Section 1013 — EXIT SIGNS
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
1013.1 Where required. ¶
Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that any point in an exit access corridor or exit passageway is within 100 feet (30 480 mm) or the listed viewing distance of the sign, whichever is less, from the nearest visible exit sign.
Exceptions:
Exit signs are not required in rooms or areas that require only one exit or exit access.
Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the building official.
Exit signs are not required in occupancies in Group U and individual sleeping units or dwelling units in Group R-1, R-2 or R-3 or R-3.1 .
Exit signs are not required where inmates are housed or held in dayrooms, sleeping rooms or dormitories in occupancies in Group I-3.
In occupancies in Groups A-4 and A-5, exit signs are not required on the seating side of vomitories or openings into seating areas where exit signs are provided in the concourse that are readily apparent from the vomitories. Egress lighting is provided to identify each vomitory or opening within the seating area in an emergency.
1013.2 Low-level exit signs in Group R-1. See Section 1013.7. ¶
1013.3 Illumination. Exit signs shall be internally or externally illuminated. ¶
Exception: Tactile signs required by Section 1013.4 need not be provided with illumination.
10-34 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
1013.4 Raised character and braille exit signs. ¶
[HCD 1-AC] Tactile exit signs shall be required at the following locations: 1. Each grade-level exterior exit door that is required to comply with Section 1013.1, shall be identified by a tactile exit sign with the word, “EXIT”.
2. Each exit door that is required to comply with Section 1013.1, and that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be identified by a tactile exit sign with the following words as appropriate:
2.1. “EXIT STAIR DOWN”
2.2. “EXIT RAMP DOWN”
2.3. “EXIT STAIR UP”
2.4. “EXIT RAMP UP”
3. Each exit door that is required to comply with Section 1013.1, and that leads directly to a grade-level exterior exit by means of an exit enclosure or an exit passageway shall be identified by a tactile exit sign with the words, “EXIT ROUTE.” 4. Each exit access door from an interior room or area to a corridor or hallway that is required to comply with Section 1013.1, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” 5. Each exit door through a horizontal exit that is required to comply with Section 1013.1, shall be identified by a sign with the words, “TO EXIT.”
Raised character and Braille exit signs shall comply with Chapter 11A, Section 1143A or Chapter 11B, Sections 11B-703.1, 11B-703.2, 11B-703.3 and 11B-703.5.
1013.5 Internally illuminated exit signs. ¶
Electrically powered, self-luminous and photoluminescent exit signs shall be listed and labeled in accordance with UL 924 and shall be installed in accordance with the manufacturer’s instructions and Chapter 27. Exit signs shall be illuminated at all times.
1013.5.1 Photoluminescent exit signs. Photoluminescent exit signs shall be provided with an illumination source to charge the exit sign in accordance with the manufacturer’s instructions.
1013.6 Externally illuminated exit signs. ¶
Externally illuminated exit signs shall comply with Sections 1013.6.1 through 1013.6.3.
1013.6.1 Graphics. Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than [3] / 4 inch (19.1 mm) wide. The word “EXIT” shall have letters having a width not less than 2 inches (51 mm) wide, except the letter “I,” and the minimum spacing between letters shall be not less than [3] / 8 inch (9.5 mm). Signs larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height.
The word “EXIT” shall be in high contrast with the background and shall be clearly discernible when the means of exit sign illumination is or is not energized. If a chevron directional indicator is provided as part of the exit sign, the construction shall be such that the direction of the chevron directional indicator cannot be readily changed.
1013.6.2 Exit sign illumination. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 footcandles (54 lux).
1013.6.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Chapter 27. Group I-2, Condition 2 exit sign illumination shall not be provided by unit equipment batteries only.
Exception: Approved exit sign illumination types that provide continuous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be connected to an emergency electrical system.
1013.7 Floor-level exit signs. ¶
Where exit signs are required by Chapter 10, additional approved low-level exit signs which are internally or externally illuminated photoluminescent or self-luminous, shall be provided in all interior corridors of Group A, E, I and R-2.1 occupan- cies and in all areas serving guest rooms of hotels in Group R, Division 1 occupancies.
Exceptions: 1. Group A occupancies that are protected throughout by an approved supervised fire sprinkler system. 2. Group E Occupancies where direct exits have been provided from each classroom. 3. Group I and R-2.1 occupancies which are provided with smoke barriers constructed in accordance with Section 407.5.
4. Group I-3 occupancies.
The bottom of the sign shall not be less than 6 inches (152 mm) or more than 8 inches (203 mm) above the floor level and shall indicate the path of exit travel. For exit and exit-access doors, the sign shall be on the door or adjacent to the door with the closest edge of the sign or marker within 4 inches (102 mm) of the door frame.
Note: Pursuant to Health and Safety Code Section 13143, this California amendment applies to all newly constructed buildings or structures subject to this section for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.
1013.8 Path marking. ¶
When exit signs are required by Chapter 10, in addition to approved floor-level exit signs, approved path marking shall be installed at floor level or no higher than 8 inches (203 mm) above the floor level in all interior rated exit corridors of unsprinklered Group A, R-1 and R-2 occupancies.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
Such marking shall be continuous except as interrupted by door-ways, corridors or other such architectural features in order to provide a visible delineation along the path of travel.
Note: Pursuant to Health and Safety Code Section 13143, the California amendments of this section shall apply to all newly constructed buildings or structures subject to this section for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
-
▸ Chapter 10 — MEANS OF EGRESS
Overview- Section 1001 — ADMINISTRATION
- Section 1002 — MAINTENANCE AND PLANS
- Section 1003 — GENERAL MEANS OF EGRESS
- Section 1004 — OCCUPANT LOAD
- Section 1005 — MEANS OF EGRESS SIZING
- Section 1006 — NUMBER OF EXITS AND EXIT ACCESS DOORWAYS
- Section 1007 — EXIT AND EXIT ACCESS DOORWAY CONFIGURATION
- Section 1008 — MEANS OF EGRESS ILLUMINATION
- Section 1009 — ACCESSIBLE MEANS OF EGRESS
- Section 1010 — DOORS, GATES AND TURNSTILES
- Section 1011 — STAIRWAYS
- Section 1012 — RAMPS
- Section 1013 — EXIT SIGNS
- Section 1014 — HANDRAILS
- Section 1015 — GUARDS
- Section 1016 — EXIT ACCESS
- Section 1017 — EXIT ACCESS TRAVEL DISTANCE
- Section 1018 — AISLES
- Section 1019 — EXIT ACCESS STAIRWAYS AND RAMPS
- Section 1020 — CORRIDORS
- Section 1021 — EGRESS BALCONIES
- Section 1022 — EXITS
- Section 1023 — INTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1024 — EXIT PASSAGEWAYS
- Section 1025 — LUMINOUS EGRESS PATH MARKINGS
- Section 1026 — HORIZONTAL EXITS
- Section 1027 — EXTERIOR EXIT STAIRWAYS AND RAMPS
- Section 1028 — EXIT DISCHARGE
- Section 1029 — EGRESS COURTS
- Section 1030 — ASSEMBLY
- Section 1031 — EMERGENCY ESCAPE AND RESCUE
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING