Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
Section 4005 — FIRE PROTECTION
2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
4005.1 Palletized storage of distilled spirits in wooden barrels. ¶
The palletized storage of distilled spirits in wooden barrels shall be protected by an approved automatic sprinkler system installed throughout the building in accordance with Section 903.3.1.1 as modified in this section. The palletized storage of metal containers of distilled spirits shall be protected by an approved automatic sprinkler system that complies with Chapter 57.
4005.1.1 Storage height. Palletized storage arrays of barrels stored on end shall be limited to a maximum of seven pallets high.
4005.1.2 Flue spaces. Flue spaces with a minimum width of 6 inches (152 mm) shall be maintained between adjacent pallets.
4005.1.3 Loading aisles. Palletized storage that is provided with a defined loading aisle between pallet storage areas shall be arranged using one of the following:
Draft curtains, installed in accordance with Section 4005.1.3.1, shall be provided along the side of palletized storage facing the loading aisle to separate the quick-response sprinklers and standard-response sprinklers.
A trench drain shall be provided on each side of the loading aisle, arranged to capture any spilled distilled spirits in the aisle space and remove them from the building to prevent spills from spreading into the barrel storage area.
Barrels shall be banded on each pallet to prevent barrels from falling off pallets during transportation and loading into the storage racks.
4005.1.3.1 Draft curtains. Where installed in accordance with Section 4005.1.3, Item 1, draft curtains shall be designed and constructed in accordance with Sections 4005.1.3.1.1 through 4005.1.3.1.3.
4005.1.3.1.1 Construction. Draft curtains shall be constructed of sheet metal, lath and plaster, gypsum board or other approved noncombustible materials that provide equivalent performance to resist the passage of smoke. Joints and connections shall be designed to resist the passage of smoke.
4005.1.3.1.2 Location. Draft curtains shall be located along loading aisles serving storage areas.
4005.1.3.1.3 Depth. Draft curtains shall extend vertically downward from the ceiling for a minimum distance of 20 percent of the ceiling height measured from the floor, with a minimum depth of 6 feet (1829 mm).
4005.1.4 Automatic sprinkler system design. Storage heights and automatic sprinkler densities for palletized on-end barrels shall be in accordance with Table 4005.1.4 and Sections 4005.1.4.1 through 4005.1.4.6.
TABLE 4005.1.4—PALLETIZED STORAGE OF DISTILLED SPIRITS WITH UP TO 75 PERCENT ALCOHOL BY VOLUME IN WOODEN BARRELS
| PROTECTION AREA | SPRINKLER SYSTEM TYPE |
MAXIMUM CEILING HEIGHT (feet) |
MAXIMUM STORAGE HEIGHT |
CEILING SPRINKLER PROTECTION | CEILING SPRINKLER PROTECTION | CEILING SPRINKLER PROTECTION |
|---|---|---|---|---|---|---|
| PROTECTION AREA | SPRINKLER SYSTEM TYPE |
MAXIMUM CEILING HEIGHT (feet) |
MAXIMUM STORAGE HEIGHT |
Response/Nominal Temperature Rating/Orientation |
K-Factor (gpm/psi1/2) |
Designa, # of Sprinklers @ Pressure (psi) |
| Barrel storage | Wet-pipe | 30 | 24 feet or 7 barrels |
QR/165°F/Pendent | 14.0 | 12 @ 18 |
| Barrel storage | Dry-pipe | Dry-pipe | Dry-pipe | SR/286°F/Upright | 16.8 | 24 @ 13 |
| Barrel storage | Wet-pipe | 30 | 1 barrel | Any/165°F/Any | 11.2 | 30 @ 7 |
| Barrel storage | Dry-pipe | Dry-pipe | Dry-pipe | SR/286°F/Upright | 11.2 | 50 @ 7 |
| Barrel storage | Wet-pipe | 30 | 2 barrels | SR/286°F/Any | 11.2 | 50 @ 29 |
| Loading aisle w/ draft curtain |
Wet-pipe or Dry-pipe |
30 | NA | SR/286°F/Any | 5.6 | 100 @ 13 |
| Loading aisle w/ draft curtain |
Wet-pipe or Dry-pipe |
30 | NA | SR/286°F/Any | > 8.0 | 100 @ 7 |
| Loading aisle w/ trench drains or banded barrels or no permanent loading aisle |
Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). | Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). | Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). | Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). | Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). | Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch (psi) = 6.895 kPa, K-factor of 1 gpm/psi1/2 = 14.395 L/min/bar1/2, °C = (°F – 32)/1.8. QR = Quick Response; SR = Standard Response; NA = Not Applicable. a. Sprinklers shall have a maximum coverage area of 100 square feet. |
40-4 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STORAGE OF DISTILLED SPIRITS AND WINES
4005.1.4.1 Protected product. The storage and automatic sprinkler requirements in Table 4005.1.4 apply to alcohol-water mixtures greater than 20 percent and up to 75 percent alcohol by volume in wooden barrel sizes not exceeding 130 gallons (492 L).
