Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS

503 General Building Height and Area Limitations — 2025 California Building Code

California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Building Code (Title 24, Part 2) § 503 · Effective January 1, 2026 · Official source: Building Standards Commission

503.1 General.

Unless otherwise specifically modified in Chapter 4 and this chapter, building height, number of stories and building area shall not exceed the limits specified in Sections 504 and 506 based on the type of construction as determined by Section 602 and the occupancies as determined by Section 302 except as modified hereafter. Building height, number of stories and building area provisions shall be applied independently. For the purposes of determining area limitations, height limitations and type of construction, each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building.

Exceptions: 1. [HCD 1] Limited-density owner-built rural dwellings may be of any type of construction which will provide for a sound struc- tural condition. Structural hazards which result in an unsound condition and which may constitute a substandard building are delineated by Section 17920.3 of the Health and Safety Code. 2. Other than structural requirements, solar photovoltaic panels supported by a structure with no use underneath shall not constitute additional story or additional floor area and may exceed the height limit when constructed on a roof top of a building provided the following conditions are met: 1. For all occupancies, the highest point of the structure/panel shall meet the lower of the two values below: 1. 3 ′ above the allowable building height per this code. 2. 3 ′ above the roof of the building immediately below. 2. For installations on flat roofs in other than Group R-3 and R-4 occupancies, the highest point of the structure/panel shall meet the lower of the two values below:

1. 10 ′ above the allowable building height per this code. 2. 10 ′ above the roof of the building immediately below. 3. Other than structural requirements, solar photovoltaic panels supported by a structure over parking stalls shall not consti- tute additional story or additional floor area and may exceed the height limit as specified in exception 2 (above) when the following conditions are met (see Figure 5-1): 1. The area within the perimeter of the photovoltaic array has maximum rectangular dimension of 40 feet by 150 feet. 2. The distance between solar photovoltaic array structures is a minimum of 10 feet clear. 3. The driveway aisle separating solar photovoltaic array structures has a minimum width of 25 feet clear. 4. Solar photovoltaic array structure is used only for parking purposes with no storage. 5. Completely open on all sides (other than necessary structural supports) with no interior partitions.

GENERAL BUILDING HEIGHTS AND AREAS

FIGURE 5-1

503.1.1 Special industrial occupancies. Buildings and structures designed to house special industrial processes that require large areas and unusual building heights to accommodate craneways or special machinery and equipment, including, among others, rolling mills; structural metal fabrication shops and foundries; or the production and distribution of electric, gas or steam power, shall be exempt from the building height, number of stories and building area limitations specified in Sections 504 and 506.

503.1.2 Buildings on same lot. Two or more buildings on the same lot shall be regulated as separate buildings or shall be considered as portions of one building where the building height, number of stories of each building and the aggregate building area of the buildings are within the limitations specified in Sections 504 and 506. The provisions of this code applicable to the aggregate building shall be applicable to each building.

503.1.3 Type I construction. Buildings of Type I construction permitted to be of unlimited tabular building heights and areas are not subject to the special requirements that allow unlimited area buildings in Section 507 or unlimited building height in Sections 503.1.1 and 504.3 or increased building heights and areas for other types of construction.

503.1.4 Occupiable roofs. A roof level or portion thereof shall not be used as an occupiable roof unless the occupancy of the roof is an occupancy that is permitted by Table 504.4 for the story immediately below the roof. The area of the occupiable roofs shall not be included in the building area as regulated by Section 506. An occupiable roof shall not be included in the building height or number of stories as regulated by Section 504, provided that the penthouses and other enclosed rooftop structures comply with Section 1511.

Exceptions:

  1. The occupancy located on an occupiable roof shall not be limited to the occupancies allowed on the story immediately below the roof where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and occupant notification in accordance with Sections 907.5.2.1 and 907.5.2.3 is provided in the area of the occupiable roof. Emergency voice/alarm communication system notification per Section 907.5.2.2 shall also be provided in the area of the occupiable roof where such system is required elsewhere in the building.
  2. Assembly occupancies shall be permitted on roofs of open parking spaces of Type I or Type II construction, in accordance with the exception to Section 903.2.1.6.

503.1.4.1 Enclosures over occupiable roof areas. Elements or structures enclosing the occupiable roof areas shall not extend more than 48 inches (1220 mm) above the surface of the occupiable roof.

Exceptions:

  1. Penthouses constructed in accordance with Section 1511.2 and towers, domes, spires and cupolas constructed in accordance with Section 1511.5.

  2. Elements or structures enclosing the occupiable roof areas where the roof deck is located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access.

Exceptions & meaning →

Explained in plain English

Guides that cite this section.

Get a plain-English answer with a citation back to this text.

Ask AI about this code