Chapter 10 — MEANS OF EGRESS

Section 1021 — EGRESS BALCONIES

2025 California Building Code (Title 24, Part 2) · 2025 edition · ingested 2026-07-07 · California

Full text via GoCodebook AI

We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.

Ask about this chapter

1021.1 General.

1021.1 General. Balconies used for egress purposes shall conform to the same requirements as corridors for minimum width, required capacity, headroom, dead ends and projections.

1021.2 Wall separation.

1021.2 Wall separation. Exterior egress balconies shall be separated from the interior of the building by walls and opening protectives as required for corridors. Exception: Separation is not required where the exterior egress balcony is served by not less than two stairways and a dead-end travel condition does not require travel past an unprotected opening to reach a stairway.

1021.3 Openness.

1021.3 Openness. The long side of an egress balcony shall be not less than 50 percent open, and the open area above the guards shall be so distributed as to minimize the accumulation of smoke or toxic gases.

1021.4 Location.

1021.4 Location. Exterior egress balconies shall have a minimum fire separation distance of 10 feet (3048 mm) measured at right angles from the exterior edge of the egress balcony to the following: 1. Adjacent lot lines. 2. Other portions of the building. 3. Other buildings on the same lot unless the adjacent building exterior walls and openings are protected in accordance with Section 705 based on fire separation distance. For the purposes of this section, other portions of the building shall be treated as separate buildings.