CRC · California Residential Code
Roof ventilation, unvented attics and attic access
This hub summarizes CRC requirements for attic ventilation, the conditions allowing unvented attic assemblies, and minimum attic access dimensions and insulation.
Last reviewed: July 6, 2026
Overview
This section of the California Residential Code (CRC) governs the ventilation of enclosed attics and rafter spaces, the conditions under which attics may be left unvented, and minimum attic access requirements. The primary provisions live in Chapter 8—see §R806 for roof/attic ventilation (including minimum net free area, vent placement and Wildland‑Urban Interface requirements) and §R807 for attic access openings.
Unvented attic assemblies are permitted only when specific thermal‑envelope, vapor‑retarder and insulation criteria are met (see §R806.5), because these details control condensation risk and energy performance. The CRC requirements for unvented assemblies tie directly to Title 24 energy provisions (insulation placement, attic access insulation and air sealing) in the California Energy Code.
Key rules to know at a glance: minimum net free ventilating area (normally 1/150 of the attic area, with a 1/300 exception when upper and lower vents and vapor retarder conditions are met) is in §R806.2; unvented attic conditions and insulation placement are in §R806.5; attic access size and location are in §R807.1. For nonresidential roof ventilation see the CBC cross‑references in Chapter 12.
In this section
- Are there special venting rules for Wildland‑Urban Interface (WUI) areas?
- What are the CRC ventilation requirements for enclosed attics and rafter spaces?
- What are the required attic access opening size, location and headroom requirements?
- When are unvented attic assemblies permitted and what conditions apply?
Code references
Grounded in the retrieved California Residential Code — click a citation to read the verbatim passage:
CRC § 3.8 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF-CEILING CONSTRUCTION
R804.3.8 Roof tie-down. Roof assemblies shall be connected to walls below in accordance with Table R804.3. A continuous load path shall be provided to transfer uplift loads to the foundation.
SECTION R805—CEILING FINISHES
R805.1 Ceiling installation. Ceilings shall be installed in accordance with the requirements for interior wall finishes as provided in Sections R702.1 through R702.6.
SECTION R806—ROOF VENTILATION
Note: The IECC climate zones used by this section differ from those used by the California Energy Code to determine applicability of energy efficiency measures. Comparison of IECC and California Energy Code climate zones is shown in Table R702.7.3.
R806.1 Ventilation required. Enclosed attics and enclosed rafter spaces formed where ceilings are applied directly to the underside of roof rafters shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain or snow. Ventilation openings shall have a least dimension of [1] / 16 inch (1.6 mm) minimum and [1] / 4 inch (6.4 mm) maximum. Ventilation openings having a least dimension larger than [1] / 4 inch (6.4 mm) shall be provided with corrosion-resistant wire cloth screening, hardware cloth, perforated vinyl or similar material with openings having a least dimension of [1] / 16 inch (1.6 mm) minimum and [1] / 4 inch (6.4 mm) maximum. Openings in roof framing members shall conform to the requirements of Section R802.7. Required ventilation openings shall open directly to the outside air and shall be protected to prevent the entry of birds, rodents, snakes and other similar creatures.
R806.1.1 Vents in the Wildland Urban Interface (WUI). Where provided, ventilation openings for enclosed attics, gable ends, ridge ends, under eaves and cornices, enclosed eave soffit spaces, enclosed rafter spaces formed where ceilings are applied directly to the underside of roof rafters, underfloor ventilation, foundations and crawl spaces, or any other opening intended to permit ventilation, either in a horizontal or vertical plane, shall be in accordance with Part 7, California Wildland-Urban Interface Code to resist building ignition from the intrusion of burning embers and flame through the ventilation openings. R806.2 Minimum vent area. The minimum net free ventilating area shall be [1] / 150 of the area of the vented space. Exception: The minimum net free ventilation area shall be [1] / 300 of the vented space provided both of the following conditions are met:
- In Climate Zones 6, 7 and 8, a Class I or II vapor retarder is installed on the warm-in-winter side of the ceiling.