4005.1.4.2 Hose stream allowance. The automatic sprinkler design shall include a 500 gallons per minute (1900 L/min) hose stream allowance.
4005.1.4.3 Water supply duration. The automatic sprinkler system water supply duration, including hose stream demand, shall be a minimum of 1 hour.
4005.1.4.4 Automatic sprinkler system balancing. Where a permanent loading aisle is provided with a separate automatic sprinkler system on the ceiling, the barrel storage automatic sprinkler design and the loading aisle automatic sprinkler design are not required to be balanced at the point of connection.
4005.1.4.5 Dry pipe sprinkler systems. Where dry-pipe sprinkler systems are installed, the sprinkler system shall be designed to deliver water to the most remote four sprinklers within 40 seconds.
4005.1.4.6 Small distilled spirits facilities. Fire protection for palletized storage of distilled spirits in small distilled spirits facilities not greater than 7,500 square feet (697 m2) is permitted to be in accordance with Sections 4005.1.4.6.1 through 4005.1.4.6.3.
4005.1.4.6.1 Ceiling clearance. The clearance from the top of storage to the deflector of the automatic sprinklers at the ceiling shall be a minimum of 18 inches (457 mm) and a maximum of 10 feet (3048 mm).
4005.1.4.6.2 Automatic sprinkler coverage area. The automatic sprinkler coverage area shall not exceed 80 square feet (7.4 m [2] ) per sprinkler.
4005.1.4.6.3 Fire protection scheme. The storage arrangement and automatic sprinkler system design shall be in accordance with Table 4005.1.4.6.3.
TABLE 4005.1.4.6.3—PALLETIZED STORAGE OF DISTILLED SPIRITS IN WOODEN BARRELS IN SMALL DISTILLED SPIRITS FACILITIES
| PROTECTION AREA |
SPRINKLER SYSTEM TYPE |
MAXIMUM CEILING HEIGHT (feet) |
MAXIMUM STORAGE HEIGHT (feet) |
CEILING SPRINKLER PROTECTION | CEILING SPRINKLER PROTECTION | CEILING SPRINKLER PROTECTION | CEILING SPRINKLER PROTECTION |
|---|---|---|---|---|---|---|---|
| PROTECTION AREA |
SPRINKLER SYSTEM TYPE |
MAXIMUM CEILING HEIGHT (feet) |
MAXIMUM STORAGE HEIGHT (feet) |
Response/Temperature Rating/Orientation |
K-Factor (gpm/psi1/2) |
Sprinkler Density (gpm/ft2) |
Area (square feet) |
| Barrel storage | Wet-pipe | 24 | 12 | SR/286°F/Any | ≥ 11.2 | 0.35 | 4,000 |
| Barrel storage | Wet-pipe | 24 | 12 | SR/165°F/Any | ≥ 11.2 | 0.35 | 7,500 |
| For SI: 1 foot = 304.8 mm, 1 pound per square inch (psi) = 6.895 kPa, K-factor of 1 gpm/psi1/2 = 14.395 L/min/bar1/2, °C = (°F – 32)/1.8, 1 gallon per minute per square foot = 40.75 L/min/m2. SR = Standard Response. |
4005.2 Rack storage in wooden barrels. ¶
The rack storage of distilled spirits and wine greater than 20 percent alcohol shall be protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3.1.1 and Sections 4005.2.1 through 4005.2.3.6.
