Chapter 61 — LIQUEFIED PETROLEUM GASES
6110 LP-Gas Containers Not in Service — 2025 California Fire Code
California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Fire Code (Title 24, Part 9) § 6110 · Effective January 1, 2026 · Official source: Building Standards Commission
6110.1 Removed from service.¶
LP-gas containers whose use has been discontinued shall comply with all of the following:
- Be disconnected from appliance piping.
LIQUEFIED PETROLEUM GASES
- Have LP-gas container outlets, except relief valves, closed or plugged.
- Be positioned with the relief valve in direct communication with the LP-gas container vapor space.
6110.2 Removal from site.¶
LP-gas containers discontinued from service shall be removed from the site.