- Not less than 40 percent and not more than 50 percent of the required ventilating area is provided by ventilators located in the upper portion of the attic or rafter space. Upper ventilators shall be located not more than 3 feet (914 mm) below the ridge or highest point of the space, measured vertically. The balance of the required ventilation provided shall be located in the bottom one-third of the attic space.
CRC § 1.1 High relevance — show source text
Openings in roof framing members shall conform to the requirements of Section R802.7. Required ventilation openings shall open directly to the outside air and shall be protected to prevent the entry of birds, rodents, snakes and other similar creatures.
R806.1.1 Vents in the Wildland Urban Interface (WUI). Where provided, ventilation openings for enclosed attics, gable ends, ridge ends, under eaves and cornices, enclosed eave soffit spaces, enclosed rafter spaces formed where ceilings are applied directly to the underside of roof rafters, underfloor ventilation, foundations and crawl spaces, or any other opening intended to permit ventilation, either in a horizontal or vertical plane, shall be in accordance with Part 7, California Wildland-Urban Interface Code to resist building ignition from the intrusion of burning embers and flame through the ventilation openings. R806.2 Minimum vent area. The minimum net free ventilating area shall be [1] / 150 of the area of the vented space. Exception: The minimum net free ventilation area shall be [1] / 300 of the vented space provided both of the following conditions are met:
- In Climate Zones 6, 7 and 8, a Class I or II vapor retarder is installed on the warm-in-winter side of the ceiling.
- Not less than 40 percent and not more than 50 percent of the required ventilating area is provided by ventilators located in the upper portion of the attic or rafter space. Upper ventilators shall be located not more than 3 feet (914 mm) below the ridge or highest point of the space, measured vertically. The balance of the required ventilation provided shall be located in the bottom one-third of the attic space. Where the location of wall or roof framing members conflicts with the installation of upper ventilators, installation more than 3 feet (914 mm) below the ridge or highest point of the space shall be permitted.
R806.3 Vent and insulation clearance. Where eave or cornice vents are installed, blocking, bridging and insulation shall not block the free flow of air. Not less than a 1-inch (25 mm) space shall be provided between the insulation and the roof sheathing and at the location of the vent.
R806.4 Installation and weather protection. Ventilators shall be installed in accordance with manufacturer’s instructions. Installation of ventilators in roof systems shall be in accordance with the requirements of Section R903. Installation of ventilators in wall systems shall be in accordance with the requirements of Section R703.1.
R806.5 Unvented attic and unvented enclosed rafter assemblies. Unvented attics and unvented enclosed roof framing assemblies created by ceilings that are applied directly to the underside of the roof framing members and structural roof sheathing applied directly to the top of the roof framing members/rafters, shall be permitted where all the following conditions are met:
- The unvented attic space is completely within the building thermal envelope.
- Interior Class I vapor retarders are not installed on the ceiling side (attic floor) of the unvented attic assembly or on the ceiling side of the unvented enclosed roof framing assembly.
- Where wood shingles or shakes are used, a minimum [1] / 4 -inch (6.4 mm) vented airspace separates the shingles or shakes and the roofing underlayment above the structural sheathing.
CRC § 1202.1 High relevance — show source text
SECTION 1202—VENTILATION
1202.1 General. Buildings shall be provided with natural ventilation in accordance with Section 1202.5, or mechanical ventilation in accordance with the California Mechanical Code .
Dwelling units complying with the air leakage requirements of the California Energy Code or ASHRAE 90.1 shall be ventilated by mechanical means in accordance with Section 403 of the California Mechanical Code . Ambulatory care facilities and Group I-2 occupancies shall be ventilated by mechanical means in accordance with Section 407 of the California Mechanical Code .
1202.2 Roof ventilation. Roof assemblies shall be ventilated in accordance with this section or shall comply with Section 1202.3.
1202.2.1 Ventilated attics and rafter spaces. Enclosed attics and enclosed rafter spaces formed where ceilings are applied directly to the underside of roof framing members shall have cross ventilation for each separate space by ventilation openings protected against the entrance of rain and snow. Blocking and bridging shall be arranged so as not to interfere with the movement of air. An airspace of not less than 1 inch (25 mm) shall be provided between the insulation and the roof sheathing. The net free ventilating area shall be not less than [1] / 150 of the area of the space ventilated. Ventilators shall be installed in accordance with manufacturer’s installation instructions.
