Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES

Section 4005 — FIRE PROTECTION

2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

4005.1 Palletized storage of distilled spirits in wooden barrels.

The palletized storage of distilled spirits in wooden barrels shall be protected by an approved automatic sprinkler system installed throughout the building in accordance with Section 903.3.1.1 as modified in this section. The palletized storage of metal containers of distilled spirits shall be protected by an approved automatic sprinkler system that complies with Chapter 57.

4005.1.1 Storage height. Palletized storage arrays of barrels stored on end shall be limited to a maximum of seven pallets high.

4005.1.2 Flue spaces. Flue spaces with a minimum width of 6 inches (152 mm) shall be maintained between adjacent pallets.

4005.1.3 Loading aisles. Palletized storage that is provided with a defined loading aisle between pallet storage areas shall be arranged using one of the following:

  1. Draft curtains, installed in accordance with Section 4005.1.3.1, shall be provided along the side of palletized storage facing the loading aisle to separate the quick-response sprinklers and standard-response sprinklers.

  2. A trench drain shall be provided on each side of the loading aisle, arranged to capture any spilled distilled spirits in the aisle space and remove them from the building to prevent spills from spreading into the barrel storage area.

  3. Barrels shall be banded on each pallet to prevent barrels from falling off pallets during transportation and loading into the storage racks.

4005.1.3.1 Draft curtains. Where installed in accordance with Section 4005.1.3, Item 1, draft curtains shall be designed and constructed in accordance with Sections 4005.1.3.1.1 through 4005.1.3.1.3.

4005.1.3.1.1 Construction. Draft curtains shall be constructed of sheet metal, lath and plaster, gypsum board or other approved noncombustible materials that provide equivalent performance to resist the passage of smoke. Joints and connections shall be designed to resist the passage of smoke.

4005.1.3.1.2 Location. Draft curtains shall be located along loading aisles serving storage areas.

4005.1.3.1.3 Depth. Draft curtains shall extend vertically downward from the ceiling for a minimum distance of 20 percent of the ceiling height measured from the floor, with a minimum depth of 6 feet (1829 mm).

4005.1.4 Automatic sprinkler system design. Storage heights and automatic sprinkler densities for palletized on-end barrels shall be in accordance with Table 4005.1.4 and Sections 4005.1.4.1 through 4005.1.4.6.

TABLE 4005.1.4—PALLETIZED STORAGE OF DISTILLED SPIRITS WITH UP TO 75 PERCENT ALCOHOL BY VOLUME IN WOODEN BARRELS

PROTECTION AREA SPRINKLER
SYSTEM TYPE
MAXIMUM
CEILING HEIGHT
(feet)
MAXIMUM
STORAGE
HEIGHT
CEILING SPRINKLER PROTECTION CEILING SPRINKLER PROTECTION CEILING SPRINKLER PROTECTION
PROTECTION AREA SPRINKLER
SYSTEM TYPE
MAXIMUM
CEILING HEIGHT
(feet)
MAXIMUM
STORAGE
HEIGHT
Response/Nominal
Temperature
Rating/Orientation
K-Factor
(gpm/psi1/2)
Designa, # of
Sprinklers @
Pressure (psi)
Barrel storage Wet-pipe 30 24 feet or
7 barrels
QR/165°F/Pendent 14.0 12 @ 18
Barrel storage Dry-pipe Dry-pipe Dry-pipe SR/286°F/Upright 16.8 24 @ 13
Barrel storage Wet-pipe 30 1 barrel Any/165°F/Any 11.2 30 @ 7
Barrel storage Dry-pipe Dry-pipe Dry-pipe SR/286°F/Upright 11.2 50 @ 7
Barrel storage Wet-pipe 30 2 barrels SR/286°F/Any 11.2 50 @ 29
Loading aisle w/ draft
curtain
Wet-pipe or
Dry-pipe
30 NA SR/286°F/Any 5.6 100 @ 13
Loading aisle w/ draft
curtain
Wet-pipe or
Dry-pipe
30 NA SR/286°F/Any > 8.0 100 @ 7
Loading aisle w/ trench
drains or banded barrels or
no permanent loading aisle
Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle). Provide the barrel storage design across the entire roof area (i.e., storage area and loading aisle).
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch (psi) = 6.895 kPa, K-factor of 1 gpm/psi1/2 = 14.395 L/min/bar1/2, °C = (°F –
32)/1.8.
QR = Quick Response; SR = Standard Response; NA = Not Applicable.
a. Sprinklers shall have a maximum coverage area of 100 square feet.

