CRC · California Residential Code
When must foundation or basement walls be designed by a registered design professional?
If your foundation or basement wall will be loaded by groundwater (hydrostatic pressure) or will retain more than 48 inches of unbalanced fill without permanent lateral support, the California Residential Code requires that wall be engineered — have it designed per accepted engineering practice and provide the required sealed documents to the building official where the jurisdiction requires them (§ R404.1.1).
Last reviewed: July 6, 2026
What the code requires — plain English
When a concrete or masonry foundation or basement wall is either (a) subject to hydrostatic pressure from groundwater, or (b) supports more than 48 inches (1219 mm) of unbalanced backfill and does not have permanent lateral support at the top or bottom, the wall must be designed in accordance with accepted engineering practice — i.e., design is required and typically must be prepared by a registered design professional. See § R404.1 and § R404.1.1 for the controlling requirements.
The single most important rule: if a foundation wall will hold more than 48 inches of unbalanced fill (without permanent lateral support) or will be loaded by groundwater, treat it as an engineered wall and have it designed per accepted engineering practice.
Requirements in detail
Trigger conditions (the two “design required” cases)
- Hydrostatic pressure from groundwater: any concrete or masonry foundation wall that will be subject to hydrostatic pressure must be designed in accordance with accepted engineering practice. § R404.1.1(1).
- Unbalanced backfill: any concrete or masonry foundation wall that supports more than 48 inches (1219 mm) of unbalanced backfill and does not have permanent lateral support at the top or bottom must be designed. § R404.1.1(2).
What “designed in accordance with accepted engineering practice” implies
- Design must follow the applicable provisions of Chapter 4 and referenced standards (for example, ACI 318, ACI 332, PCA 100 when used for concrete walls) or other accepted engineering practice as applicable. See § R404.1 and related design sections.
- Where the code itself is used for design (e.g., the specific reinforcement tables and provisions in R404.1.3), project drawings and details prepared under those code provisions are permitted to be unsecured by a registered design professional’s seal only when state law/jurisdiction does not require a seal; however, where design is required by R404.1.1 the construction documents must be prepared by the registered design professional where required by the jurisdiction. See § R404.1.2, § R404.1.3, and § R106.1.
How to measure the key dimension (unbalanced backfill)
- Unbalanced backfill height is generally the height of retained soil that is not balanced by soil or slab on the other side. Note: where an interior concrete slab-on-grade is in contact with the interior surface of the foundation wall, the unbalanced backfill height may be measured from the exterior finish ground level to the top of the interior slab (the code explicitly permits this measurement method). See measurement allowance in related text.
Decision-relevant thresholds and values (quick reference)
| Decision factor | Threshold / value | What it means | Code Reference |
|---|---|---|---|
| Hydrostatic pressure present? | Any groundwater hydrostatic loading | If yes → design required | § R404.1.1(1) |
| Unbalanced backfill height | > 48 in (1219 mm) | If wall supports more than this without permanent lateral support top/bottom → design required | § R404.1.1(2) |
| Permanent lateral support | Top or bottom support that restrains lateral movement | If present at both top and bottom you may avoid R404.1.1(2) trigger (evaluate carefully) | § R404.1.1(2) |
| Measurement when interior slab present | Measure from exterior finish grade to top of interior slab | Permitted method for determining unbalanced backfill height | (measurement allowance) |
| Masonry design alternative | Tables in R404.1.2 or TMS 402 may be used | Masonry may be designed per the code tables or TMS 402; seal requirements depend on jurisdiction | § R404.1.2 |
Documentation & submittal expectations
- Where the building official requires documents prepared by a registered design professional, such construction documents must be prepared and submitted as required by § R106.1. If design is required by § R404.1.1, expect sealed calculations/drawings where the jurisdiction requires them.
- In flood hazard areas additional sealed documentation is required (see Chapter R306 flood provisions) when constructing below required elevations. The code also requires sealed documentation for certain flood-related designs. § R306.3.9 and related flood documentation sections apply.
Exceptions & special cases
- Masonry foundation walls may be designed using the code tables (Tables in § R404.1.2 and related tables); when those tables or TMS 402 are used, the project drawings are not required to bear the architect/engineer seal unless state law or the jurisdiction requires it. § R404.1.2.
- The code includes special provisions for flood hazard areas (breakaway walls, openings, and flood documentation); when working in flood zones, additional sealed documentation and design statements may be required under Chapter R306. § R306.3.9.
- Measurement nuance: if an interior slab-on-grade is in contact with the interior face of the foundation wall, that interior slab top may be used as the reference for measuring unbalanced backfill height (allowing a smaller unbalanced height in some cases). Measurement allowance is described in the code.
Common mistakes
- Mis-measuring “unbalanced backfill”: counting total fill instead of the unbalanced portion (and failing to use the permitted interior-slab measurement method). Refer to the measurement allowance.
- Assuming “less than 4 feet” in casual terms is safe: the code’s trigger is more than 48 inches (1219 mm); anything over that without permanent lateral support triggers design. § R404.1.1(2).
