Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
Section 321 — [BSC, DSA-SS & DSA-SS/CC]—METHOD B
2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
321.1 The existing or retrofitted structure shall be demonstrated to have the… ¶
specified earthquake ground motions and meet the seismic performance requirements of Section 317. The registered design professional shall provide an evaluation of the response of the existing structure in its modified configuration and condition to the ground motions specified. If the building’s seismic performance is evaluated as satisfactory and the peer reviewer(s) and the enforcement agency concurs, then no further structural retrofit and/or repair of the lateral load-resisting system is required.
When the evaluation indicates the building does not meet the required performance levels given in Table 317.5 for the risk category, then a retrofit and/or repair design shall be prepared that provides a structure that meets these performance objectives and reflects the appropriate consideration of existing conditions. Any approach to analysis and design is permitted to be used, provided that the approach shall be rational, shall be consistent with the established principals of mechanics and shall use the known performance characteristics of materials and assemblages under reversing loads typical of severe earthquake ground motions.
Exception: Further consideration of the structure’s seismic performance may be waived by the enforcement agency if both the registered design professional and peer reviewer(s) conclude that the structural system can be expected to perform at least as well as required by the provisions of this section without completing an analysis of the structure’s compliance with these requirements. A detailed report shall be submitted to the responsible building official that presents the reasons and basis for this conclusion. This report shall be prepared by the registered design professional. The peer reviewer(s) shall concur in this conclusion and affirm to it in writing. The building official shall either approve this decision or require completion of the indicated work specified in this section prior to approval.
321.2 The approach, models, analysis procedures, assumptions on material and system… ¶
reviewed in accordance with the requirements of Section 322 and accepted by the peer reviewer(s).
Exceptions: 1. The enforcement agency may perform the work of peer review when qualified staff is available within the jurisdiction. 2. The enforcement agency may modify or waive the requirements for peer review when appropriate.
321.2.1 The approach used in the development of the design shall be acceptable to the peer reviewer and the enforcement agency and shall be the same method as used in the evaluation of the building. Approaches that are specifically tailored to the type of building, construction materials and specific building characteristics may be used, if they are acceptable to the independent peer reviewer. The use of Method A allowed procedures may also be used under Method B.
321.2.2 Any method of analysis may be used, subject to acceptance by the peer reviewer(s) and the building official. The general requirements given in ASCE 41, Chapters 6 and 7, shall be complied with unless exceptions are accepted by the peer reviewer(s) and building official. Use of other than ASCE 41 procedures in Method B requires building official concurrence before implementation.
321.2.3 Prior to implementation, the procedures, methods, material assumptions and acceptance/rejection criteria proposed by the registered design professional will be peer reviewed as provided in Section 322. Where nonlinear procedures are used, prior to any analysis, the representation of the seismic ground motion shall be reviewed and approved by the peer reviewer(s) and the building official.
[DSA-SS, DSA-SS/CC] For public school and community college projects, the representation of the seismic ground motion shall be reviewed and approved by the California Geological Survey.
321.2.4 The conclusions and design decisions shall be reviewed and accepted by the peer reviewer(s) and the building official.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Existing Building Code (Title 24, Part 10)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
-
▸ Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
Overview- Section 301 — ADMINISTRATION
- Section 302 — GENERAL PROVISIONS
- Section 303 — STORM SHELTERS
- Section 304 — STRUCTURAL DESIGN LOADS AND EVALUATION AND DESIG…
- Section 305 — IN-SITU LOAD TESTS
- Section 306 — ACCESSIBILITY FOR EXISTING BUILDINGS
- Section 307 — SMOKE ALARMS
- Section 308 — CARBON MONOXIDE DETECTION
- Section 309 — ADDITIONS AND REPLACEMENTS OF EXTERIOR WALL COVE…
- Section 310 — [OSHPD 1R, 2 AND 5]—SERVICES/SYSTEMS AND UTILITIES
- Section 311 — [OSHPD 1R, 2 AND 5]—MEANS OF EGRESS
- Section 312 — [OSHPD 1R]—HOSPITAL SPC AND FREESTANDING BUILDIN…
- Section 313 — [SFM]—EXISTING GROUP R-1 AND GROUP R-2 OCCUPANCIES
- Section 314 — [SFM]—EXISTING HIGH-RISE BUILDINGS
- Section 315 — [SFM]—EXISTING GROUP I OCCUPANCIES
- Section 316 — [SFM]—EXISTING GROUP L OCCUPANCIES
- Section 317 — [BSC, DSA-SS & DSA-SS/CC]—EARTHQUAKE EVALUATION …
- Section 318 — [BSC, DSA-SS & DSA-SS/CC]—DEFINITIONS
- Section 319 — [BSC, DSA-SS & DSA-SS/CC]—SEISMIC CRITERIA SELEC…
- Section 320 — [BSC, DSA-SS & DSA-SS/CC]—METHOD A
- Section 321 — [BSC, DSA-SS & DSA-SS/CC]—METHOD B
- Section 322 — [BSC, DSA-SS & DSA-SS/CC]—PEER REVIEW REQUIREMENTS
- Section 323 — [DSA-SS, DSA-SS/CC]—ADDITIONAL REQUIREMENTS FOR …
- Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 4A — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS—LEVEL 1
- Chapter 8 — ALTERATIONS—LEVEL 2
- Chapter 9 — ALTERATIONS—LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
- Chapter 16 — REFERENCED STANDARDS
- Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
- Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
- Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
- Appendix D — BOARD OF APPEALS
- Appendix E — TEMPORARY EMERGENCY USES
- Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…