40-4 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

STORAGE OF DISTILLED SPIRITS AND WINES

4005.1.4.1 Protected product. The storage and automatic sprinkler requirements in Table 4005.1.4 apply to alcohol-water mixtures greater than 20 percent and up to 75 percent alcohol by volume in wooden barrel sizes not exceeding 130 gallons (492 L).

4005.1.4.2 Hose stream allowance. The automatic sprinkler design shall include a 500 gallons per minute (1900 L/min) hose stream allowance.

4005.1.4.3 Water supply duration. The automatic sprinkler system water supply duration, including hose stream demand, shall be a minimum of 1 hour.

4005.1.4.4 Automatic sprinkler system balancing. Where a permanent loading aisle is provided with a separate automatic sprinkler system on the ceiling, the barrel storage automatic sprinkler design and the loading aisle automatic sprinkler design are not required to be balanced at the point of connection.

4005.1.4.5 Dry pipe sprinkler systems. Where dry-pipe sprinkler systems are installed, the sprinkler system shall be designed to deliver water to the most remote four sprinklers within 40 seconds.

4005.1.4.6 Small distilled spirits facilities. Fire protection for palletized storage of distilled spirits in small distilled spirits facilities not greater than 7,500 square feet (697 m2) is permitted to be in accordance with Sections 4005.1.4.6.1 through 4005.1.4.6.3.

4005.1.4.6.1 Ceiling clearance. The clearance from the top of storage to the deflector of the automatic sprinklers at the ceiling shall be a minimum of 18 inches (457 mm) and a maximum of 10 feet (3048 mm).

4005.1.4.6.2 Automatic sprinkler coverage area. The automatic sprinkler coverage area shall not exceed 80 square feet (7.4 m [2] ) per sprinkler.

4005.1.4.6.3 Fire protection scheme. The storage arrangement and automatic sprinkler system design shall be in accordance with Table 4005.1.4.6.3.

TABLE 4005.1.4.6.3—PALLETIZED STORAGE OF DISTILLED SPIRITS IN WOODEN BARRELS IN SMALL DISTILLED SPIRITS FACILITIES

PROTECTION
AREA
SPRINKLER
SYSTEM
TYPE
MAXIMUM
CEILING
HEIGHT
(feet)
MAXIMUM
STORAGE
HEIGHT
(feet)
CEILING SPRINKLER PROTECTION CEILING SPRINKLER PROTECTION CEILING SPRINKLER PROTECTION CEILING SPRINKLER PROTECTION
PROTECTION
AREA
SPRINKLER
SYSTEM
TYPE
MAXIMUM
CEILING
HEIGHT
(feet)
MAXIMUM
STORAGE
HEIGHT
(feet)
Response/Temperature
Rating/Orientation
K-Factor
(gpm/psi1/2)
Sprinkler
Density
(gpm/ft2)
Area
(square feet)
Barrel storage Wet-pipe 24 12 SR/286°F/Any ≥ 11.2 0.35 4,000
Barrel storage Wet-pipe 24 12 SR/165°F/Any ≥ 11.2 0.35 7,500
For SI: 1 foot = 304.8 mm, 1 pound per square inch (psi) = 6.895 kPa, K-factor of 1 gpm/psi1/2 = 14.395 L/min/bar1/2, °C = (°F – 32)/1.8,
1 gallon per minute per square foot = 40.75 L/min/m2.
SR = Standard Response.

