Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
Section C105
California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
REFERENCED STANDARD
ICC IBC—18 International Residential Code Table C102.1
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
APPENDIX C
TABLE C102.1 REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS h
| FIRE-FLOW REQUIREMENT (gpm) |
MINIMUM NUMBER OF HYDRANTS |
AVERAGE SPACING BETWEEN HYDRANTSa, b, c, f, g (feet) |
MAXIMUM DISTANCE FROM ANY POINT ON STREET OR ROAD FRONTAGE TO A HYDRANTd, f, g |
|---|---|---|---|
| 1,750 or less | 1 | 500 | 250 |
| 1,751–2,250 | 2 | 450 | 225 |
| 2,251–2,750 | 3 | 450 | 225 |
| 2,751–3,250 | 3 | 400 | 225 |
| 3,251–4,000 | 4 | 350 | 210 |
| 4,001–5,000 | 5 | 300 | 180 |
| 5,001–5,500 | 6 | 300 | 180 |
| 5,501–6,000 | 6 | 250 | 150 |
| 6,001–7,000 | 7 | 250 | 150 |
| 7,001 or more | 8 or moree | 200 | 120 |
For SI: 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m. a. Reduce by 100 feet for dead-end streets or roads. b. Where streets are provided with median dividers that cannot be crossed by fire fighters pulling hose lines, or where arterial streets are provided with four or
more traffic lanes and have a traffic count of more than 30,000 vehicles per day, hydrant spacing shall average 500 feet on each side of the street and be arranged on an alternating basis. c. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems, fire hydrants shall be
provided at spacing not to exceed 1,000 feet to provide for transportation hazards. d. Reduce by 50 feet for dead-end streets or roads. e. One hydrant for each 1,000 gallons per minute or fraction thereof. f. A 50-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with
Section 903.3.1.1 of the California Fire Code . g. A 25-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with
Section 903.3.1.2 or 903.3.1.3 of the California Fire Code or Section P2904 of the California Residential Code . h. The fire code official is authorized to modify the location, number and distribution of fire hydrants based on site-specific constraints and hazards.
756 2019 CALIFORNIA FIRE CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.