Exception: The net free cross-ventilation area shall be permitted to be reduced to [1] / 300 provided both of the following conditions are met:
- In Climate Zones 6, 7 and 8, a Class I or II vapor retarder is installed on the warm-in-winter side of the ceiling.
- At least 40 percent and not more than 50 percent of the required venting area is provided by ventilators located in the upper portion of the attic or rafter space. Upper ventilators shall be located not more than 3 feet (914 mm) below the ridge or highest point of the space, measured vertically, with the balance of the ventilation provided by eave or cornice vents. Where the location of wall or roof framing members conflicts with the installation of upper ventilators, installation more than 3 feet (914 mm) below the ridge or highest point of the space shall be permitted.
1202.2.2 Openings into attic. Exterior openings into the attic space of any building intended for human occupancy shall be protected to prevent the entry of birds, squirrels, rodents, snakes and other similar creatures. Openings for ventilation having a least dimension of not less than [1] / 16 inch (1.6 mm) and not more than [1] / 4 inch (6.4 mm) shall be permitted. Openings for ventilation having a least dimension larger than [1] / 4 inch (6.4 mm) shall be provided with corrosion-resistant wire cloth screening, hardware cloth, perforated vinyl or similar material with openings having a least dimension of not less than [1] / 16 inch (1.6 mm) and not more than [1] / 4 inch (6.4 mm). Where combustion air is obtained from an attic area, it shall be in accordance with Chapter 7 of the California Mechanical Code .
1202.3 Unvented attic and unvented enclosed rafter assemblies. Unvented attics and unvented enclosed roof framing assemblies created by ceilings applied directly to the underside of the roof framing members/rafters and the structural roof sheathing at the top of the roof framing members shall be permitted where all of the following conditions are met: 1.
CRC § 6.4 High relevance — show source text
The balance of the required ventilation provided shall be located in the bottom one-third of the attic space. Where the location of wall or roof framing members conflicts with the installation of upper ventilators, installation more than 3 feet (914 mm) below the ridge or highest point of the space shall be permitted.
R806.3 Vent and insulation clearance. Where eave or cornice vents are installed, blocking, bridging and insulation shall not block the free flow of air. Not less than a 1-inch (25 mm) space shall be provided between the insulation and the roof sheathing and at the location of the vent.
R806.4 Installation and weather protection. Ventilators shall be installed in accordance with manufacturer’s instructions. Installation of ventilators in roof systems shall be in accordance with the requirements of Section R903. Installation of ventilators in wall systems shall be in accordance with the requirements of Section R703.1.
R806.5 Unvented attic and unvented enclosed rafter assemblies. Unvented attics and unvented enclosed roof framing assemblies created by ceilings that are applied directly to the underside of the roof framing members and structural roof sheathing applied directly to the top of the roof framing members/rafters, shall be permitted where all the following conditions are met:
- The unvented attic space is completely within the building thermal envelope.
- Interior Class I vapor retarders are not installed on the ceiling side (attic floor) of the unvented attic assembly or on the ceiling side of the unvented enclosed roof framing assembly.
- Where wood shingles or shakes are used, a minimum [1] / 4 -inch (6.4 mm) vented airspace separates the shingles or shakes and the roofing underlayment above the structural sheathing.
- In Climate Zones 5, 6, 7 and 8, any air-impermeable insulation shall be a Class II vapor retarder, or shall have a Class II vapor retarder coating or covering in direct contact with the underside of the insulation.
- Insulation shall comply with Item 5.3 and either Item 5.1 or 5.2: 5.1. Item 5.1.1, 5.1.2, 5.1.3 or 5.1.4 shall be met, depending on the air permeability of the insulation directly under the structural roof sheathing. 5.1.1. Where only air-impermeable insulation is provided, it shall be applied in direct contact with the underside of the structural roof sheathing. 5.1.2. Where air-permeable insulation is installed directly below the structural sheathing, rigid board or sheet insulation shall be installed directly above the structural roof sheathing in accordance with the R-values in Table R806.5 for condensation control.