4005.2 Rack storage in wooden barrels.

The rack storage of distilled spirits and wine greater than 20 percent alcohol shall be protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3.1.1 and Sections 4005.2.1 through 4005.2.3.6.

4005.2.1 Flue spaces for on-side wooden barrels. Rack storage for on-side wooden barrels shall be provided with a minimum width of 8 inches (203 mm) between adjacent rows of barrels.

4005.2.1.1 Elevated walkways. Where provided, elevated walkways between barrels shall be constructed in accordance with one of the following:

  1. Noncombustible materials that are 50 percent open.
  2. Noncombustible materials that are open less than 50 percent, provided that the walkway has a maximum width of 1 foot (305 mm) and a minimum gap of 3 inches (76 mm) is provided between the walkway and the barrel storage.
  3. Combustible materials that are provided with a row of automatic sprinklers directly beneath each walkway.

4005.2.2 Flue spaces for on-end wooden barrels. Rack storage arrangements with on-end wooden barrels shall be provided with transverse and longitudinal flue spaces with a minimum width of 6 inches (152 mm).

4005.2.3 Fire protection for rack storage. Rack storage arrangements of alcohol-water mixtures up to 75 percent alcohol in wooden barrels with sizes not exceeding 130 gallons (492 L) shall be protected in accordance with Sections 4005.2.3.1 through 4005.2.3.6.

4005.2.3.1 Hose stream allowance. The automatic sprinkler system design shall include a 500-gallon-per-minute (1900 L/min) hose stream allowance.

4005.2.3.2 Water supply duration. The automatic sprinkler system water supply duration, including hose stream demand, shall be a minimum of 1 hour.

4005.2.3.3 Dry-pipe automatic sprinkler system. Where dry-pipe automatic sprinkler systems are installed, the automatic sprinkler system shall be designed to deliver water to the most remote four sprinklers within 40 seconds.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

STORAGE OF DISTILLED SPIRITS AND WINES

4005.2.3.4 Ceiling automatic sprinkler systems. The automatic sprinkler systems installed at the ceiling shall be designed with a minimum density of 0.2 gallon per minute (0.8 L/min) per square foot with an operating area of 2,000 square feet (186 m [2] ).

4005.2.3.5 Automatic sprinkler system balancing. The automatic sprinkler system installed at the ceiling and the in-rack sprinkler system shall be balanced at the point of connection.

4005.2.3.6 Automatic sprinkler system design. The design of the automatic sprinkler system at the ceiling and the in-rack sprinkler system shall be in accordance with Table 4005.2.3.6.

