CRSC · California Referenced Standards Code
Performance tests, environmental exposure, markings & instructions
This hub orients readers to CRSC provisions that set the test procedures, environmental conditioning, and marking/instruction requirements used to demonstrate product performance and field readiness.
Last reviewed: July 6, 2026
Overview
This area of the California Referenced Standards Code (CRSC) collects the test methods, conditioning procedures, and product identification and manual requirements used to verify performance and durability of building products and assemblies. It includes environmental-conditioning protocols (e.g., elevated, low and humidity conditioning) used to simulate field exposure and confirm continued operation, as set out in Sec. 12‑3‑10 § — Environmental Exposure Test . It also contains the mandatory marking and user/installation‑instruction provisions in Secs. 12‑3‑12 and 12‑3‑13 § that prescribe permanent identification, release/operation diagrams, and required installation/maintenance instructions .
Performance testing in the CRSC spans a range of SFM standards (fire‑resistive tests, endurance and abuse tests, and wildfire‑exposure methods) used to judge acceptance — for example, fire door assembly tests at Sec. 12‑7‑400 § and large‑scale test furnace requirements , and the wildfire exposure tests for eaves, windows and decking under SFM 12‑7A (see the horizontal‑projection and decking standards and their heat‑release and duration criteria) . These sections matter because passing the prescribed test exposures, and providing the required markings and instructions, is the basis for listing, field acceptance and safe operation of the product.
In this section
Code references
Grounded in the retrieved California Referenced Standards Code — click a citation to read the verbatim passage:
CRSC § 2.2. High relevance — show source text
2.2. Gypsum board for mounting around the window once it is installed; 2.3. Pieces of gypsum cut into narrow strips for use as trim around the window; 2.4. Caulk to be used as per the window manufacturer's instructions. 3. Wall assembly. A noncombustible wall shall be used with a manufacturer or code-specified opening for the particular window. Install window in framed rough opening following manufacturer guidelines. Apply manufacturer-recommended caulk to nailing flange prior to installation. Use narrow strips of gypsum board as trim around window, covering the nail flange of the window. Any type of framing material may be tested. 3.1. Fit the window test assembly into the rear wall of the Wall Assembly Test Module, sealing all edges, including the soffit-to-wall joint. Ceramic wool or comparable material shall be used for sealing.
12-7A-2.7 Conduct of tests.
Burner output verification. Without the window in place, set the burner for 150 kW output. Conduct a verification run of 3 minutes to assure the heat release rate, and then turn off the burner.
Test. Place the burner against the wall assembly at the center. Ignite the burner at the 150 kW output and control during the test for constant and uniform output. Optional radiometers can be placed behind the Wall Assembly Test Module to measure heat flux through the window glass.
Duration and observations. The test shall be continued until flame-through occurs at the window. Flame-through can occur at the glass (glazing) and/or in the frame. At this point, the burner shall be extinguished and the assembly monitored for sustained combustion. Note the time elapsed and location of penetration if it occurs.
Report. Report a description of the window unit, including the types of frames, cladding and panes being tested and details of the installation. Record when and how the glass breaks or flame-through occurs in the framing materials or sash, and/or
2025 CALIFORNIA REFERENCED STANDARDS CODE 41
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
if the framing material deforms or otherwise suffers a loss of integrity such that the glass cannot be held in place, and a record of the time at which any of these events occur.
12-7A-2.8 Conditions of Acceptance.
- Duration of direct flame exposure. To pass this test standard, the window and window assembly shall withstand 8 minutes of direct flame exposure with the absence of flame penetration through the window frame or pane, or structural failure of the window frame or pane.
- Flame penetration or structural failure. Flame penetration or structural failure of the flame or pane anytime during the test constitutes failure of this test standard.
FIGURE 1 — SCHEMATIC OF THE WALL ASSEMBLY Test Module used for evaluating the fire performance of a window.
