Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
Section B105 — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
B105.1 One- and two-family dwellings, Group R-3 and R-4 buildings and townhouses. ¶
The minimum fire-flow and flow duration requirements for one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Tables B105.1(1) and B105.1(2).
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX B—FIRE-FLOW REQUIREMENTS FOR BUILDINGS
TABLE B105.1(1)—REQUIRED FIRE FLOW FOR ONE- AND
TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
| FIRE-FLOW CALCULATION AREA (square feet) |
AUTOMATIC SPRINKLER SYSTEM (Design Standard) |
MINIMUM FIRE FLOW (gallons per minute) |
FLOW DURATION (hours) |
|---|---|---|---|
| 0–3,600 | No automatic sprinkler system | 1,000 | 1 |
| 3,601 and greater | No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) at the required fire-flow rate |
| 0–3,600 | Section 903.3.1.3 of the_California Fire Code_ or Section P2904 of the_California Residential Code_ |
500 | 1/2 |
| 3,601 and greater | Section 903.3.1.3 of the_California Fire Code_ or Section P2904 of the_California Residential Code_ |
1/2 value in Table B105.1(2) | 1 |
| For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m. |
TABLE B105.1(2)—REFERENCE TABLE FOR TABLES B105.1(1) AND B105.2
| FIRE-FLOW CALCULATION AREA (square feet) | FIRE-FLOW CALCULATION AREA (square feet) | FIRE-FLOW CALCULATION AREA (square feet) | FIRE-FLOW CALCULATION AREA (square feet) | FIRE-FLOW CALCULATION AREA (square feet) | FIRE FLOW (gallons per minute)b |
FLOW DURATION (hours) |
|---|---|---|---|---|---|---|
| Types IA and IBa | Types IIA and IIIAa | Types IV and V-Aa | Types IIB and IIIBa | Type V-Ba | Type V-Ba | Type V-Ba |
| 0–22,700 | 0–12,700 | 0–8,200 | 0–5,900 | 0–3,600 | 1,500 | 2 |
| 22,701–30,200 | 12,701–17,000 | 8,201–10,900 | 5,901–7,900 | 3,601–4,800 | 1,750 | 1,750 |
| 30,201–38,700 | 17,001–21,800 | 10,901–12,900 | 7,901–9,800 | 4,801–6,200 | 2,000 | 2,000 |
| 38,701–48,300 | 21,801–24,200 | 12,901–17,400 | 9,801–12,600 | 6,201–7,700 | 2,250 | 2,250 |
| 48,301–59,000 | 24,201–33,200 | 17,401–21,300 | 12,601–15,400 | 7,701–9,400 | 2,500 | 2,500 |
| 59,001–70,900 | 33,201–39,700 | 21,301–25,500 | 15,401–18,400 | 9,401–11,300 | 2,750 | 2,750 |
| 70,901–83,700 | 39,701–47,100 | 25,501–30,100 | 18,401–21,800 | 11,301–13,400 | 3,000 | 3 |
| 83,701–97,700 | 47,101–54,900 | 30,101–35,200 | 21,801–25,900 | 13,401–15,600 | 3,250 | 3,250 |
| 97,701–112,700 | 54,901–63,400 | 35,201–40,600 | 25,901–29,300 | 15,601–18,000 | 3,500 | 3,500 |
| 112,701–128,700 | 63,401–72,400 | 40,601–46,400 | 29,301–33,500 | 18,001–20,600 | 3,750 | 3,750 |
| 128,701–145,900 | 72,401–82,100 | 46,401–52,500 | 33,501–37,900 | 20,601–23,300 | 4,000 | 4 |
| 145,901–164,200 | 82,101–92,400 | 52,501–59,100 | 37,901–42,700 | 23,301–26,300 | 4,250 | 4,250 |
| 164,201–183,400 | 92,401–103,100 | 59,101–66,000 | 42,701–47,700 | 26,301–29,300 | 4,500 | 4,500 |
| 183,401–203,700 | 103,101–114,600 | 66,001–73,300 | 47,701–53,000 | 29,301–32,600 | 4,750 | 4,750 |
| 203,701–225,200 | 114,601–126,700 | 73,301–81,100 | 53,001–58,600 | 32,601–36,000 | 5,000 | 5,000 |
| 225,201–247,700 | 126,701–139,400 | 81,101–89,200 | 58,601–65,400 | 36,001–39,600 | 5,250 | 5,250 |
| 247,701–271,200 | 139,401–152,600 | 89,201–97,700 | 65,401–70,600 | 39,601–43,400 | 5,500 | 5,500 |
| 271,201–295,900 | 152,601–166,500 | 97,701–106,500 | 70,601–77,000 | 43,401–47,400 | 5,750 | 5,750 |
| 295,901–Greater | 166,501–Greater | 106,501–115,800 | 77,001–83,700 | 47,401–51,500 | 6,000 | 6,000 |
| — | — | 115,801–125,500 | 83,701–90,600 | 51,501–55,700 | 6,250 | 6,250 |
| — | — | 125,501–135,500 | 90,601–97,900 | 55,701–60,200 | 6,500 | 6,500 |
| — | — | 135,501–145,800 | 97,901–106,800 | 60,201–64,800 | 6,750 | 6,750 |
| — | — | 145,801–156,700 | 106,801–113,200 | 64,801–69,600 | 7,000 | 7,000 |
| — | — | 156,701–167,900 | 113,201–121,300 | 69,601–74,600 | 7,250 | 7,250 |
| — | — | 167,901–179,400 | 121,301–129,600 | 74,601–79,800 | 7,500 | 7,500 |
| — | — | 179,401–191,400 | 129,601–138,300 | 79,801–85,100 | 7,750 | 7,750 |
| — | — | 191,401–Greater | 138,301–Greater | 85,101–Greater | 8,000 | 8,000 |
| For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa. a. Types of construction are based on the_California Building Code_. b. Measured at 20 psi residual pressure. |
APPENDIX B-4 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX B—FIRE-FLOW REQUIREMENTS FOR BUILDINGS
B105.2 Buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses. ¶
The minimum fireflow and flow duration for buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Tables B105.1(2) and B105.2.