TABLE 4005.2.3.6—RACK STORAGE OF DISTILLED SPIRITS IN WOODEN BARRELS

BARREL
ARRANGEMENT
SPRIN-
KLER
SYSTEM
TYPE
MAXI-
MUM
CEILING
HEIGHT
(feet)
MAXI-
MUM
STORAGE
HEIGHT
(feet)
MINIMUM
AISLE
WIDTH
(feet)
CEILING SPRINKLER PROTECTION CEILING SPRINKLER PROTECTION CEILING SPRINKLER PROTECTION IN-RACK SPRINKLER PROTECTION IN-RACK SPRINKLER PROTECTION IN-RACK SPRINKLER PROTECTION IN-RACK SPRINKLER PROTECTION
BARREL
ARRANGEMENT
SPRIN-
KLER
SYSTEM
TYPE
MAXI-
MUM
CEILING
HEIGHT
(feet)
MAXI-
MUM
STORAGE
HEIGHT
(feet)
MINIMUM
AISLE
WIDTH
(feet)
Response/
Nominal
Temperature
Rating/
Orientation
K-Factor
(gpm/psi1/2)
Design, # of
Sprinklers
@ Pressure
(psi)
Layout Response/
Nominal
Temperature
Rating/
Orientation
K-Factor
(gpm/psi1/2)
Designa, #
of Sprin-
klers @
Pressure
(psi)
On-side Wet 40 33 feet/
9 barrels
NA QR/165°F/
Pendent
14.0 12 @ 37 None None None None
On-side Wet 40 33 feet/
9 barrels
NA SR/286°F/Any ≥ 11.2 20 @ 7 Figures
4005.2.3.6(1)
and
4005.2.3.6(2)
QR/165°F/Any 8.0 6 @ 45
(one level
of in-racks)
or
12 @ 45
(more than
one level of
in racks)
On-side Dry 40 33 feet/
9 barrels
NA SR/286°F/
Upright
16.8 24 @ 25 None None None None
On-side Dry 40 33 feet/
9 barrels
NA SR/286°F/
Upright
≥ 11.2 20 @ 7 Figures
4005.2.3.6(1)
and
4005.2.3.6(2)
QR/165°F/
Upright
8.0 6 @ 45
(one level
of in-racks)
or
12 @ 45
(more than
one level of
in racks)
On-end Wet 30 25 feet/
5 barrels
8 SR/286°F/Any ≥ 11.2 50 @ 7 Figures
4005.2.3.6(3)
,
4005.2.3.6(4)
and
4005.2.3.6(5)
QR/165°F/Any ≥ 8.0 6 @ 25
(one level)
or
12 @ 25
(more than
one level)
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2, 1 pound per square inch (psi) = 6.895 kPa, K-factor of 1 gpm/psi1/2 = 14.395 L/min/bar1/2, °C = (°F – 32)/1.8.
QR = Quick Response; SR = Standard Response; NA = Not Applicable.
a. Sprinklers shall have a maximum coverage area of 100 square feet.

40-6 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

STORAGE OF DISTILLED SPIRITS AND WINES

FIGURE 4005.2.3.6(1)—IN-RACK SPRINKLER LAYOUT FOR WOODEN BARRELS ON THEIR SIDES (PLAN VIEW)

10 FT (3 M) 10 FT (3 M)

4 FT (1.2 M)

70% OPEN

8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)
8 IN (200 MM)

IN-RACK SPRINKLERS

Figure credit: FM Global Property Loss Prevention Data Sheet 7-29

FIGURE 4005.2.3.6(2)—IN-RACK SPRINKLER LAYOUT FOR WOODEN BARRELS ON THEIR SIDES (ELEVATION VIEW)

6 IN (150 MM)

3 FT (10 M)/ 30 FT (
9 BARRELS 8 BAR

3 FT (10 M)/
9 BARRELS
30 FT (
8 BAR
3 FT (10 M)/
9 BARRELS
30 FT (
8 BAR
30 FT (
8 BAR
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS
3 FT (10 M)/
9 BARRELS