42 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
HORIZONTAL PROJECTION UNDERSIDE
SFM STANDARD 12-7A-3
CRSC § 9.5 High relevance — show source text
The specimen shall be suspended vertically with its lower edge 2 inches (51 mm) above the top of a [3] / 8 inch (9.5 mm) diameter Bunsen Burner. The test shall be performed in a draft-free area.
The flames from the burner shall be 4 inches (101 mm) long and shall be adjusted with sufficient air supply to eliminate any yellow flame tips but without any distinct inner blue cone.
The specimen shall be exposed to the flame at each corner and at not less than one other point along the lower edge. Each exposure shall be of sufficient duration to determine if the material will ignite and continue to burn, but shall be not less than 20 seconds.
The criteria for acceptance shall be as follows: (A) There shall be not more than intermittent flaming appreciably beyond the area exposed to the test flame. (B) Flame shall not reach the top of the specimen. (C) On removing the test flame there shall be not more than 1 second of after flaming except there may be nonprogressive flaming of short duration in areas of accumulated char which were directly exposed to the test flame.
Section 12-7-502
(a) Framed rigid combustible decorative material. Rigid combustible decorative material and assemblies of materials not more than [1] / 4 inch (6 mm) in thickness used for folding doors, room dividers, decorative screens and similar applications, and which are installed with all edges protected, shall conform to the following:
All exposed edges shall be protected with frames of metal or other noncombustible material, or solid wood of minimum [1] / 4 inch (6 mm) dimension.
The total square foot area of the material shall not exceed ten percent of that of the floor area of the room in which the material is installed.
When tested as follows, flames shall not reach the top edge of the specimen. The test shall be conducted in a draft free area, on a specimen of the material 12 inches by 12 inches (305 mm by 305 mm) suspended at a 45-degree angle from the horizontal with the upper and lower edges in a horizontal plane. The test flame shall be 3 inches (76 mm) long from a Bunsen burner of approximately [1] / 2 -inch (13 mm) inside diameter with the air supply completely shut off. The burner shall be positioned so that its top is 1 inch (25 mm) vertically below a point on the lower surface of the test specimen, 1 inch (25 mm) up from its lower horizontal edge and midway between the inclined edges. The exposure to the test flame and the duration of test shall be for a period of 2 minutes.
2025 CALIFORNIA REFERENCED STANDARDS CODE 35
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
36 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-7A MATERIALS AND CONSTRUCTION METHODS
FOR EXTERIOR WILDFIRE EXPOSURE
EXTERIOR WALL SIDING AND SHEATHING
SFM STANDARD 12-7A-1
12-7A-1.1 Application. The minimum design, construction and performance standards set forth herein for exterior wall siding and sheathing are those deemed necessary to establish conformance to the provisions of these regulations. Materials and assemblies that meet the performance criteria of this standard are acceptable for use as defined in California Building Standards Code.
CRSC § 410-66. High relevance — show source text
Insulation boards exclusive of facings and membranes shall not exceed the following values:
Flame spread. . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Smoke developed. . . . . . . . . . . . . . . . . . . . . . . 50 (i) Mineral fiber in loose fill form.
- Composition. Mineral fiber insulation shall be made from mineral substances such as rock, slag or glass processed from a molten state into fibrous form. The insulation shall be mechanically processed to produce a mineral fiber suitable for pneumatic or poured application.
2025 CALIFORNIA REFERENCED STANDARDS CODE 93
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STANDARDS FOR INSULATING MATERIAL
- Thermal performance. Determination of the thermal performance shall be in accordance with ANSI/ASTM C177-76, ANSI/ASTM C236-66 or ANSI/ASTM C518-76 at the manufacturer’s option.
- Density. The density shall be determined according to installed design density. All tests shall be conducted at the installed design density.
- Resistance to combustion. Loose fill insulation shall comply with the United States General Services Administration insulation standard HH-I-1030B dated August 12, 1980, for flammability and smoldering combustion testing.
- Corrosiveness. Corrosiveness shall be determined according to Test Description Number 2. The steel plate in contact with the insulation shall show no greater corrosion than a steel plate in contact with sterile cotton.