4005.2.1 Flue spaces for on-side wooden barrels. Rack storage for on-side wooden barrels shall be provided with a minimum width of 8 inches (203 mm) between adjacent rows of barrels.
4005.2.1.1 Elevated walkways. Where provided, elevated walkways between barrels shall be constructed in accordance with one of the following:
- Noncombustible materials that are 50 percent open.
- Noncombustible materials that are open less than 50 percent, provided that the walkway has a maximum width of 1 foot (305 mm) and a minimum gap of 3 inches (76 mm) is provided between the walkway and the barrel storage.
- Combustible materials that are provided with a row of automatic sprinklers directly beneath each walkway.
4005.2.2 Flue spaces for on-end wooden barrels. Rack storage arrangements with on-end wooden barrels shall be provided with transverse and longitudinal flue spaces with a minimum width of 6 inches (152 mm).
4005.2.3 Fire protection for rack storage. Rack storage arrangements of alcohol-water mixtures up to 75 percent alcohol in wooden barrels with sizes not exceeding 130 gallons (492 L) shall be protected in accordance with Sections 4005.2.3.1 through 4005.2.3.6.
4005.2.3.1 Hose stream allowance. The automatic sprinkler system design shall include a 500-gallon-per-minute (1900 L/min) hose stream allowance.
4005.2.3.2 Water supply duration. The automatic sprinkler system water supply duration, including hose stream demand, shall be a minimum of 1 hour.
4005.2.3.3 Dry-pipe automatic sprinkler system. Where dry-pipe automatic sprinkler systems are installed, the automatic sprinkler system shall be designed to deliver water to the most remote four sprinklers within 40 seconds.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STORAGE OF DISTILLED SPIRITS AND WINES
4005.2.3.4 Ceiling automatic sprinkler systems. The automatic sprinkler systems installed at the ceiling shall be designed with a minimum density of 0.2 gallon per minute (0.8 L/min) per square foot with an operating area of 2,000 square feet (186 m [2] ).
4005.2.3.5 Automatic sprinkler system balancing. The automatic sprinkler system installed at the ceiling and the in-rack sprinkler system shall be balanced at the point of connection.
4005.2.3.6 Automatic sprinkler system design. The design of the automatic sprinkler system at the ceiling and the in-rack sprinkler system shall be in accordance with Table 4005.2.3.6.
TABLE 4005.2.3.6—RACK STORAGE OF DISTILLED SPIRITS IN WOODEN BARRELS
| BARREL ARRANGEMENT |
SPRIN- KLER SYSTEM TYPE |
MAXI- MUM CEILING HEIGHT (feet) |
MAXI- MUM STORAGE HEIGHT (feet) |
MINIMUM AISLE WIDTH (feet) |
CEILING SPRINKLER PROTECTION | CEILING SPRINKLER PROTECTION | CEILING SPRINKLER PROTECTION | IN-RACK SPRINKLER PROTECTION | IN-RACK SPRINKLER PROTECTION | IN-RACK SPRINKLER PROTECTION | IN-RACK SPRINKLER PROTECTION |
|---|---|---|---|---|---|---|---|---|---|---|---|
| BARREL ARRANGEMENT |
SPRIN- KLER SYSTEM TYPE |
MAXI- MUM CEILING HEIGHT (feet) |
MAXI- MUM STORAGE HEIGHT (feet) |
MINIMUM AISLE WIDTH (feet) |
Response/ Nominal Temperature Rating/ Orientation |
K-Factor (gpm/psi1/2) |
Design, # of Sprinklers @ Pressure (psi) |
Layout | Response/ Nominal Temperature Rating/ Orientation |
K-Factor (gpm/psi1/2) |
Designa, # of Sprin- klers @ Pressure (psi) |
| On-side | Wet | 40 | 33 feet/ 9 barrels |
NA | QR/165°F/ Pendent |
14.0 | 12 @ 37 | None | None | None | None |
| On-side | Wet | 40 | 33 feet/ 9 barrels |
NA | SR/286°F/Any | ≥ 11.2 | 20 @ 7 | Figures 4005.2.3.6(1) and 4005.2.3.6(2) |
QR/165°F/Any | 8.0 | 6 @ 45 (one level of in-racks) or 12 @ 45 (more than one level of in racks) |
| On-side | Dry | 40 | 33 feet/ 9 barrels |