IN-RACK SPRINKLERS

Figure credit: FM Global Property Loss Prevention Data Sheet 7-29

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

STORAGE OF DISTILLED SPIRITS AND WINES

FIGURE 4005.2.3.6(3)—IN-RACK SPRINKLER LAYOUT FOR SINGLE-ROW RACK OF ON-END WOODEN BARRELS

6 FT (1.8 M) MAXIMUM

PLAN VIEW MAXIMUM

ELEVATION VIEW

, = IN-RACK SPRINKLERS

Figure credit: FM Global Property Loss Prevention Data Sheet 7-29

40-8 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

STORAGE OF DISTILLED SPIRITS AND WINES

FIGURE 4005.2.3.6(4)—IN-RACK SPRINKLER LAYOUT FOR DOUBLE-ROW RACK OF ON-END WOODEN BARRELS

8 FT (2.4 M)

9 FT (2.7 M) MAXIMUM

PLAN VIEW MAXIMUM

ELEVATION VIEW

, = IN-RACK SPRINKLERS

Figure credit: FM Global Property Loss Prevention Data Sheet 7-29

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

STORAGE OF DISTILLED SPIRITS AND WINES

FIGURE 4005.2.3.6(5)—IN-RACK SPRINKLER LAYOUT FOR MULTIPLE-ROW RACK OF ON-END WOODEN BARRELS

8 FT (2.4 M)

4–5 FT (1.2–1.5 M) MAXIMUM

4–5 FT (1.2–1.5 M) MAXIMUM

4–5 FT (1.2–1.5 M) MAXIMUM

4–5 FT (1.2–1.5 M) MAXIMUM

PLAN VIEW

MAXIMUM

SECOND TIER FACE SPRINKLERS ALL TIERS LONGITUDINAL FLUE SPRINKLERS

= IN-RACK SPRINKLERS

2 TO 3 DRUMS

AND

10 – 15 FT

– (3 4.6 M) MAXIMUM

,,

2 D
2 D A 10 F
10
MA
2 DRU
AND
10 FT (3
MAXIM
DRUMS
2 DRUMS
D
AND
5 FT 1 DRU
10 FT (3 M)
6 M) AND
MAXIMUM
MUM 5 FT (1.
MAXIM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRUMS
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRUMS
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
2 DRUMS
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
AND
10 FT (3 M)
MAXIMUM
2 DRU
AND
10 FT (3
MAXIM
1 DRU
AND
5 FT (1.
MAXIM
DRUMS
D
5 FT
6 M)
MUM
2 DRUMS
AND
10 FT (3 M)
MAXIMUM
AND
10 FT (3 M)
MAXIMUM

ELEVATION VIEW

,, = IN-RACK SPRINKLERS

Figure credit: FM Global Property Loss Prevention Data Sheet 7-29

4005.3 Wine with 20 percent or less alcohol content.

The storage of wine in barrels with an alcohol content of 20 percent or less shall be protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3.1.1.

4005.4 Portable fire extinguishers.

Approved portable fire extinguishers shall be provided in accordance with Section 906.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Fire Code (Title 24, Part 9)
2025 California Fire Code (Title 24, Part 9)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REQUIREMENTS
  4. Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
  5. Chapter 5 — FIRE SERVICE FEATURES
  6. Chapter 6 — BUILDING SERVICES AND SYSTEMS
  7. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  8. Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
  9. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  10. Chapter 10 — MEANS OF EGRESS
  11. Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
  12. Chapter 12 — ENERGY SYSTEMS
  13. Chapter 20 — AVIATION FACILITIES
  14. Chapter 21 — DRY CLEANING
  15. Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
  16. Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
  17. Chapter 24 — FLAMMABLE FINISHES
  18. Chapter 25 — FRUIT AND CROP RIPENING
  19. Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
  20. Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
  21. Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
  22. Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
  23. Chapter 30 — INDUSTRIAL OVENS
  24. Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
  25. Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
  26. Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
  27. Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
  28. Chapter 35 — WELDING AND OTHER HOT WORK
  29. Chapter 36 — MARINAS
  30. Chapter 37 — COMBUSTIBLE FIBERS
  31. Chapter 38 — RESERVED
  32. Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
  33. Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
  34. Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
  35. Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
  36. Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
  37. Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
  38. Chapter 51 — AEROSOLS
  39. Chapter 52 — RESERVED
  40. Chapter 53 — COMPRESSED GASES
  41. Chapter 54 — CORROSIVE MATERIALS
  42. Chapter 55 — CRYOGENIC FLUIDS
  43. Chapter 56 — EXPLOSIVES AND FIREWORKS
  44. Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
  45. Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
  46. Chapter 59 — FLAMMABLE SOLIDS
  47. Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
  48. Chapter 61 — LIQUEFIED PETROLEUM GASES
  49. Chapter 62 — ORGANIC PEROXIDES
  50. Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
  51. Chapter 64 — PYROPHORIC MATERIALS
  52. Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
  53. Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
  54. Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
  55. Chapter 80 — REFERENCED STANDARDS
  56. Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
  57. Appendix A — BOARD OF APPEALS
  58. Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  59. Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  60. Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  61. Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  62. Appendix D — FIRE APPARATUS ACCESS ROADS
  63. Appendix E — HAZARD CATEGORIES
  64. Appendix F — HAZARD RANKING
  65. Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
  66. Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
  67. Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
  68. Appendix J — BUILDING INFORMATION SIGN
  69. Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
  70. Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
  71. Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
  72. Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
  73. Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
  74. Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
  75. Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.