5.1.3. Where both air-impermeable and air-permeable insulation are provided, the air-impermeable insulation shall be applied in direct contact with the underside of the structural roof sheathing in
8-44 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF-CEILING CONSTRUCTION
accordance with Item 5.1.1 and shall be in accordance with the R-values in Table R806.5 for condensation control. The air-permeable insulation shall be installed directly under the air-impermeable insulation.
CRC § 3.7.1 High relevance — show source text
FIGURE R804.3.7.1(2)—CEILING DIAPHRAGM TO SIDEWALL DETAIL
ROOF-CEILING CONSTRUCTION
ROOF RAFTER (OR TRUSS TOP CHORD)
CEILING JOIST (OR TRUSS BOTTOM CHORD)
WOOD STRUCTURAL
PANEL OR GYPSUM
BOARD DIAPHRAGM
350T125-33 TRACK
ROOF SHEATHING
ROOF BLOCKING
NO. 8 SCREWS AT 6 IN. O.C.
STRUCTURAL WALL
For SI: 1 inch = 25.4 mm.
R804.3.7.2 Roof diaphragm. A roof diaphragm shall be provided by attaching not less than [3] / 8 -inch (9.5 mm) wood structural panel that complies with Section R803 to roof rafters or truss top chords in accordance with Table R804.3. Buildings with 3:1 or larger plan aspect ratio and with roof rafter slope (pitch) of 9:12 or larger shall have the roof rafters and ceiling joists blocked in accordance with Figure R804.3.7.2.
FIGURE R804.3.7.2—ROOF BLOCKING DETAIL
BE ATTACHED TO OUTSIDE FACE OF SHEATHING OR PREFERABLY DIRECTLY TO TRACK FLANGE PRIOR TO SHEATHING PLACEMENT AS SHOWN
For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm.
2025 CALIFORNIA RESIDENTIAL CODE 8-43
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF-CEILING CONSTRUCTION
R804.3.8 Roof tie-down. Roof assemblies shall be connected to walls below in accordance with Table R804.3. A continuous load path shall be provided to transfer uplift loads to the foundation.
SECTION R805—CEILING FINISHES
R805.1 Ceiling installation. Ceilings shall be installed in accordance with the requirements for interior wall finishes as provided in Sections R702.1 through R702.6.
SECTION R806—ROOF VENTILATION
Note: The IECC climate zones used by this section differ from those used by the California Energy Code to determine applicability of energy efficiency measures. Comparison of IECC and California Energy Code climate zones is shown in Table R702.7.3.
R806.1 Ventilation required. Enclosed attics and enclosed rafter spaces formed where ceilings are applied directly to the underside of roof rafters shall have cross ventilation for each separate space by ventilating openings protected against the entrance of rain or snow. Ventilation openings shall have a least dimension of [1] / 16 inch (1.6 mm) minimum and [1] / 4 inch (6.4 mm) maximum. Ventilation openings having a least dimension larger than [1] / 4 inch (6.4 mm) shall be provided with corrosion-resistant wire cloth screening, hardware cloth, perforated vinyl or similar material with openings having a least dimension of [1] / 16 inch (1.6 mm) minimum and [1] / 4 inch (6.4 mm) maximum. Openings in roof framing members shall conform to the requirements of Section R802.7.
CRC § 8-45 High relevance — show source text
2025 CALIFORNIA RESIDENTIAL CODE 8-45
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF-CEILING CONSTRUCTION
SECTION R807—ATTIC ACCESS
R807.1 Attic access. Buildings with attics shall have an access opening to attic areas that have a vertical height of 30 inches (762 mm) or greater over an area of not less than 30 square feet (2.8 m [2] ). The vertical height shall be measured from the top of the ceiling framing members to the underside of the roof framing members.
The rough-framed opening shall be not less than 22 inches by 30 inches (559 mm by 762 mm) and shall be located in a hallway or other location with ready access. Where located in a wall, the opening shall be not less than 22 inches wide by 30 inches high (559 mm wide by 762 mm high). Where the access is located in a ceiling, unobstructed headroom in the attic space above the access shall be not less than 30 inches (762 mm) along one side or more measured vertically from the bottom of ceiling framing members. See the California Mechanical Code for access requirements where mechanical equipment is located in attics.