NA | SR/286°F/ Upright |
16.8 | 24 @ 25 | None | None | None | None |
| On-side | Dry | 40 | 33 feet/ 9 barrels |
NA | SR/286°F/ Upright |
≥ 11.2 | 20 @ 7 | Figures 4005.2.3.6(1) and 4005.2.3.6(2) |
QR/165°F/ Upright |
8.0 | 6 @ 45 (one level of in-racks) or 12 @ 45 (more than one level of in racks) |
| On-end | Wet | 30 | 25 feet/ 5 barrels |
8 | SR/286°F/Any | ≥ 11.2 | 50 @ 7 | Figures 4005.2.3.6(3) , 4005.2.3.6(4) and 4005.2.3.6(5) |
QR/165°F/Any | ≥ 8.0 | 6 @ 25 (one level) or 12 @ 25 (more than one level) |
| For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch (psi) = 6.895 kPa, K-factor of 1 gpm/psi1/2 = 14.395 L/min/bar1/2, °C = (°F – 32)/1.8. QR = Quick Response; SR = Standard Response; NA = Not Applicable. a. Sprinklers shall have a maximum coverage area of 100 square feet. |
40-6 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STORAGE OF DISTILLED SPIRITS AND WINES
FIGURE 4005.2.3.6(1)—IN-RACK SPRINKLER LAYOUT FOR WOODEN BARRELS ON THEIR SIDES (PLAN VIEW)
10 FT (3 M) 10 FT (3 M)
4 FT (1.2 M)
70% OPEN
| 8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
8 IN (200 MM) |
IN-RACK SPRINKLERS
Figure credit: FM Global Property Loss Prevention Data Sheet 7-29
FIGURE 4005.2.3.6(2)—IN-RACK SPRINKLER LAYOUT FOR WOODEN BARRELS ON THEIR SIDES (ELEVATION VIEW)
6 IN (150 MM)
3 FT (10 M)/ 30 FT (
9 BARRELS 8 BAR
| 3 FT (10 M)/ 9 BARRELS 30 FT ( 8 BAR |
3 FT (10 M)/ 9 BARRELS 30 FT ( 8 BAR |
30 FT ( 8 BAR |
|||||||
|---|---|---|---|---|---|---|---|---|---|
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
||||||||
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
||||||||
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
||||||||
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
||||||||
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
||||||||
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
||||||||
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
||||||||
| 3 FT (10 M)/ 9 BARRELS |
3 FT (10 M)/ 9 BARRELS |
IN-RACK SPRINKLERS
Figure credit: FM Global Property Loss Prevention Data Sheet 7-29
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STORAGE OF DISTILLED SPIRITS AND WINES
FIGURE 4005.2.3.6(3)—IN-RACK SPRINKLER LAYOUT FOR SINGLE-ROW RACK OF ON-END WOODEN BARRELS
6 FT (1.8 M) MAXIMUM
PLAN VIEW MAXIMUM
ELEVATION VIEW
, = IN-RACK SPRINKLERS
Figure credit: FM Global Property Loss Prevention Data Sheet 7-29
40-8 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STORAGE OF DISTILLED SPIRITS AND WINES
FIGURE 4005.2.3.6(4)—IN-RACK SPRINKLER LAYOUT FOR DOUBLE-ROW RACK OF ON-END WOODEN BARRELS
8 FT (2.4 M)
9 FT (2.7 M) MAXIMUM
PLAN VIEW MAXIMUM
ELEVATION VIEW
, = IN-RACK SPRINKLERS
Figure credit: FM Global Property Loss Prevention Data Sheet 7-29
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STORAGE OF DISTILLED SPIRITS AND WINES
FIGURE 4005.2.3.6(5)—IN-RACK SPRINKLER LAYOUT FOR MULTIPLE-ROW RACK OF ON-END WOODEN BARRELS
8 FT (2.4 M)
4–5 FT (1.2–1.5 M) MAXIMUM
4–5 FT (1.2–1.5 M) MAXIMUM
4–5 FT (1.2–1.5 M) MAXIMUM
4–5 FT (1.2–1.5 M) MAXIMUM
PLAN VIEW
MAXIMUM
SECOND TIER FACE SPRINKLERS ALL TIERS LONGITUDINAL FLUE SPRINKLERS
= IN-RACK SPRINKLERS
2 TO 3 DRUMS
AND
10 – 15 FT
– (3 4.6 M) MAXIMUM
,,
| 2 D | |
|---|---|
| 2 D A 10 F | |
|---|---|
MA |
|
| 2 DRU AND 10 FT (3 MAXIM DRUMS 2 DRUMS D AND 5 FT 1 DRU 10 FT (3 M) 6 M) AND MAXIMUM MUM 5 FT (1. MAXIM |
2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM |
||||||||
|---|---|---|---|---|---|---|---|---|---|
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
|||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
AND MAXIMUM |
||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
AND MAXIMUM |