- Ignoring groundwater/hydrostatic conditions: even a modest wall may require design if groundwater exerts hydrostatic pressure. § R404.1.1(1).
- Failing to get sealed documents where the jurisdiction requires them: the code allows some code-prescriptive designs without a seal only when the jurisdiction’s laws permit — check local requirements. § R404.1.2, § R106.1.
- Forgetting flood provisions: in flood hazard areas, additional sealed documentation and special design for breakaway walls, openings, or dry floodproofing may be required under Chapter R306.
Worked example — concrete scenario
Scenario: New basement wall will retain an exterior backfill that, from exterior grade to the top of the interior slab, measures 60 inches (1524 mm). There is no permanent lateral support at the top (no continuous bond beam tied to a supported above-grade wall) and none at the bottom.
Step 1 — Determine the trigger: The wall supports 60 in of unbalanced backfill, which is greater than 48 in (1219 mm). That meets the second trigger in § R404.1.1(2) so design is required.
Step 2 — Engage a registered design professional: Because design is required by the code, prepare foundation/basement wall structural drawings and calculations per accepted engineering practice (ACI 318 or other applicable standards) and submit them in accordance with § R106.1 if the jurisdiction requires sealed documents.
Step 3 — Provide documentation at inspection: Expect foundation inspection after forms and reinforcing are in place (see foundation inspection rules), and provide the sealed design/drawings to the building official as required.
Related provisions (quick pointers)
- § R404.1 — Concrete and masonry foundation walls (general selection & construction).
- § R404.1.1 — Design required (hydrostatic pressure; >48 in unbalanced backfill).
- § R404.1.2 — Design of masonry foundation walls; use of TMS 402 or code tables; seal notes.
- § R404.1.3 — Concrete foundation wall design and references to ACI 318/ACI 332/PCA 100.
- § R404.4 — Retaining walls (design required for retaining >48 in unbalanced fill not laterally supported at top).
- § R306.3.9 — Flood-hazard construction documents; sealed documentation required for certain flood designs.
- § R106.1 — Construction documents to be prepared by a registered design professional where required by the jurisdiction.
- § R109.1.1 — Foundation inspection timing and expectations.
Code references
Grounded in the retrieved California Residential Code — click a citation to read the verbatim passage:
CRC § 3.9. High relevance — show source text
- Flood and wave loads shall be determined in accordance with ASCE 7 and shall include loads associated with the design flood. Wind loads shall be those required by this code.
- Foundation designs and construction documents shall be prepared and sealed in accordance with Section R306.3.9.
Exception: In Coastal A Zones, stem wall foundations supporting a floor system above and backfilled with soil or gravel to the underside of the floor system shall be permitted provided that the foundations are designed to account for wave action, debris impact, erosion and local scour. Where soils are susceptible to erosion and local scour, stem wall foundations shall have deep footings to account for the loss of soil.
R306.3.4 Concrete slabs. Concrete slabs used for parking, floors of enclosures, landings, decks, walkways, patios and similar uses that are located beneath structures, or slabs that are located such that if undermined or displaced during base flood conditions could cause structural damage to the building foundation, shall be designed and constructed in accordance with one of the following:
- To be structurally independent of the foundation system of the structure, to not transfer flood loads to the main structure, and to be frangible and break away under flood conditions prior to base flood conditions. Slabs shall be a maximum of 4 inches (102 mm) thick, shall not have turned-down edges, shall not contain reinforcing, shall have isolation joints at pilings and columns, and shall have control or construction joints in both directions spaced not more than 4 feet (1219 mm) apart.
- To be self-supporting, structural slabs capable of remaining intact and functional under base flood conditions, including erosion and local scour, and the main structure shall be capable of resisting any added flood loads and effects of local scour caused by the presence of the slabs.
R306.3.5 Walls below required elevation. Walls and partitions are permitted below the elevation required in Section R306.3.2, provided that such walls and partitions are not part of the structural support of the building or structure and:
- Electrical, mechanical and plumbing system components are not to be mounted on or penetrate through walls that are designed to break away under flood loads; and
- Are constructed with insect screening or open lattice; or
- Are designed to break away or collapse without causing collapse, displacement or other structural damage to the elevated portion of the building or supporting foundation system. Such walls, framing and connections shall have a resistance of not less than 10 (479 Pa) and not more than 20 pounds per square foot (958 Pa) as determined using allowable stress design, or a resistance to an ultimate load of not less than 17 and not more than 33 pounds per square foot (814 and 1580 Pa); or
2025 CALIFORNIA RESIDENTIAL CODE 3-39
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
BUILDING PLANNING
- Where wind loading values of this code exceed 20 pounds per square foot (958 Pa), as determined using allowable stress design or an ultimate load of 33 pounds per square foot (1580 Pa), the construction documents shall include documentation prepared and sealed by a registered design professional that: 4.1. The walls and partitions below the required elevation have been designed to collapse from a water load less than that which would occur during the base flood. 4.2. The elevated portion of the building and supporting foundation system have been designed to withstand the effects of wind and flood loads acting simultaneously on structural and nonstructural building components.
