storage. Fuel for vehicles or equipment shall be stored in approved containers in an approved location outside of the structure in accordance with Section 3107.14.2.
3107.15.5.2 Fueling. Refueling shall be performed outside of the structure in accordance with Section 3107.14.3.
3107.15.5.3 Spills. Fuel spills shall be cleaned up immediately.
3107.16 Separation of generators. Generators and other¶
internal combustion power sources shall be separated from tents or membrane structures by not less than 20 feet (6096 mm) and shall be isolated from contact with the public by fencing, enclosure or other approved means.
3107.17 Standby personnel. Where, in the opinion of the¶
fire code official, it is essential for public safety in a tent or membrane structure used as a place of assembly or any other use where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest or activity, the owner, agent or lessee shall
employ one or more qualified persons, as required and approved, to remain on duty during the times such places are open to the public, or when such activity is being conducted.
[California Code of Regulations, Title 19, Division 1, §320] Fire Safety Personnel.
The owners or operators of any tent used as a place of assemblage shall provide at least one qualified fire safety person in every tent having a capacity of 500 persons and one additional qualified person for each 1,000 additional persons or fraction thereof. Such persons shall be on duty in the tent at all times when the tent is open to the public. They shall be proficient in the handling of fire extinguishers and equipment and shall be familiar with the fire and panic safety regulations. The individual designated under this sec- tion shall meet the approval of the fire authority having jurisdiction.
Exception: The enforcing authority may waive or modify the provisions of this section if, in his opinion, public safety will not be jeopardized.
3107.17.1 Duties. Before each performance or the start of such activity, standby personnel shall keep diligent watch for fires during the time such place is open to the public or such activity is being conducted and take prompt measures for extinguishment of fires that occur and assist in the evacuation of the public from the structure.
3107.17.2 Crowd managers. There shall be trained crowd managers or trained crowd supervisors at a ratio of one crowd manager or supervisor for every 250 occupants, as approved.
3107.18 Combustible vegetation. Combustible vegetation¶
that could create a fire hazard shall be removed from the area occupied by a tent or membrane structure, and from areas within 30 feet (9144 mm) of such structures.
[California Code of Regulations, Title 19, Division 1, §326.(a)] Hazard Abatement.
(a) All flammable vegetation within 50 feet of any tent shall be removed.
3107.19 Combustible waste material. The floor surface¶
inside tents or membrane structures and the grounds outside and within a 30-foot (9144 mm) perimeter shall be kept free of combustible waste and other combustible materials that could create a fire hazard. Such waste shall be stored in approved containers and removed from the premises not less than once a day during the period the structure is occupied by the public.
[California Code of Regulations, Title 19, Division 1, §326.(c)] Hazard Abatement.
(c) Combustible waste shall not be permitted to accumu- late on the grounds either inside or outside of tents. Such waste shall be stored in approved containers until removed from the premises.
3107.20 Obstructions. Exits, aisles and passageways shall¶
not be blocked or have their minimum clear width obstructed in any manner by ticket offices, turnstiles, concessions,
432 2019 CALIFORNIA FIRE CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTHER MEMBRANE STRUCTURES
chairs, equipment, animal chutes, poles or guy ropes, or any- thing whatsoever, nor shall they be blocked by persons for whom no seats are available.
In occupancies having fixed seating, and on request of the owner or manager, the enforcing agency may permit modifi- cations from the provisions of this code to accommodate seat- ing for handicapped persons using mechanical aids such as, but not limited to, walkers and wheelchairs.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
434 2019 CALIFORNIA FIRE CODE Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
CALIFORNIA FIRE CODE – MATRIX ADOPTION TABLE
Get a plain-English answer with a citation back to this text.
Ask AI about this code