Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
Section 5705 — DISPENSING, USE, MIXING AND HANDLING
2025 California Fire Code (Title 24, Part 9) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
5705.1 Scope. ¶
5705.1 Scope. Dispensing, use, mixing and handling of flammable liquids shall be in accordance with Section 5703 and this section. Tank vehicle and tank car loading and unloading and other special operations shall be in accordance with Section 5706. Exception: Containers of organic coatings having no fire point and which are opened for pigmentation are not required to comply with this section.
5705.2 Liquid transfer. ¶
5705.2 Liquid transfer. Liquid transfer equipment and methods for transfer of Class I, II and IIIA liquids shall be approved and be in accordance with Sections 5705.2.1 through 5705.2.6. 5705.2.1 Pumps. Where positive-displacement pumps are used, they shall be provided with pressure relief discharging back to the tank, pump suction or other approved location, or shall be provided with interlocks to prevent over-pressure. 5705.2.2 Pressured systems. Where gases are introduced to provide for transfer of Class I liquids, or Class II and III liquids transferred at temperatures at or above their…
5705.3 Use, dispensing and mixing inside of buildings. ¶
5705.3 Use, dispensing and mixing inside of buildings. Indoor use, dispensing and mixing of flammable and combustible liquids shall be in accordance with Section 5705.2 and Sections 5705.3.1 through 5705.3.5.3. 5705.3.1 Closure of mixing or blending vessels. Vessels used for mixing or blending of Class I liquids and Class II or III liquids heated up to or above their flash points shall be provided with self-closing, tight-fitting, noncombustible lids that will control a fire within such vessel. Exception: Where such devices are impractical, approved automatic or manually controlled…
5705.4 Solvent distillation units. ¶
5705.4 Solvent distillation units. Solvent distillation units shall comply with Sections 5705.4.1 through 5705.4.9. 5705.4.1 Unit with a capacity of 60 gallons or less. Solvent distillation units used to recycle Class I, II or IIIA liquids having a distillation chamber capacity of 60 gallons (227 L) or less shall be listed, labeled and installed in accordance with Section 5705.4 and UL 2208. Exceptions: 1. Solvent distillation units used in continuous through-put industrial processes where the source of heat is remotely supplied using steam, hot water, oil or other heat transfer fluids, the…
5705.5 Alcohol-based hand rubs classified as Class I or II liquids. ¶
5705.5 Alcohol-based hand rubs classified as Class I or II liquids. The use of dispensers containing alcohol-based hand rubs classified as Class I or II liquids shall be in accordance with all of the following: 1. The maximum capacity of each dispenser shall be 68 ounces (2 L). 2. The minimum separation between dispensers shall be 48 inches (1219 mm). 3. Dispensers shall not be located above, below or closer than 1 inch (25 mm) to an electrical receptacle, switch, appliance, device or other ignition source. The wall space between the dispenser and the floor or intervening counter top shall be…