Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
3311 Additional Safeguards for Types I and II Construction — 2025 California Fire Code
California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Fire Code (Title 24, Part 9) § 3311 · Effective January 1, 2026 · Official source: Building Standards Commission
3311.1 Separations between construction areas.¶
Separations used in Type I and Type II construction to separate construction areas from occupied portions of the building shall be constructed of materials that comply with one of the following:
Noncombustible materials.
Materials that exhibit a flame spread index not exceeding 25 when tested in accordance with ASTM E84 or UL 723.
Materials exhibiting a peak heat release rate not exceeding 300 kW/m [2] when tested in accordance with ASTM E1354 at an incident heat flux of 50 kW/m [2] in the horizontal orientation on specimens at the thickness intended for use.
3311.2 Group I-2 separations.¶
For additional requirements for occupancies in Group I-2, see Section 1105.12 and Section 1105.12.1.