Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
Section 313 — [SFM]—EXISTING GROUP R-1 AND GROUP R-2 OCCUPANCIES
2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
313.1 Scope. ¶
313.1 Scope. The provisions of this section are intended to maintain or increase the current degree of public safety, health and general welfare in existing buildings classified as Group R Occupancies. 313.1.1 Application. In accordance with Health and Safety Code Section 13143.2, the provisions of Sections 313.2 through 313.12 shall only apply to multiple-story structures existing on January 1, 1975, let for human habitation, including, and limited to, apartment houses, hotels and motels wherein rooms used for sleeping are let above the ground floor.
313.2 Number of exits. ¶
313.2 Number of exits. Every apartment and every other sleeping room shall have access to not less than two exits when the occupant load is 10 or more (exits need not be directly from the apartment or sleeping room). A fire escape as specified herein may be used as one required exit. Subject to approval of the authority having jurisdiction, a ladder device as specified herein may be used in lieu of a fire escape when the construction feature or the location of the building on the property cause the installation of a fire escape to be impractical.
313.3 Stair construction. ¶
313.3 Stair construction. All stairs shall have a minimum run of 9 inches (229 mm) and a maximum rise of 8 inches (203 mm) and a minimum width exclusive of handrails of 30 inches (762 mm). Every stairway shall have at least one handrail. A landing having a minimum horizontal dimension of 30 inches (762 mm) shall be provided at each point of access to the stairway.
313.4 Interior stairways. ¶
313.4 Interior stairways. Every interior stairway shall be enclosed with walls of not less than 1-hour fire-resistive construction. Where existing partitions form part of a stairwell enclosure, wood lath and plaster in good condition will be acceptable in lieu of 1-hour fire- resistive construction. Doors to such enclosures shall be protected by a self-closing door equivalent to a solid wood door with a thickness of not less than 1 [3] / 4 inches (44.5 mm). Enclosures shall include all landings between flights and any corridors, passageways or public rooms necessary for continuous exit to the…
313.5 Exterior stairways. ¶
313.5 Exterior stairways. Exterior stairways shall be noncombustible or of wood of not less than 2-inch (51 mm) nominal thickness with solid treads and risers.
313.6 Fire escapes, exit ladder devices. ¶
313.6 Fire escapes, exit ladder devices. Fire escapes may be used as one means of egress if the pitch does not exceed 60 degrees, the width is not less than 18 inches (457 mm), the treads are not less than 4 inches (102 mm) wide, and they extend to the ground or are provided with counterbalanced stairs reaching to the ground. Access shall be by an opening having a minimum dimension of 29 inches (737 mm) when open. The sill shall not be more than 30 inches (762 mm) above the floor and landing. A ladder device, when used in lieu of a fire escape, shall conform to Section 313.6.1 and the…
313.7 Doors and openings. ¶
313.7 Doors and openings. Exit doors and openings shall meet the requirements of Sections 1008.1.2, 1008.8.1.8, 1008.1.9 and 708.6 of the California Building Code. Doors shall not reduce the required width of stairway more than 6 inches (152 mm) when open. Transoms and openings other than doors from corridors to rooms shall be fixed closed and shall be covered with a minimum of [3] / 4 -inch (19 mm) plywood or [1] / 2 -inch (13 mm) gypsum wallboard or equivalent material. Exceptions: 1. Existing solid-bonded wood-core doors 1 [3] / 8 inches thick (34.9 mm), or their equivalent may be…
313.8 Exit signs. ¶
313.8 Exit signs. Every exit doorway or change of direction of a corridor shall be marked with a well-lighted exit sign having letters at least 5 inches (127 mm) high.
313.9 Enclosure of vertical openings. ¶
313.9 Enclosure of vertical openings. Elevators, shafts, ducts and other vertical openings shall be enclosed as required for stairways in Section 313.4 or by wired glass set in metal frames. Doors shall be noncombustible or as regulated in Section 313.4.
313.10 Separation of occupancies. ¶
313.10 Separation of occupancies. Occupancy separations shall be provided as specified in Section 508 of the California Building Code. Lobbies and public dining rooms, not including cocktail lounges, shall not require a separation if the kitchen is so separated from the dining room. Every room containing a boiler or central heating plant shall be separated from the rest of the building by not less than a one-hour fire-resistive occupancy separation. Exception: A separation shall not be required for such rooms with equipment serving only one dwelling unit.
313.11 Equivalent protection. ¶
313.11 Equivalent protection. In lieu of the separation of occupancies required by Section 313.10, equivalent protection may be permitted when approved by the enforcement agency. Exception: The provisions of Sections 313.3 through 313.11 above shall not apply to any existing apartment house, hotel or motel having floors (as measured from the top of the floor surface) used for human occupancy located more than 75 feet (22 860 mm) above the lowest floor level having building access which is subject to the provisions of Section 314 and the California Fire Code ~~, r~~ elating to existing…
313.12 Fire alarms. ¶
313.12 Fire alarms. 313.12.1 General. Every apartment house three or more stories in height or containing more than 15 apartments, every hotel three or more stories in height or containing 20 or more guest rooms, shall have installed therein an automatic or manually operated fire alarm system. Such fire alarm systems shall be so designed that all occupants of the building may be warned simultaneously and shall be in accordance with the California Fire Code. See Section 314.14 for special requirements in buildings over 75 feet (22 860 mm) in height. Exception: A fire alarm system need not be…
313.13 Existing Group R Occupancy high-rise buildings. ¶
313.13 Existing Group R Occupancy high-rise buildings. 313.13.1 General. Regardless of other provisions of these regulations relating to existing high-rise buildings, requirements relative to existing Group R-1 or Group R-2 Occupancies shall not be less restrictive than those established pursuant to Health and Safety Code Section 13143.2. 313.13.2 Corridor openings. Openings in corridor walls and ceilings shall be protected by not less than 1 [3] / 4 -inch (44.5 mm) solid- bonded wood-core doors, [ 1] / 4 -inch-thick (6 mm) wired glass conforming to Section 715.1 of the California Building…