8-46 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA RESIDENTIAL CODE – MATRIX ADOPTION TABLE
CHAPTER 9 – ROOF ASSEMBLIES
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting agency BSC BSC-
CGSFM HCD Col6 Col7 DSA Col9 Col10 OSHPD Col12 Col13 Col14 Col15 Col16 BSCC DPH AGR DWR CEC CA SL SLC Adopting agency BSC BSC-
CGSFM 1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5 5 5 5 5 5 5 5 5 Adopt entire chapter Adopt entire chapter as
amended (amended
sections listed below)X Adopt only those sections
that are listed belowX Chapter / Section R901.1 X R902.1 - R902.4 X R903.4.1 X R904.1 - R904.4 X R905.15 X R905.16 X R907. CRC § 0.098. High relevance — show source text
For vented attics, the mandatory insulation shall be installed at the ceiling level; for unvented attics, the mandatory insulation shall be placed at either ceiling or roof level; B. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The attic access shall be gasketed to prevent air leakage; and C. When loose-fill insulation is installed, the minimum installed weight per square foot shall conform with the insulation manufacturer's installed design weight per square foot at the manufacturer's labeled R- value. 2. Nonattic roof. Roofs without attic spaces shall meet the applicable requirements of A through C below: A. Metal building—The area-weighted average U- factor of the roof assembly shall not exceed 0.098. B. Wood framed and others—The area-weighted average U- factor of the roof assembly shall not exceed 0.075. C. Insulation placement—When insulation is installed at the roof, fixed vents or openings to the outdoors or to unconditioned spaces shall not be installed. When the space between the ceiling and the roof is either directly or indirectly conditioned space, it shall not be considered an attic for the purposes of complying with CBC attic ventilation requirements. Exception to Section 160.1(a)2C: Vents that do not penetrate the roof deck and are instead designed for wind resistance for roof membranes are not within the scope of Section 160.1(a)2C. 3. Insulation shall be installed in direct contact with a roof or ceiling that is sealed to limit infiltration and exfiltration as specified in Section 110.7, including but not limited to placing insulation either above or below the roof deck or on top of a drywall ceiling.
(b) Wall insulation. Opaque portions of above grade walls separating conditioned spaces from unconditioned spaces or ambient air shall meet the following applicable requirements:
Metal building—The area-weighted average U- factor of the wall assembly shall not exceed 0.113.
Metal framed—The area-weighted average U- factor of the wall assembly shall not exceed 0.151.
Wood framed and others—
A. Nominal 2x4 inch framing shall have an area-weighted average U- factor of the wall assembly not exceeding 0.095. B. Nominal 2x6 inch framing shall have an area-weighted average U- factor of the wall assembly not exceeding 0.069. C. Other wall assemblies shall have an area-weighted average U- factor of the wall assembly not exceeding 0.102. 4. Light mass walls—A 6 inch or greater hollow core concrete masonry unit shall have a U- factor not to exceed 0.440. 5. Heavy mass walls—An 8 inch or greater hollow core concrete masonry unit shall have a U- factor not to exceed 0.690. 6. Spandrel panels and curtain wall—The area-weighted average U- factor of the spandrel panels and curtain wall assembly shall not exceed 0.280.
- Demising walls—The opaque portions of framed demising walls shall meet the requirements of Item A or B below: A. Wood framed walls shall be insulated to meet a U- factor not greater than 0.099. B. Metal framed walls shall be insulated to meet a U- factor not greater than 0.151.
- Bay or bow window roofs and floors shall be insulated to meet the wall insulation requirements of Table 170.2-A.
CRC § 2025 High relevance — show source text
Chapter 6 also regulates exterior windows and doors installed in walls. This chapter contains criteria for the performance of exterior windows and doors and includes provisions for testing and labeling, garage doors, windborne debris protection and anchorage details.
Chapter 7 Wall Covering.