CRC § 3.5 High relevance — show source text
R306.3.5 Walls below required elevation. Walls and partitions are permitted below the elevation required in Section R306.3.2, provided that such walls and partitions are not part of the structural support of the building or structure and:
- Electrical, mechanical and plumbing system components are not to be mounted on or penetrate through walls that are designed to break away under flood loads; and
- Are constructed with insect screening or open lattice; or
- Are designed to break away or collapse without causing collapse, displacement or other structural damage to the elevated portion of the building or supporting foundation system. Such walls, framing and connections shall have a resistance of not less than 10 (479 Pa) and not more than 20 pounds per square foot (958 Pa) as determined using allowable stress design, or a resistance to an ultimate load of not less than 17 and not more than 33 pounds per square foot (814 and 1580 Pa); or
2025 CALIFORNIA RESIDENTIAL CODE 3-39
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
BUILDING PLANNING
- Where wind loading values of this code exceed 20 pounds per square foot (958 Pa), as determined using allowable stress design or an ultimate load of 33 pounds per square foot (1580 Pa), the construction documents shall include documentation prepared and sealed by a registered design professional that: 4.1. The walls and partitions below the required elevation have been designed to collapse from a water load less than that which would occur during the base flood. 4.2. The elevated portion of the building and supporting foundation system have been designed to withstand the effects of wind and flood loads acting simultaneously on structural and nonstructural building components. Water-loading values used shall be those associated with the design flood. Wind-loading values shall be those required by this code.
- Walls intended to break away under flood loads as specified in Item 3 or 4 have flood openings that meet the criteria in Section R306.2.2, Item 2.
Exceptions: The following shall not be required to comply with this section:
Elevator shafts.
Utility chases that protect utility lines from freezing, provided that the utility chases are the minimum size necessary to protect the utility lines and do not provide access for a person to enter the space.
R306.3.6 Enclosed areas below required elevation. Enclosed areas below the elevation required in Section R306.3.2 shall be used solely for parking of vehicles, building access or storage.
R306.3.6.1 Protection of building envelope. An exterior door that meets the requirements of Section R609 shall be installed at the top of stairs that provide access to the building and that are enclosed with walls designed to break away in accordance with Section R306.3.5.
R306.3.7 Stairways and ramps. Stairways and ramps that are located below the lowest floor elevations specified in Section R306.3.2 shall comply with one or more of the following:
- Be designed and constructed with open or partially open risers and guards.
- Stairways and ramps not part of the required means of egress shall be designed and constructed to break away during design flood conditions without causing damage to the building or structure, including foundation.
- Be retractable, or able to be raised to or above the lowest floor elevation, provided that the ability to be retracted or raised prior to the onset of flooding is not contrary to the means of egress requirements of the code.
CRC § 25.4 High relevance — show source text
ML-CL and**
inorganic CL 60| |8|4|NR|NR|NR| |8|5|NR|6 @ 39|6 @ 48| |8|6|5 @ 39|6 @ 48|6 @ 35| |8|7|6 @ 48|6 @ 34|6 @ 25| |8|8|6 @ 39|6 @ 25|6 @ 18| |9|4|NR|NR|NR| |9|5|NR|5 @ 37|6 @ 48| |9|6|5 @ 36|6 @ 44|6 @ 32| |9|7|6 @ 47|6 @ 30|6 @ 22| |9|8|6 @ 34|6 @ 22|6 @ 16| |9|9|6 @ 27|6 @ 17|DR| |10|4|NR|NR|NR| |10|5|NR|5 @ 35|6 @ 48| |10|6|6 @ 48|6 @ 41|6 @ 30| |10|7|6 @ 43|6 @ 28|6 @ 20| |10|8|6 @ 31|6 @ 20|DR| |10|9|6 @ 24|6 @ 15|DR| |10|10|6 @ 19|DR|DR| |For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.
NR = Not Required.
DR = Design Required.
a. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R401.4.1(2).
b. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical
reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
c. Vertical reinforcement with a yield strength of less than 60,000 psi and bars of a different size than specified in the table are permitted in accordance with Section
R404.1.3.3.7.6 and Table R404.1.3.2(9).
d. Deflection criterion is_L_/240, where_L_ is the height of the basement wall in inches.
e. Interpolation is not permitted.
f. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
g. NR indicates vertical wall reinforcement is not required, except for 6-inch-nominal walls formed with stay-in-place forming systems in which case vertical reinforcement shall
be No. 4@48 inches on center.
h. See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
i. See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
j. DR means design is required in accordance with the applicable building code, or in the absence of a code, in accordance with ACI 318.
k.CRC § 304.8 High relevance — show source text
4 mm, 1 foot = 304.8 mm, 1 mph = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mph = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mph = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mph = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mph = 0.447 m/s.|
SECTION R404—FOUNDATION AND RETAINING WALLS
R404.1 Concrete and masonry foundation walls. Concrete foundation walls shall be selected and constructed in accordance with the provisions of Section R404.1.3. Masonry foundation walls shall be selected and constructed in accordance with the provisions of Section R404.1.2.
R404.1.1 Design required. Concrete or masonry foundation walls shall be designed in accordance with accepted engineering practice where either of the following conditions exists:
- Walls are subject to hydrostatic pressure from ground water.
- Walls supporting more than 48 inches (1219 mm) of unbalanced backfill that do not have permanent lateral support at the top or bottom.
R404.1.2 Design of masonry foundation walls. Masonry foundation walls shall be designed and constructed in accordance with the provisions of this section or in accordance with the provisions of TMS 402. Where TMS 402 or the provisions of this section are used to design masonry foundation walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority.
R404.1.2.1 Masonry foundation walls. Concrete masonry and clay masonry foundation walls shall be constructed as set forth in Table R404.1.2.1(1), R404.1.2.1(2), R404.1.2.1(3) or R404.1.2.1(4) and shall comply with applicable provisions of Section R606. In buildings assigned to Seismic Design Categories D 0, D 1 and D 2, concrete masonry and clay masonry foundation walls shall also comply with Section R404.1.4.1. Rubble stone masonry foundation walls shall be constructed in accordance with Sections R404.1.8 and R606.4.2. Rubble stone masonry walls shall not be used in Seismic Design Categories D 0, D 1 and D 2, or in townhouses in Seismic Design Category C.
4-24 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FOUNDATIONS
TABLE R404.1.2.1(1)—PLAIN MASONRY FOUNDATION WALLSf Col2 Col3 Col4 Col5 ** MAXIMUM**
UNSUPPORTED
WALL HEIGHT
(feet)** MAXIMUM**
UNBALANCED
BACKFILL HEIGHTc
(feet)** PLAIN MASONRYa MINIMUM NOMINAL WALL THICKNESS (inches)** ** PLAIN CRC § 2.4 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FOUNDATIONS
R404.2.4 Backfilling. Wood foundation walls shall not be backfilled until the basement floor and first floor have been constructed or the walls have been braced. For crawl space construction, backfill or bracing shall be installed on the interior of the walls prior to placing backfill on the exterior.
R404.2.5 Drainage and dampproofing. Wood foundation basements shall be drained and dampproofed in accordance with Sections R405 and R406, respectively.
R404.2.6 Fastening. Wood structural panel foundation wall sheathing shall be attached to framing in accordance with Table R602.3(1) and Section R402.1.1.
R404.3 Wood sill plates. Wood sill plates shall be not less than 2-inch by 4-inch (51 mm by 102 mm) nominal lumber. Sill plate anchorage shall be in accordance with Sections R403.1.6 and R602.11.
R404.4 Retaining walls. Retaining walls that are not laterally supported at the top and that retain in excess of 48 inches (1219 mm) of unbalanced fill, or retaining walls exceeding 24 inches (610 mm) in height that resist lateral loads in addition to soil, shall be designed in accordance with accepted engineering practice to ensure stability against overturning, sliding, excessive foundation pressure and water uplift. Retaining walls shall be designed for a safety factor of 1.5 against lateral sliding and overturning. This section shall not apply to foundation walls supporting buildings.
R404.5 Precast concrete foundation walls.
R404.5.1 Design. Precast concrete foundation walls shall be designed in accordance with accepted engineering practice. The design and manufacture of precast concrete foundation wall panels shall comply with the materials requirements of Section R402.3 or ACI 318. The panel design drawings shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section R106.1.
R404.5.2 Precast concrete foundation design drawings. Precast concrete foundation wall design drawings shall be submitted to the building official and approved prior to installation. Drawings shall include, at a minimum, the following information:
Design loading as applicable.
Footing design and material.
Concentrated loads and their points of application.
Soil bearing capacity.
Maximum allowable total uniform load.
Seismic design category.
Basic wind speed.
R404.5.3 Identification. Precast concrete foundation wall panels shall be identified by a certificate of inspection label issued by an approved third-party inspection agency.
SECTION R405 —FOUNDATION DRAINAGE
R405.1 Concrete or masonry foundations. Drains shall be provided around concrete or masonry foundations that retain earth and enclose habitable or usable spaces located below grade. Drainage tiles, gravel or crushed stone drains, perforated pipe or other approved systems or materials shall be installed at or below the top of the footing or below the bottom of the slab and shall discharge by gravity or mechanical means into an approved drainage system. Gravel or crushed stone drains shall extend not less than 1 foot (305 mm) beyond the outside edge of the footing and 6 inches (152 mm) above the top of the footing and be covered with an approved filter membrane material. The top of open joints of drain tiles shall be protected with strips of building paper.
CRC § 1612.3.2 High relevance — show source text
source.
- Determine the design flood elevation or floodway in accordance with accepted hydrologic and hydraulic engineering practices used to define special flood hazard areas. Determinations shall be undertaken by a registered design professional who shall document that the technical methods used reflect currently accepted engineering practice.
1612.3.2 Determination of impacts. In riverine flood hazard areas where design flood elevations are specified but floodways have not been designated, the applicant shall provide a floodway analysis that demonstrates that the proposed work will not increase the design flood elevation more than 1 foot (305 mm) at any point within the jurisdiction of the applicable governing authority.
1612.4 Flood hazard documentation. The following documentation shall be prepared and sealed by a registered design professional and submitted to the building official:
- For construction in flood hazard areas other than coastal high hazard areas or coastal A zones: 1.1. The elevation of the lowest floor, including the basement, as required by the lowest floor elevation inspection in Section 110.3.3 and for the final inspection in Section 110.3.12.1. 1.2. For fully enclosed areas below the design flood elevation where provisions to allow for the automatic entry and exit of floodwaters do not meet the minimum requirements in Section 2.7.2.1 of ASCE 24, construction documents shall include a statement that the design will provide for equalization of hydrostatic flood forces in accordance with Section 2.7.2.2 of ASCE 24.
2025 CALIFORNIA BUILDING CODE 16-33
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STRUCTURAL DESIGN
1.3. For dry floodproofed nonresidential buildings, construction documents shall include a statement that the dry floodproofing is designed in accordance with ASCE 24 and shall include the flood emergency plan specified in Chapter 6 of ASCE 24. 1.4. For dry floodproofed nonresidential buildings, the elevation to which the building is dry floodproofed as required for the final inspection in Section 110.3.12.1. 2. For construction in coastal high hazard areas and coastal A zones: 2.1. The elevation of the bottom of the lowest horizontal structural member as required by the lowest floor elevation inspection in Section 110.3.3 and for the final inspection in Section 110.3.12.1. 2.2. Construction documents shall include a statement that the building is designed in accordance with ASCE 24, including that the pile or column foundation and building or structure to be attached thereto is designed to be anchored to resist flotation, collapse and lateral movement due to the effects of wind and flood loads acting simultaneously on all building components, and other load requirements of Chapter 16. 2.3. For breakaway walls designed to have a resistance of more than 20 psf (0.96 kN/m [2] ) determined using allowable stress design or a resistance to an ultimate load of more than 33 pounds per square foot (1.58 kN/m [2] ), construction documents shall include a statement that the breakaway wall is designed in accordance with ASCE 24. 2.4 For breakaway walls where provisions to allow for the automatic entry and exit of floodwaters do not meet the minimum requirements in Section 2.7.2.1 of ASCE 24, construction documents shall include a statement that the design will provide for equalization of hydrostatic flood forces in accordance with Section 2.7.2.2 of ASCE 24.
SECTION 1613—EARTHQUAKE LOADS
CRC § 1.4 High relevance — show source text
VERIFIED PER A304.1.4
For SI: 1 inch = 25.4 mm, 1 pound = 4.4 N. NOTE: See Section A304.4 for cripple wall bracing.
����������������������������������
NEW 2x BLOCKING. SEE REQUIREMENTS
WHERE EXISTING NAILING FROM EXISTING RIM
JOIST TO TOP PLATE CANNOT BE VERIFIED
PROVIDE NEW ¾ WOOD STRUCTURAL PANEL" BLOCKING. SEE REQUIREMENTS ABOVE.
�������������������������������
[BS] A304.2 Foundations.
[BS] A304.2.1 New perimeter foundations. New perimeter foundations shall be provided for structures with the structural weaknesses noted in Items 1 and 2 of Section A303. Soil investigations or geotechnical studies are not required for this work unless the building is located in a special study zone as designated by the code official or other authority having jurisdiction.
[BS] A304.2.2 Evaluation of existing foundations. Partial perimeter foundations or unreinforced masonry foundations shall be evaluated by a registered design professional for the force levels specified in Section A301.3. Test reports or other substantiating data to determine existing foundation material strengths shall be submitted to the code official. Where approved by the code official, these existing foundation systems shall be strengthened in accordance with the recommendations included with the evaluation in lieu of being replaced.
Exception: In lieu of testing existing foundations to determine material strengths, and where approved by the code official, a new nonperimeter foundation system designed for the forces specified in Section A301.3 shall be used to resist lateral forces from perimeter walls. A registered design professional shall confirm the ability of the existing diaphragm to transfer seismic forces to the new nonperimeter foundations.
[BS] A304.2.3 Details for new perimeter foundations. All new perimeter foundations shall be continuous and constructed according to Figure A304.2.3(1) and Table A304.2.3(1) or Figure A304.2.3(2) and Table A304.2.3(2). New construction materials
APPENDIX A-32 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS
shall comply with the requirements of building code. Where approved by the code official, the existing clearance between existing floor joists or girders and existing grade below the floor need not comply with the building code.
Exception: Where designed by a registered design professional and approved by the code official, partial perimeter foundations shall be used in lieu of a continuous perimeter foundation.
[BS]TABLE A304.2.3(1)—NEW REINFORCED CONCRETE FOUNDATION SYSTEM Col2 Col3 Col4 Col5 Col6 Col7 Col8 MINIMUM FOUNDATION DIMENSIONS MINIMUM FOUNDATION DIMENSIONS MINIMUM FOUNDATION DIMENSIONS MINIMUM FOUNDATION DIMENSIONS MINIMUM FOUNDATION DIMENSIONS MINIMUM FOUNDATION DIMENSIONS MINIMUM FOUNDATION
REINFORCINGMINIMUM FOUNDATION
REINFORCINGNumber
of storiesW F **Da, b, CRC § 0.90 High relevance — show source text
00|0.90|DR|DR|DR| |Minimum
1× wood
furringd|Minimum
2× wood
stud|No.10
wood
screw|1|24|4.00|0.90|DR|DR|DR|2.85|DR|DR|DR|DR| |Minimum
1× wood
furringd|Minimum
2× wood
stud|1/4″
lag screw|11/2|12|4.00|2.65|1.90|1.50|0.90|4.00|1.65|1.05|0.80|DR| |Minimum
1× wood
furringd|Minimum
2× wood
stud|1/4″
lag screw|11/2|16|4.00|1.95|1.25|0.95|0.50|4.00|1.10|0.65|DR|DR| |Minimum
1× wood
furringd|Minimum
2× wood
stud|1/4″
lag screw|11/2|24|4.00|1.10|0.65|DR|DR|3.25|0.50|DR|DR|DR| |For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa.
DR = Design Required.
o.c. = On Center.
a. Wood framing and furring shall be Spruce-pine-fir or any wood species with a specific gravity of 0.42 or greater in accordance with AWC NDS.
b. Nail fasteners shall comply with ASTM F1667, except nail length shall be permitted to exceed ASTM F1667 standard lengths.
c. The thickness of wood structural panels complying with the specific gravity requirements of Note a shall be permitted to be included in satisfying the minimum required pene-
tration into framing.
d. Where the required cladding fastener penetration into wood material exceeds3/4 inch and is not more than 11/2 inches, a minimum 2× wood furring or an approved design shall
be used.
e. Foam sheathing shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289.
f. Furring shall be spaced not more than 24 inches on center, in a vertical or horizontal orientation. In a vertical orientation, furring shall be located over wall studs and attached
with the required fastener spacing. In a horizontal orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall be achieved by use of two fasteners into studs
at 16 inches and 24 inches on center, respectively.
g. Cladding weight is the maximum weight of cladding materials in pounds per square foot of wall area. The 3 psf category typically applies to panel and lap siding materials; the
11 psf category typically applies to conventional three-coat stucco of7/8-inch thickness; and 15 psf to 25 psf categories typically apply to adhered masonry veneers.|For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa.
DR = Design Required.
o.c. = On Center.
a.CRC § 1.3 High relevance — show source text
Where an interior concrete slab-on-grade is provided and in contact with the interior surface of the foundation wall, measurement of
the unbalanced backfill height is permitted to be measured from the exterior finish ground level to the top of the interior concrete slab is permitted.
f. The use of this table shall be prohibited for soil classifications not shown.|R404.1.3 Concrete foundation walls. Concrete foundation walls that support light-frame walls shall be designed and constructed in accordance with the provisions of this section, ACI 318, ACI 332 or PCA 100. Concrete foundation walls that support above-grade concrete walls that are within the applicability limits of Section R608.2 shall be designed and constructed in accordance with the provisions of this section, ACI 318, ACI 332 or PCA 100. Concrete foundation walls that support above-grade concrete walls that are not within the applicability limits of Section R608.2 shall be designed and constructed in accordance with the provisions of ACI 318, ACI 332 or PCA 100. Where ACI 318, ACI 332, PCA 100 or the provisions of this section are used to design concrete foundation walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority.
R404.1.3.1 Concrete cross section. Concrete walls constructed in accordance with this code shall comply with the shapes and minimum concrete cross-sectional dimensions required by Table R608.3. Other types of forming systems resulting in concrete walls not in compliance with this section and Table R608.3 shall be designed in accordance with ACI 318.
4-28 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FOUNDATIONS
R404.1.3.2 Reinforcement for foundation walls. Concrete foundation walls shall be laterally supported at the top and bottom. Horizontal reinforcement shall be provided in accordance with Table R404.1.3.2(1). Vertical reinforcement shall be provided in accordance with Table R404.1.3.2(2), R404.1.3.2(3), R404.1.3.2(4), R404.1.3.2(5), R404.1.3.2(6), R404.1.3.2(7) or R404.1.3.2(8). Vertical reinforcement for flat basement walls retaining 4 feet (1219 mm) or more of unbalanced backfill is permitted to be determined in accordance with Table R404.1.3.2(9). For basement walls supporting above-grade concrete walls, vertical reinforcement shall be the greater of that required by Tables R404.1.3.2(2) through R404.1.3.2(8) or by Section R608.6 for the above-grade wall. In buildings assigned to Seismic Design Category D 0, D 1 or D 2, concrete foundation walls shall also comply with Section R404.1.4.2.
