Chapter 36 — MARINAS

3604 Fire Protection Equipment — 2025 California Fire Code

California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Fire Code (Title 24, Part 9) § 3604 · Effective January 1, 2026 · Official source: Building Standards Commission

3604.1 General.

Piers, marinas and wharves with facilities for mooring or servicing five or more vessels, and marine motor fueldispensing facilities shall be equipped with fire protection equipment in accordance with Sections 3604.2 through 3604.6.

Exceptions & meaning →

3604.2 Standpipes.

Marinas and boatyards shall be equipped throughout with standpipe systems in accordance with NFPA 303. Systems shall be provided with hose connections located such that no point on the marina pier or float system exceeds 150 feet (15 240 mm) from a standpipe hose connection.

3604.2.1 Identification of standpipe outlets. Standpipe hose connection locations shall be clearly identified by a flag or other approved means designed to be readily visible from the pier accessing the float system.

Exceptions & meaning →

3604.3 Access and water supply.

Piers and wharves shall be provided with fire apparatus access roads and water-supply systems with on-site fire hydrants where required by the fire code official. Such roads and water systems shall be provided and maintained in accordance with Sections 503 and 507.

MARINAS

Exceptions & meaning →

3604.4 Portable fire extinguishers.

One portable fire extinguisher of the ordinary (moderate) hazard type shall be provided at each required standpipe hose connection. Additional portable fire extinguishers, suitable for the hazards involved, shall be provided and maintained in accordance with Section 906.

Exceptions & meaning →

3604.5 Communications.

A telephone not requiring a coin to operate or other approved, clearly identified means to notify the fire department shall be provided on the site in a location approved by the fire code official.

Exceptions & meaning →

3604.6 Emergency operations staging areas.

Space shall be provided on all float systems for the staging of emergency equipment. Emergency operation staging areas shall provide a minimum of 4 feet wide by 10 feet long (1219 mm by 3048 mm) clear area exclusive of walkways and shall be located at each standpipe hose connection. Emergency operation staging areas shall be provided with a curb or barrier having a minimum height of 4 inches (102 mm) and maximum space between the bottom edge and the surface of the staging area of 2 inches (51 mm) on the outboard sides of the staging area.

An approved sign reading “FIRE EQUIPMENT STAGING AREA—KEEP CLEAR” shall be provided at each staging area.

Exceptions & meaning →