Chapter 7 contains provisions for the design and construction of interior and exterior wall coverings. This chapter establishes the various types of materials, materials standards and methods of application permitted for use as interior coverings, including interior plaster, gypsum board, ceramic tile, wood veneer paneling, hardboard paneling, wood shakes and wood shingles. Chapter 7 also contains requirements for the use of vapor retarders for moisture control in walls.
2025 CALIFORNIA RESIDENTIAL CODE xv
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Exterior wall coverings provide the weather-resistant exterior envelope that protects the building’s interior from the elements. Chapter 7 provides the requirements for wind resistance and water-resistive barrier for exterior wall coverings. This chapter prescribes the exterior wall coverings as well as the water-resistive barrier required beneath the exterior materials. Exterior wall coverings regulated by this section include aluminum, stone and masonry veneer, wood, hardboard, particleboard, wood structural panel siding, wood shakes and shingles, exterior plaster, steel, vinyl, fiber cement and exterior insulation finish systems.
Chapter 8 Roof-Ceiling Construction.
Chapter 8 regulates the design and construction of roof-ceiling systems. This chapter contains two roof-ceiling framing systems: wood framing and cold-formed steel framing. Allowable span tables are provided to simplify the selection of rafter and ceiling joist size for wood roof framing and cold-formed steel framing. Chapter 8 also provides requirements for the application of ceiling finishes, the proper ventilation of concealed spaces in roofs (e.g., enclosed attics and rafter spaces), unvented attic assemblies and attic access.
Chapter 9 Roof Assemblies.
Chapter 9 regulates the design and construction of roof assemblies. A roof assembly includes the roof deck, vapor retarder, substrate or thermal barrier, insulation, vapor retarder and roof covering. This chapter provides the requirement for wind resistance of roof coverings.
The types of roof covering materials and installation regulated by Chapter 9 are: asphalt shingles, clay and concrete tile, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shakes and shingles, built-up roofs, metal roof panels, modified bitumen roofing, thermoset and thermoplastic single-ply roofing, sprayed polyurethane foam roofing, liquid applied coatings and photovoltaic shingles. Chapter 9 also provides requirements for roof drainage, flashing, above deck thermal insulation, rooftop-mounted photovoltaic systems and recovering or replacing an existing roof covering.
Chapter 10 Chimneys and Fireplaces.
Chapter 10 contains requirements for the safe construction of masonry chimneys and fireplaces and establishes the standards for the use and installation of factory-built chimneys, fireplaces and masonry heaters. Chimneys and fireplaces constructed of masonry rely on prescriptive requirements for the details of their construction; the factory-built type relies on the listing and labeling method of approval. Chapter 10 provides the requirements for seismic reinforcing and anchorage of masonry fireplaces and chimneys.
Chapter 11 [RE] Energy Efficiency.
Chapter 11 is not adopted in California. See California Energy Code, Title 24, Part 6.
Chapter 12 Mechanical Administration.
CRC § 1202.2.2 Medium relevance — show source text
1202.2.2 Openings into attic. Exterior openings into the attic space of any building intended for human occupancy shall be protected to prevent the entry of birds, squirrels, rodents, snakes and other similar creatures. Openings for ventilation having a least dimension of not less than [1] / 16 inch (1.6 mm) and not more than [1] / 4 inch (6.4 mm) shall be permitted. Openings for ventilation having a least dimension larger than [1] / 4 inch (6.4 mm) shall be provided with corrosion-resistant wire cloth screening, hardware cloth, perforated vinyl or similar material with openings having a least dimension of not less than [1] / 16 inch (1.6 mm) and not more than [1] / 4 inch (6.4 mm). Where combustion air is obtained from an attic area, it shall be in accordance with Chapter 7 of the California Mechanical Code .
1202.3 Unvented attic and unvented enclosed rafter assemblies. Unvented attics and unvented enclosed roof framing assemblies created by ceilings applied directly to the underside of the roof framing members/rafters and the structural roof sheathing at the top of the roof framing members shall be permitted where all of the following conditions are met:
- The unvented attic space is completely within the building thermal envelope.
- No interior Class I vapor retarders are installed on the ceiling side (attic floor) of the unvented attic assembly or on the ceiling side of the unvented enclosed roof framing assembly.