TABLE R404.1.3.2(1)—MINIMUM HORIZONTAL REINFORCEMENT FOR CONCRETE BASEMENT WALLSa, b Col2 ** MAXIMUM UNSUPPORTED**
WALL HEIGHT (feet)** LOCATION OF HORIZONTAL REINFORCEMENT** ≤ 8 One No. CRC § 1-23 Medium relevance — show source text
R108.6 Work commencing before permit issuance. Any person who commences work requiring a permit on a building, structure, electrical, gas, mechanical or plumbing system before obtaining the necessary permits shall be subject to a fee established by the applicable governing authority that shall be in addition to the required permit fees.
SECTION R109—INSPECTIONS
R109.1 Types of inspections. For on-site construction, from time to time the building official, upon notification from the permit holder or his agent, shall make or cause to be made any necessary inspections and shall either approve that portion of the construction as completed or shall notify the permit holder or his or her agent wherein the same fails to comply with this code. The enforcing
2025 CALIFORNIA RESIDENTIAL CODE 1-23
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
DIVISION II SCOPE AND ADMINISTRATION
agency upon notification of the permit holder or their agent shall within a reasonable time make the inspections set forth in Sections R109.1.1, R109.1.1.1, R109.1.3, R109.1.4, R109.1.4.1, R109.1.4.2, R109.1.5, R109.1.5.1, R109.1.5.2, R109.1.5.3, R109.1.6, R109.1.6.1 and
R109.1.6.2.
Note: Reinforcing steel or structural framework of any part of any building or structure shall not be covered or concealed without first obtaining the approval of the enforcing agency.
R109.1.1 Foundation inspection. Inspection of the foundation and footings shall be made after poles or piers are set or trenches or basement areas are excavated and any required forms erected and any required reinforcing steel is in place and supported prior to the placing of concrete. The foundation or footings inspection shall include excavations for thickened slabs intended for the support of bearing walls, partitions, structural supports, or equipment and special requirements for wood foundations. Mate- rials for the foundation shall be on the job site except where concrete is ready-mixed in accordance with ASTM C94. Under this circumstance, concrete is not required to be at the job site.
R109.1.1.1 Concrete slab and under-floor inspection. Concrete slab and under-floor inspections shall be made after in-slab or under-floor reinforcing steel and building service equipment, conduits, piping or other ancillary building trade products or equip- ment are installed, but before any concrete is placed or floor sheathing is installed, including the subfloor.
R109.1.2 Plumbing, mechanical, gas and electrical systems inspection. Rough inspection of plumbing, mechanical, gas and electrical systems shall be made prior to covering or concealment, before fixtures or appliances are set or installed, and prior to framing inspection.
Exception: Backfilling of ground-source heat pump loop systems tested in accordance with the California Mechanical Code prior to inspection shall be permitted.
R109.1.3 Floodplain inspections. For construction in flood hazard areas as established by Table R301.2, upon placement of the lowest floor, including basement, and prior to further vertical construction, the building official shall require submission of documentation, prepared and sealed by a registered design professional, of the elevation of the lowest floor, including basement, required in Section R306.
CRC § 2.2 Medium relevance — show source text
Wind-loading values shall be those required by this code. 5. Walls intended to break away under flood loads as specified in Item 3 or 4 have flood openings that meet the criteria in Section R306.2.2, Item 2.
Exceptions: The following shall not be required to comply with this section:
Elevator shafts.
Utility chases that protect utility lines from freezing, provided that the utility chases are the minimum size necessary to protect the utility lines and do not provide access for a person to enter the space.
R306.3.6 Enclosed areas below required elevation. Enclosed areas below the elevation required in Section R306.3.2 shall be used solely for parking of vehicles, building access or storage.
R306.3.6.1 Protection of building envelope. An exterior door that meets the requirements of Section R609 shall be installed at the top of stairs that provide access to the building and that are enclosed with walls designed to break away in accordance with Section R306.3.5.
R306.3.7 Stairways and ramps. Stairways and ramps that are located below the lowest floor elevations specified in Section R306.3.2 shall comply with one or more of the following:
- Be designed and constructed with open or partially open risers and guards.
- Stairways and ramps not part of the required means of egress shall be designed and constructed to break away during design flood conditions without causing damage to the building or structure, including foundation.
- Be retractable, or able to be raised to or above the lowest floor elevation, provided that the ability to be retracted or raised prior to the onset of flooding is not contrary to the means of egress requirements of the code.
- Be designed and constructed to resist flood loads and minimize transfer of flood loads to the building or structure, including foundation.
Areas below stairways and ramps shall not be enclosed with walls below the elevation required in Section R306.3.2 unless such walls are constructed in accordance with Section R306.3.5.
R306.3.8 Decks and porches. Attached decks and porches shall meet the elevation requirements of Section R306.3.2 and shall either meet the foundation requirements of this section or shall be cantilevered from or knee braced to the building or structure. Self-supporting decks and porches that are below the elevation required in Section R306.3.2 shall not be enclosed by solid, rigid walls, including walls designed to break away. Self-supporting decks and porches shall be designed and constructed to remain in place during base flood conditions or shall be frangible and break away under base flood conditions.
