2303.1 Location of dispensing devices. Dispensing devices shall be located as follows:

2303.1 Location of dispensing devices. Dispensing devices shall be located as follows: 1. Ten feet (3048 mm) or more from lot lines. 2. Ten feet (3048 mm) or more from buildings having combustible exterior wall surfaces or buildings having noncombustible exterior wall surfaces that are not part of a 1-hour fire-resistance-rated assembly or buildings having combustible overhangs. Exception: Canopies constructed in accordance with the California Building Code providing weather protection for the fuel islands. 3. Such that all portions of the vehicle being fueled will be on the premises of the…

2303.2 Emergency disconnect switches.

2303.2 Emergency disconnect switches. An approved emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be provided with ready access and shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be provided with ready access and be installed at an approved location. Such devices…