Exception: [SFM] Group B, S-2 and U occupancies having a floor area not exceeding 1,000 square feet, primarily constructed of noncombustible exterior walls with wood or steel roof framing, having a Class A roof assembly, with uses limited to the following or similar uses:
1. California State Parks buildings of an accessory nature (restrooms). 2. Safety roadside rest areas, (SRRA), public restrooms. 3. Truck inspection facilities, (TIF), CHP office space and vehicle inspection bays. 4. Sand/salt storage buildings, storage of sand and salt.
TABLE B105.2—REQUIRED FIRE FLOW FOR BUILDINGS OTHER THAN
ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
| AUTOMATIC SPRINKLER SYSTEM (Design Standard) |
MINIMUM FIRE FLOW (gallons per minute) |
FLOW DURATION (hours) |
|---|---|---|
| No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) |
| Section 903.3.1.1 of the_California Fire Code_ | 25% of the value in Table B105.1(2)a | Duration in Table B105.1(2) at the reduced flow rate |
| Section 903.3.1.2 of the_California Fire Code_ | 25% of the value in Table B105.1(2)b | Duration in Table B105.1(2) at the reduced flow rate |
| For SI: 1 gallon per minute = 3.785 L/m. a. The reduced fire flow shall be not less than 1,000 gallons per minute. b. The reduced fire flow shall be not less than 1,500 gallons per minute. |
B105.3 Water supply for buildings equipped with an automatic sprinkler system. ¶
For buildings equipped with an approved automatic sprinkler system, the water supply shall be capable of providing the greater of:
- The automatic sprinkler system demand, including hose stream allowance.
- The required fire flow.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Fire Code (Title 24, Part 9)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REQUIREMENTS
- Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
- Chapter 5 — FIRE SERVICE FEATURES
- Chapter 6 — BUILDING SERVICES AND SYSTEMS
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
- Chapter 12 — ENERGY SYSTEMS
- Chapter 20 — AVIATION FACILITIES
- Chapter 21 — DRY CLEANING
- Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
- Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
- Chapter 24 — FLAMMABLE FINISHES
- Chapter 25 — FRUIT AND CROP RIPENING
- Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
- Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
- Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
- Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
- Chapter 30 — INDUSTRIAL OVENS
- Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
- Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
- Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
- Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
- Chapter 35 — WELDING AND OTHER HOT WORK
- Chapter 36 — MARINAS
- Chapter 37 — COMBUSTIBLE FIBERS
- Chapter 38 — RESERVED
- Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
- Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
- Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
- Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
- Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
- Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
- Chapter 51 — AEROSOLS
- Chapter 52 — RESERVED
- Chapter 53 — COMPRESSED GASES
- Chapter 54 — CORROSIVE MATERIALS
- Chapter 55 — CRYOGENIC FLUIDS
- Chapter 56 — EXPLOSIVES AND FIREWORKS
- Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
- Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
- Chapter 59 — FLAMMABLE SOLIDS
- Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
- Chapter 61 — LIQUEFIED PETROLEUM GASES
- Chapter 62 — ORGANIC PEROXIDES
- Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
- Chapter 64 — PYROPHORIC MATERIALS
- Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
- Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
- Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
- Chapter 80 — REFERENCED STANDARDS
- Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
- Appendix A — BOARD OF APPEALS
-
▸ Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
- Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
- Appendix D — FIRE APPARATUS ACCESS ROADS
- Appendix E — HAZARD CATEGORIES
- Appendix F — HAZARD RANKING
- Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
- Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
- Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
- Appendix J — BUILDING INFORMATION SIGN
- Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
- Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
- Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
- Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
- Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
- Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
- Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…