R306.3.9 Construction documents. The construction documents shall include documentation that is prepared and sealed by a registered design professional that the design and methods of construction to be used meet the applicable criteria of this section.
R306.3.10 Tanks. Underground tanks shall be anchored to prevent flotation, collapse and lateral movement under conditions of the base flood. Above-ground tanks shall be installed at or above the elevation required in Section R306.3.2. Where elevated on platforms, the platforms shall be cantilevered from or knee braced to the building or shall be supported on foundations that conform to the requirements of Section R306.3.
SECTION R307—STORM SHELTERS
CRC § 1202.4. Medium relevance — show source text
The procedure used to establish the final ground level adjacent to the foundation shall account for additional settlement of the backfill.
1804 A .5 Grading and fill in flood hazard areas. In flood hazard areas established in Section 1612 A .3, grading, fill, or both, shall not be approved:
- Unless such fill is placed, compacted and sloped to minimize shifting, slumping and erosion during the rise and fall of flood water and, as applicable, wave action.
- In floodways, unless it has been demonstrated through hydrologic and hydraulic analyses performed by a registered design professional in accordance with standard engineering practice that the proposed grading or fill, or both, will not result in any increase in flood levels during the occurrence of the design flood.
- In coastal high hazard areas, unless such fill is conducted or placed to avoid diversion of water and waves toward any building or structure.
- Where design flood elevations are specified but floodways have not been designated, unless it has been demonstrated that the cumulative effect of the proposed flood hazard area encroachment, when combined with all other existing and anticipated flood hazard area encroachment, will not increase the design flood elevation more than 1 foot (305 mm) at any point.
1804 A .6 Compacted fill material. Where shallow foundations will bear on compacted fill material, the compacted fill shall comply with the provisions of an approved geotechnical report, as set forth in Section 1803 A .
Exception: Compacted fill material 12 inches (305 mm) in depth or less need not comply with an approved report, provided that the in-place dry density is not less than 90 percent of the maximum dry density at optimum moisture content determined in accordance with ASTM D1557. The compaction shall be verified by special inspection in accordance with Section 1705 A .6.
1804 A .7 Controlled low-strength material (CLSM). Where shallow foundations will bear on controlled low-strength material (CLSM), the CLSM shall comply with the provisions of an approved geotechnical report, as set forth in Section 1803 A .
SECTION 1805 A —DAMPPROOFING AND WATERPROOFING
1805 A .1 General. Walls or portions thereof that retain earth and enclose interior spaces and floors below grade shall be waterproofed and dampproofed in accordance with this section, with the exception of those spaces containing groups other than residential and institutional where such omission is not detrimental to the building or occupancy.
Ventilation for crawl spaces shall comply with Section 1202.4.
1805 A .1.1 Story above grade plane. Where a basement is considered a story above grade plane and the finished ground level adjacent to the basement wall is below the basement floor elevation for 25 percent or more of the perimeter, the floor and walls shall be dampproofed in accordance with Section 1805 A .2 and a foundation drain shall be installed in accordance with Section 1805 A .4.2. The foundation drain shall be installed around the portion of the perimeter where the basement floor is below ground level. The provisions of Sections 1803 A .5.4, 1805 A .3 and 1805 A .4.1 shall not apply in this case.
Frequently asked questions
Do all foundation walls over 48 inches need an engineer?
If a wall supports more than 48 inches of unbalanced backfill and lacks permanent lateral support at top or bottom, yes — that condition triggers the design requirement in § R404.1.1(2) and the wall must be designed in accordance with accepted engineering practice.
What counts as “unbalanced backfill” measurement?
Unbalanced backfill is the retained soil not balanced by soil or slab on the other side. If an interior concrete slab-on-grade is in contact with the interior wall face, the code permits measuring the unbalanced height from exterior finish grade to the top of that interior slab.
If I’m using code tables for masonry, do I still need a seal?
Masonry foundation walls designed using the code tables or TMS 402 may not require the architect/engineer seal unless state law or the local jurisdiction requires it — see § R404.1.2. However, when § R404.1.1 triggers a required engineering design, expect sealed drawings where the jurisdiction requires them.
Does groundwater always force an engineered design?
Yes — if the foundation wall is subject to hydrostatic pressure from groundwater, the wall must be designed in accordance with accepted engineering practice under § R404.1.1(1).
What about floodplain locations?
If the structure is in a flood hazard area, additional Chapter R306 requirements apply; some flood-related designs and documentation must be prepared and sealed by a registered design professional. See § R306.3.9 and related flood provisions.
More in California Residential Code
Ask about the CRC
Get cited, plain-English answers on the California Residential Code for your project — any code section, any scenario.
Start Free TrialRelated in the CRC
What are the rules for wood foundation walls and sill plate anchorage?
What are the design requirements for freestanding and retaining walls?
How are concrete and masonry foundation walls selected and sized (thickness, reinforcement)?
Foundation and retaining wall requirements
California Residential Code