B105.1 One- and two-family dwellings, Group R-3 and R-4 buildings and townhouses.

The minimum fire-flow and flow duration requirements for one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Tables B105.1(1) and B105.1(2).

APPENDIX B—FIRE-FLOW REQUIREMENTS FOR BUILDINGS

TABLE B105.1(1)—REQUIRED FIRE FLOW FOR ONE- AND
TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES

FIRE-FLOW
CALCULATION AREA
(square feet)
AUTOMATIC
SPRINKLER SYSTEM
(Design Standard)
MINIMUM
FIRE FLOW
(gallons per minute)
FLOW
DURATION
(hours)
0–3,600 No automatic sprinkler system 1,000 1
3,601 and greater No automatic sprinkler system Value in Table B105.1(2) Duration in Table B105.1(2) at
the required fire-flow rate
0–3,600 Section 903.3.1.3 of the_California Fire Code_ or
Section P2904 of the_California Residential Code_
500 1/2
3,601 and greater Section 903.3.1.3 of the_California Fire Code_ or
Section P2904 of the_California Residential Code_
1/2 value in Table B105.1(2) 1
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m.

TABLE B105.1(2)—REFERENCE TABLE FOR TABLES B105.1(1) AND B105.2

FIRE-FLOW CALCULATION AREA (square feet) FIRE-FLOW CALCULATION AREA (square feet) FIRE-FLOW CALCULATION AREA (square feet) FIRE-FLOW CALCULATION AREA (square feet) FIRE-FLOW CALCULATION AREA (square feet) FIRE FLOW
(gallons per
minute)b
FLOW
DURATION
(hours)
Types IA and IBa Types IIA and IIIAa Types IV and V-Aa Types IIB and IIIBa Type V-Ba Type V-Ba Type V-Ba
0–22,700 0–12,700 0–8,200 0–5,900 0–3,600 1,500 2
22,701–30,200 12,701–17,000 8,201–10,900 5,901–7,900 3,601–4,800 1,750 1,750
30,201–38,700 17,001–21,800 10,901–12,900 7,901–9,800 4,801–6,200 2,000 2,000
38,701–48,300 21,801–24,200 12,901–17,400 9,801–12,600 6,201–7,700 2,250 2,250
48,301–59,000 24,201–33,200 17,401–21,300 12,601–15,400 7,701–9,400 2,500 2,500
59,001–70,900 33,201–39,700 21,301–25,500 15,401–18,400 9,401–11,300 2,750 2,750
70,901–83,700 39,701–47,100 25,501–30,100 18,401–21,800 11,301–13,400 3,000 3
83,701–97,700 47,101–54,900 30,101–35,200 21,801–25,900 13,401–15,600 3,250 3,250
97,701–112,700 54,901–63,400 35,201–40,600 25,901–29,300 15,601–18,000 3,500 3,500
112,701–128,700 63,401–72,400 40,601–46,400 29,301–33,500 18,001–20,600 3,750 3,750
128,701–145,900 72,401–82,100 46,401–52,500 33,501–37,900 20,601–23,300 4,000 4
145,901–164,200 82,101–92,400 52,501–59,100 37,901–42,700 23,301–26,300 4,250 4,250
164,201–183,400 92,401–103,100 59,101–66,000 42,701–47,700 26,301–29,300 4,500 4,500
183,401–203,700 103,101–114,600 66,001–73,300 47,701–53,000 29,301–32,600 4,750 4,750
203,701–225,200 114,601–126,700 73,301–81,100 53,001–58,600 32,601–36,000 5,000 5,000
225,201–247,700 126,701–139,400 81,101–89,200 58,601–65,400 36,001–39,600 5,250 5,250
247,701–271,200 139,401–152,600 89,201–97,700 65,401–70,600 39,601–43,400 5,500 5,500
271,201–295,900 152,601–166,500 97,701–106,500 70,601–77,000 43,401–47,400 5,750 5,750
295,901–Greater 166,501–Greater 106,501–115,800 77,001–83,700 47,401–51,500 6,000 6,000
— — 115,801–125,500 83,701–90,600 51,501–55,700 6,250 6,250
— — 125,501–135,500 90,601–97,900 55,701–60,200 6,500 6,500
— — 135,501–145,800 97,901–106,800 60,201–64,800 6,750 6,750
— — 145,801–156,700 106,801–113,200 64,801–69,600 7,000 7,000
— — 156,701–167,900 113,201–121,300 69,601–74,600 7,250 7,250
— — 167,901–179,400 121,301–129,600 74,601–79,800 7,500 7,500
— — 179,401–191,400 129,601–138,300 79,801–85,100 7,750 7,750
— — 191,401–Greater 138,301–Greater 85,101–Greater 8,000 8,000
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa.
a. Types of construction are based on the_California Building Code_.
b. Measured at 20 psi residual pressure.

APPENDIX B-4 2025 CALIFORNIA FIRE CODE

APPENDIX B—FIRE-FLOW REQUIREMENTS FOR BUILDINGS

Exceptions & meaning →

B105.2 Buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses.

The minimum fireflow and flow duration for buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Tables B105.1(2) and B105.2.

Exception: [SFM] Group B, S-2 and U occupancies having a floor area not exceeding 1,000 square feet, primarily constructed of noncombustible exterior walls with wood or steel roof framing, having a Class A roof assembly, with uses limited to the following or similar uses:

1. California State Parks buildings of an accessory nature (restrooms). 2. Safety roadside rest areas, (SRRA), public restrooms. 3. Truck inspection facilities, (TIF), CHP office space and vehicle inspection bays. 4. Sand/salt storage buildings, storage of sand and salt.

TABLE B105.2—REQUIRED FIRE FLOW FOR BUILDINGS OTHER THAN
ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES

AUTOMATIC SPRINKLER SYSTEM
(Design Standard)
MINIMUM FIRE FLOW
(gallons per minute)
FLOW DURATION
(hours)
No automatic sprinkler system Value in Table B105.1(2) Duration in Table B105.1(2)
Section 903.3.1.1 of the_California Fire Code_ 25% of the value in Table B105.1(2)a Duration in Table B105.1(2) at the reduced flow rate
Section 903.3.1.2 of the_California Fire Code_ 25% of the value in Table B105.1(2)b Duration in Table B105.1(2) at the reduced flow rate
For SI: 1 gallon per minute = 3.785 L/m.
a. The reduced fire flow shall be not less than 1,000 gallons per minute.
b. The reduced fire flow shall be not less than 1,500 gallons per minute.
Exceptions & meaning →

B105.3 Water supply for buildings equipped with an automatic sprinkler system.

For buildings equipped with an approved automatic sprinkler system, the water supply shall be capable of providing the greater of:

  1. The automatic sprinkler system demand, including hose stream allowance.
  2. The required fire flow.