Skip to content

Earlier editions: 20222019

Chapter 20 — AVIATION FACILITIES

2005 Portable Fire Extinguishers — 2025 California Fire Code

California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Fire Code (Title 24, Part 9) § 2005 · Effective January 1, 2026 · Official source: Building Standards Commission

2005.1 General.

Portable fire extinguishers suitable for flammable or combustible liquid and electrical-type fires shall be provided as specified in Sections 2005.2 through 2005.6 and Section 906. Extinguishers required by this section shall be inspected and maintained in accordance with Section 906.

Exceptions & meaning →

2005.2 On towing vehicles.

Vehicles used for towing aircraft shall be equipped with not less than one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 20-B:C.

Exceptions & meaning →

2005.3 On welding apparatus.

Welding apparatus shall be equipped with not less than one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 2-A:20-B:C.

Exceptions & meaning →

2005.4 On aircraft fuel-servicing tank vehicles.

Aircraft fuel-servicing tank vehicles shall be equipped with not less than two listed portable fire extinguishers complying with Section 906, each having a minimum rating of 20-B:C. A portable fire extinguisher shall be provided with ready access from either side of the vehicle.

Exceptions & meaning →

2005.5 On hydrant fuel-servicing vehicles.

Hydrant fuel-servicing vehicles shall be equipped with not less than one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 20-B:C.

Exceptions & meaning →

2005.6 At fuel-dispensing stations.

Portable fire extinguishers at fuel-dispensing stations shall be located such that pumps or dispensers are not more than 75 feet (22 860 mm) from one such extinguisher. Fire extinguishers shall be provided as follows:

  1. Where the open-hose discharge capacity of the fueling system is not more than 200 gallons per minute (13 L/s), not less than two listed portable fire extinguishers complying with Section 906 and having a minimum rating of 20-B:C shall be provided.
  2. Where the open-hose discharge capacity of the fueling system is more than 200 gallons per minute (13 L/s) but not more than 350 gallons per minute (22 L/s), not less than one listed wheeled extinguisher complying with Section 906 and having a minimum extinguishing rating of 80-B:C, and a minimum agent capacity of 125 pounds (57 kg), shall be provided.
  3. Where the open-hose discharge capacity of the fueling system is more than 350 gallons per minute (22 L/s), not less than two listed wheeled extinguishers complying with Section 906 and having a minimum rating of 80-B:C each, and a minimum capacity agent of 125 pounds (57 kg) each, shall be provided.
Exceptions & meaning →

2005.7 Fire extinguisher access.

Access to portable fire extinguishers required by this chapter shall be maintained at all times. Where necessary, provisions shall be made to clear accumulations of snow, ice and other forms of weather-induced obstructions.

2005.7.1 Cabinets. Cabinets and enclosed compartments used to house portable fire extinguishers shall be clearly marked with the words “FIRE EXTINGUISHER” in letters not less than 2 inches (51 mm) high. Cabinets and compartments shall be provided with ready access at all times.

Exceptions & meaning →

2005.8 Reporting use.

Use of a fire extinguisher under any circumstances shall be immediately reported to the manager of the airport and the fire code official.