- Resistance to fungi. Resistance to fungi shall be determined according to Method 508 of the March 10, 1975, edition of the Military Standard for Environmental Test Methods known as MIL-STD-810C, except the spore suspensions shall be prepared using distilled water. The core of gypsum wall board shall be used as the control. After the test exposure, the test samples shall show no more fungal growth than the control material when examined at 40 times magnification.
- Odor emission. Odor emission shall be determined according to Test Description Number 1. A detectable odor of objectionable nature observed by two or more of the panel members shall be cause for rejection.
- Identification. Each insulation container shall be marked with the type (pouring or pneumatic), the net weight and the manufacturer’s recommendations for installation including minimum thickness, maximum coverage and installed design density to provide the levels of thermal performance shown. Manufacturer’s installation recommendations shall include precautions according to the California Electrical Code Section 410-66. Products which may be used for pressure fill retrofit wall application shall be marked with the recommended wall density to prevent settling and separately marked with the tested thermal performance for such applications.
(j) Perlite in loose fill form.
- Composition. Expanded perlite loose fill insulation shall be produced by the expanding of natural perlite or by heating.
- Thermal performance. Determination of the thermal performance shall be in accordance with ANSI/ASTM C177-76, ANSI/ASTM C236-66 or ANSI/ASTM C518-76 at the manufacturer’s option.
- Density. Density shall be determined according to installed design density. All tests except the ANSI/ASTM E84-79 test shall be conducted at the installed design density.
- **Resistance to combustion.
CRSC § 12-3 High relevance — show source text
SECTION 12-3-9—ENDURANCE TEST
12-3-9.1 A sample of the security bar releasing system shall function as intended during 250 cycles of operation without failure or excessive wear of the parts, including serving or fraying of individual cable wires. Following the cycling, the system shall be subjected to the Operation Test.
12-3-9.2 The system shall be operated and reset as described in the manufacturer's operating instructions. As part of the cycling, it is only necessary to unlatch, disengage and reset the system, and not open the security bars to the full open position. The cycling rate shall not exceed 30 cycles per minute.
SECTION 12-3-10—ENVIRONMENTAL EXPOSURE TEST
12-3-10.1 After each of the following exposures, test assemblies shall be subjected to the Manual Actuation Test. The test shall be performed while the test assemblies are in the test chambers, or immediately after their removal from the test chamber. Opening forces after these conditionings shall not exceed the values shown in Section 12-3-8.2 or 12-3-8.3. A single sample shall be subjected to each exposure. The same sample, or different sample, shall be allowed to be used for each exposure condition.
12-3-10.2 Elevated ambient. Samples shall be conditioned in a 120°F (49°C) environment for 24 hours.
12-3-10.3 Low ambient. Samples shall be conditioned in a 32°F (0°C) environment for 24 hours.
12-3-10.4 Humidity test. Samples shall be conditioned for 24 hours in moist air having a relative humidity of 85 +/– 5 percent at a temperature of 90°F +/– 5°F (32 +/– 2°C).
SECTION 12-3-11—ABUSE TEST
12-3-11.1 A sample shall comply with the Manual Actuation Test requirements in Sections 12-3-8.2 and 12-3-8.3 after being subjected to the simulated abuse provided in Section 12-3-11.2.
12-3-11.2 The sample shall be subject to six impacts of 5 feet-pounds (6.8 N · m) each applied with a 2-inch diameter (51 mm) steel ball on portions of the release system that are most likely to adversely affect the operation of the system.
MARKINGS AND INSTRUCTIONS
SECTION 12-3-12—MARKINGS
12-3-12.1 Security bars and the latching mechanism shall be permanently marked with the company name, model number and date of manufacture. When a manufacturer produces assemblies at more than one factory, each such assembly shall have a distinctive marking to identify it as the product of a particular factory.
12-3-12.2 Symbols or diagrams shall be marked on the manual actuator to identify how to manually release the security bars. The diagram or symbols shall be readily visible to occupants when the assembly is mounted as intended.
12-3-12.3 Security bars and the latching mechanism shall be marked with the name or logo of the testing agency certifying to compliance of the products with this standard, and identification of the standard as SFM SB-2000.