- Where wood shingles or shakes are used, not less than a [1] / 4 -inch (6.4 mm) vented airspace separates the shingles or shakes and the roofing underlayment above the structural sheathing.
- In Climate Zones 5, 6, 7 and 8, any air-impermeable insulation shall be a Class II vapor retarder or shall have a Class II vapor retarder coating or covering in direct contact with the underside of the insulation.
- Insulation shall comply with either Item 5.1 or 5.2, and additionally Item 5.3.
2025 CALIFORNIA BUILDING CODE 12-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
INTERIOR ENVIRONMENT
5.1. Item 5.1.1, 5.1.2, 5.1.3 or 5.1.4 shall be met, depending on the air permeability of the insulation directly under the structural roof sheathing. 5.1.1. Where only air-impermeable insulation is provided, it shall be applied in direct contact with the underside of the structural roof sheathing. 5.1.2. Where air-permeable insulation is provided inside the building thermal envelope, it shall be installed in accordance with Item 5.1.1. In addition to the air-permeable insulation installed directly below the structural sheathing, rigid board or sheet insulation shall be installed directly above the structural roof sheathing in accordance with the R -value percentages in Table 1202.3 for condensation control. 5.1.3. Where both air-impermeable and air-permeable insulation are provided, the air-impermeable insulation shall be applied in direct contact with the underside of the structural roof sheathing in accordance with Item 5.1.1 and shall be in accordance with the R -value percentages in Table 1202.3 for condensation control.
CRC § 8-45 Medium relevance — show source text
Contributes to but does not supersede the requirements in Section N1102.
b. Alternatively, sufficient continuous insulation shall be installed directly above the structural roof sheathing to maintain the monthly average temperature of the underside of
the structural roof sheathing above 45°F (7°C). For calculation purposes, an interior air temperature of 68°F (20°C) is assumed and the exterior air temperature is assumed to
be the monthly average outside air temperature of the three coldest months.|a. Contributes to but does not supersede the requirements in Section N1102.
b. Alternatively, sufficient continuous insulation shall be installed directly above the structural roof sheathing to maintain the monthly average temperature of the underside of
the structural roof sheathing above 45°F (7°C). For calculation purposes, an interior air temperature of 68°F (20°C) is assumed and the exterior air temperature is assumed to
be the monthly average outside air temperature of the three coldest months.|2025 CALIFORNIA RESIDENTIAL CODE 8-45
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF-CEILING CONSTRUCTION
SECTION R807—ATTIC ACCESS
R807.1 Attic access. Buildings with attics shall have an access opening to attic areas that have a vertical height of 30 inches (762 mm) or greater over an area of not less than 30 square feet (2.8 m [2] ). The vertical height shall be measured from the top of the ceiling framing members to the underside of the roof framing members.
The rough-framed opening shall be not less than 22 inches by 30 inches (559 mm by 762 mm) and shall be located in a hallway or other location with ready access. Where located in a wall, the opening shall be not less than 22 inches wide by 30 inches high (559 mm wide by 762 mm high). Where the access is located in a ceiling, unobstructed headroom in the attic space above the access shall be not less than 30 inches (762 mm) along one side or more measured vertically from the bottom of ceiling framing members. See the California Mechanical Code for access requirements where mechanical equipment is located in attics.
8-46 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA RESIDENTIAL CODE – MATRIX ADOPTION TABLE
CHAPTER 9 – ROOF ASSEMBLIES
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
CRC § 1.1 Medium relevance — show source text
1.1 Note||||X|||||||||||||||||||| |R802.10.2||||X|||||||||||||||||||| |R803.2.1.2|||X||||||||||||||||||||| |R806 Note||||||||||||||||||||X|||| |R806.1.1|||X|X|||||||||||||||||||| |R807.1||||X||||||||||||||||||||
The state agency does not adopt sections identified with the following symbol: †
2025 CALIFORNIA RESIDENTIAL CODE 8-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8 ROOF-CEILING CONSTRUCTION
User notes:
About this chapter: Chapter 8 addresses the design and construction of roof-ceiling systems. This chapter contains two roof-ceiling framing systems: wood framing and cold-formed steel framing. Allowable span tables are provided to simplify the selection of rafter and ceiling joist size for wood roof framing and cold-formed steel framing. Chapter 8 also provides requirements for the application of ceiling finishes, the proper ventilation of concealed spaces in roofs (for example, enclosed attics and rafter spaces), unvented attic assemblies and attic access.