||||||||
| 2 DRU AND 10 FT (3 MAXIM 1 DRU AND 5 FT (1. MAXIM DRUMS D 5 FT 6 M) MUM AND MAXIMUM |
AND MAXIMUM |
ELEVATION VIEW
,, = IN-RACK SPRINKLERS
Figure credit: FM Global Property Loss Prevention Data Sheet 7-29
4005.3 Wine with 20 percent or less alcohol content. ¶
The storage of wine in barrels with an alcohol content of 20 percent or less shall be protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3.1.1.
4005.4 Portable fire extinguishers. ¶
Approved portable fire extinguishers shall be provided in accordance with Section 906.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Fire Code (Title 24, Part 9)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REQUIREMENTS
- Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
- Chapter 5 — FIRE SERVICE FEATURES
- Chapter 6 — BUILDING SERVICES AND SYSTEMS
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
- Chapter 12 — ENERGY SYSTEMS
- Chapter 20 — AVIATION FACILITIES
- Chapter 21 — DRY CLEANING
- Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
- Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
- Chapter 24 — FLAMMABLE FINISHES
- Chapter 25 — FRUIT AND CROP RIPENING
- Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
- Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
- Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
- Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
- Chapter 30 — INDUSTRIAL OVENS
- Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
- Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
- Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
- Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
- Chapter 35 — WELDING AND OTHER HOT WORK
- Chapter 36 — MARINAS
- Chapter 37 — COMBUSTIBLE FIBERS
- Chapter 38 — RESERVED
- Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
-
▸ Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
- Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
- Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
- Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
- Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
- Chapter 51 — AEROSOLS
- Chapter 52 — RESERVED
- Chapter 53 — COMPRESSED GASES
- Chapter 54 — CORROSIVE MATERIALS
- Chapter 55 — CRYOGENIC FLUIDS
- Chapter 56 — EXPLOSIVES AND FIREWORKS
- Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
- Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
- Chapter 59 — FLAMMABLE SOLIDS
- Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
- Chapter 61 — LIQUEFIED PETROLEUM GASES
- Chapter 62 — ORGANIC PEROXIDES
- Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
- Chapter 64 — PYROPHORIC MATERIALS
- Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
- Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
- Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
- Chapter 80 — REFERENCED STANDARDS
- Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
- Appendix A — BOARD OF APPEALS
- Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix D — FIRE APPARATUS ACCESS ROADS
- Appendix E — HAZARD CATEGORIES
- Appendix F — HAZARD RANKING
- Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
- Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
- Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
- Appendix J — BUILDING INFORMATION SIGN
- Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
- Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
- Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
- Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
- Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
- Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
- Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…