Chapter 20 — AVIATION FACILITIES
Section 2005 — PORTABLE FIRE EXTINGUISHERS
2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
2005.1 General. ¶
Portable fire extinguishers suitable for flammable or combustible liquid and electrical-type fires shall be provided as specified in Sections 2005.2 through 2005.6 and Section 906. Extinguishers required by this section shall be inspected and maintained in accordance with Section 906.
2005.2 On towing vehicles. ¶
Vehicles used for towing aircraft shall be equipped with not less than one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 20-B:C.
2005.3 On welding apparatus. ¶
Welding apparatus shall be equipped with not less than one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 2-A:20-B:C.
2005.4 On aircraft fuel-servicing tank vehicles. ¶
Aircraft fuel-servicing tank vehicles shall be equipped with not less than two listed portable fire extinguishers complying with Section 906, each having a minimum rating of 20-B:C. A portable fire extinguisher shall be provided with ready access from either side of the vehicle.
2005.5 On hydrant fuel-servicing vehicles. ¶
Hydrant fuel-servicing vehicles shall be equipped with not less than one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 20-B:C.
2005.6 At fuel-dispensing stations. ¶
Portable fire extinguishers at fuel-dispensing stations shall be located such that pumps or dispensers are not more than 75 feet (22 860 mm) from one such extinguisher. Fire extinguishers shall be provided as follows:
- Where the open-hose discharge capacity of the fueling system is not more than 200 gallons per minute (13 L/s), not less than two listed portable fire extinguishers complying with Section 906 and having a minimum rating of 20-B:C shall be provided.
- Where the open-hose discharge capacity of the fueling system is more than 200 gallons per minute (13 L/s) but not more than 350 gallons per minute (22 L/s), not less than one listed wheeled extinguisher complying with Section 906 and having a minimum extinguishing rating of 80-B:C, and a minimum agent capacity of 125 pounds (57 kg), shall be provided.
- Where the open-hose discharge capacity of the fueling system is more than 350 gallons per minute (22 L/s), not less than two listed wheeled extinguishers complying with Section 906 and having a minimum rating of 80-B:C each, and a minimum capacity agent of 125 pounds (57 kg) each, shall be provided.
2005.7 Fire extinguisher access. ¶
Access to portable fire extinguishers required by this chapter shall be maintained at all times. Where necessary, provisions shall be made to clear accumulations of snow, ice and other forms of weather-induced obstructions.
2005.7.1 Cabinets. Cabinets and enclosed compartments used to house portable fire extinguishers shall be clearly marked with the words “FIRE EXTINGUISHER” in letters not less than 2 inches (51 mm) high. Cabinets and compartments shall be provided with ready access at all times.
2005.8 Reporting use. ¶
Use of a fire extinguisher under any circumstances shall be immediately reported to the manager of the airport and the fire code official.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Fire Code (Title 24, Part 9)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REQUIREMENTS
- Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
- Chapter 5 — FIRE SERVICE FEATURES
- Chapter 6 — BUILDING SERVICES AND SYSTEMS
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
- Chapter 12 — ENERGY SYSTEMS
- Chapter 21 — DRY CLEANING
- Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
- Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
- Chapter 24 — FLAMMABLE FINISHES
- Chapter 25 — FRUIT AND CROP RIPENING
- Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
- Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
- Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
- Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
- Chapter 30 — INDUSTRIAL OVENS
- Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
- Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
- Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
- Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
- Chapter 35 — WELDING AND OTHER HOT WORK
- Chapter 36 — MARINAS
- Chapter 37 — COMBUSTIBLE FIBERS
- Chapter 38 — RESERVED
- Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
- Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
- Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
- Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
- Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
- Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
- Chapter 51 — AEROSOLS
- Chapter 52 — RESERVED
- Chapter 53 — COMPRESSED GASES
- Chapter 54 — CORROSIVE MATERIALS
- Chapter 55 — CRYOGENIC FLUIDS
- Chapter 56 — EXPLOSIVES AND FIREWORKS
- Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
- Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
- Chapter 59 — FLAMMABLE SOLIDS
- Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
- Chapter 61 — LIQUEFIED PETROLEUM GASES
- Chapter 62 — ORGANIC PEROXIDES
- Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
- Chapter 64 — PYROPHORIC MATERIALS
- Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
- Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
- Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
- Chapter 80 — REFERENCED STANDARDS
- Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
- Appendix A — BOARD OF APPEALS
- Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix D — FIRE APPARATUS ACCESS ROADS
- Appendix E — HAZARD CATEGORIES
- Appendix F — HAZARD RANKING
- Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
- Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
- Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
- Appendix J — BUILDING INFORMATION SIGN
- Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
- Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
- Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
- Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
- Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
- Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
- Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…