SECTION R801—GENERAL
R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for buildings.
R801.2 Requirements. Roof and ceiling construction shall be capable of accommodating all loads imposed in accordance with Section R301 and of transmitting the resulting loads to the supporting structural elements.
R801.3 Roof drainage. In areas where expansive soils or collapsible soils are known to exist, all dwellings and townhouses shall have a controlled method of water disposal from roofs that will collect and discharge roof drainage to the ground surface not less than 5 feet (1524 mm) from foundation walls or to an approved drainage system.
SECTION R802—WOOD ROOF FRAMING
R802.1 General. Wood and wood-based products used for load-supporting purposes shall conform to the applicable provisions of this section.
R802.1.1 Sawn lumber. Sawn lumber shall be identified by a grade mark of an accredited lumber grading or inspection agency and have design values certified by an accreditation body that complies with DOC PS 20. In lieu of a grade mark, a certificate of inspection issued by a lumber grading or inspection agency meeting the requirements of this section shall be accepted.
Note: See Section R301.1.1.1 for limited-density owner- built rural dwellings.
R802.1.1.1 End-jointed lumber. Approved end-jointed lumber identified by a grade mark conforming to Section R802.1.1 shall be permitted to be used interchangeably with solid-sawn members of the same species and grade. End-jointed lumber used in an assembly required elsewhere in this code to have a fire-resistance rating shall have the designation “Heat-Resistant Adhesive” or “HRA” included in its grade mark.
R802.1.2 Structural glued-laminated timbers. Glued-laminated timbers shall be manufactured and identified as required in ANSI A190.1, ANSI 117 and ASTM D3737.
R802.1.3 Structural log members. Structural log members shall comply with the provisions of ICC 400.
CRC § 8-3 Medium relevance — show source text
R802 Wood Roof Framing . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
R803 Roof Sheathing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-30
R804 Cold-Formed Steel Roof Framing . . . . . . . . . . . . . . . 8-31
R805 Ceiling Finishes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-44
R806 Roof Ventilation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-44
R807 Attic Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-46
CHAPTER 9 ROOF ASSEMBLIES . . . . . . . . . . . . . . . . . . . . . .9-3
R901 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
R902 Fire Classification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
R903 Weather Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
R904 Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
R905 Requirements for Roof Coverings . . . . . . . . . . . . . . . . 9-4
R906 Roof Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-19
R907 Rooftop-Mounted Photovoltaic Panel Systems . . . 9-19
R908 Reroofing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-19
R909 Roof Coatings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-20
CHAPTER 10 CHIMNEYS AND FIREPLACES . . . . . . . . . . . .10-3
R1001 Masonry Fireplaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
R1002 Masonry Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-6
R1003 Masonry Chimneys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-7
Frequently asked questions
When are unvented attics allowed?
Unvented attics are allowed only when all CRC conditions in §R806.5 are met — the attic must be completely inside the building thermal envelope, no interior Class I vapor retarders are installed on the ceiling side, specific insulation and vapor‑retarder measures (and additional requirements in cold climates) are followed. Refer to §R806.5 for the full list of required items.
How much ventilation is required for a vented attic?
The CRC requires a minimum net free ventilating area of 1/150 of the attic area, except where the 1/300 option applies if the specified vapor retarder, climate zone and upper/lower vent distribution requirements are satisfied; see §R806.2 for details.
What are the attic access requirements and must the hatch be insulated?
Attics with sufficient height must have a framed access opening (rough‑opening at least 22" × 30") and clear headroom requirements per §R807.1; the California Energy Code also requires attic access doors be insulated and gasketed to limit air leakage.
More in California Residential Code
Ask about the CRC
Get cited, plain-English answers on the California Residential Code for your project — any code section, any scenario.
Start Free Trial