12-3-12.4 Adhesive-backed labels used to provide required markings shall be suitable for the application and shall comply with UL Standard 969, 1995 Edition.
CRSC § 5.3. High relevance — show source text
2025 CALIFORNIA REFERENCED STANDARDS CODE 43
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
5.3. Continued combustion. If penetration does not occur, continue observation for an additional 30 minutes or until all combustion has ceased.
Note: An infrared thermometer has been found to be useful to detect the increase of temperature on the back side of the eaves and as an aid to identify the areas of potential combustion. 6. Observations. Note the time, location and nature of flame penetration.
12-7A-3.9 Report. The report shall include a description of the eaves material, details of the construction of the eaves, moisture content of the framing and wood-based soffit elements as applicable, and point of flame penetration. Provide details on the time and reasons for early termination of the test.
12-7A-3.10 Conditions of Acceptance. Should one of the three replicates fail to meet the Conditions of Acceptance, three additional tests may be run. All of the additional tests must meet the Conditions of Acceptance.
- Absence of flame penetration of the eaves or horizontal projection assembly at any time.
- Absence of structural failure of the eaves or horizontal projection subassembly at any time.
- Absence of sustained combustion of any kind at the conclusion of the 40-minute test.
FIGURE 1 — EAVES TEST ASSEMBLY
44 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
DECKING
SFM STANDARD 12-7A-4
12-7A-4.1 Application. The minimum design, construction and performance standards set forth herein for unloaded decks are those deemed necessary to establish conformance to the provisions of these regulations. Materials and assemblies that meet the performance criteria of this standard are acceptable for use as defined in California Building Standards Code.
12-7A-4.2 Scope. This standard evaluates the performance of decks (or other horizontal ancillary structures in close proximity to primary structures) when exposed to direct flames and brands. The under-deck flame exposure test is intended to determine the heat release rate (HRR) and degradation modes of deck or other horizontal boards when exposed to a burner flame simulating combustibles beneath a deck. The burning brand exposure test is intended to determine the degradation modes of deck or other horizontal boards when exposed to a burning brand on the upper surface.
12-7A-4.3 Referenced document.
ASTM D4444, Test Methods for Use and Calibration of Hand-Held Moisture Meters.
ASTM E108, Test Methods for Fire Tests of Roof Coverings.
California Building Code, Chapter 7A.
UL 790, Standard Test Methods for Fire Tests of Roof Coverings.
12-7A-4.4 Definitions.
- Deck boards. Horizontal members that constitute the exposed surface of the ancillary structure.
- Deck surface area. The test specimen area defined by the overall specimen length and width after assembly.
- Heat release rate. The net rate of energy release as measured by oxygen depletion calorimetry.
**12-7A-4.5 Test assembly.
California Referenced Standards Code High relevance — show source text
|204
|420
|629
|1210
|1930
|3410
|6960
| |1200
|50
|104
|195
|400
|600
|1160
|1840
|3260
|6640
| |1300
|47
|99
|187
|384
|575
|1110
|1760
|3120
|6360
| |1400
|46
|95
|179
|368
|552
|1060
|1690
|3000
|6110
| |1500
|44
|92
|173
|355
|532
|1020
|1630
|2890
|5890
| |1600
|42
|89
|167
|343
|514
|989
|1580
|2790
|5680
| |1700
|41
|86
|162
|332
|497
|957
|1530
|2700
|5500
| |1800
|40
|83
|157
|322
|482
|928
|1480
|2610
|5330
| |1900
|39
|81
|152
|312
|468
|901
|1440
|2540
|5180
| |2000|38|79|148|304|455|877|1400|2470|5040|California Referenced Standards Code High relevance — show source text
100
| |600
|72
|151
|284
|583
|873
|1680
|2680
|4740
|9660
| |650
|69
|144
|272
|558
|836
|1610
|2570
|4540
|9250
| |700
|66
|139
|261
|536
|803
|1550
|2470
|4360
|8890
| |750
|64
|134
|252
|516
|774
|1490
|2380
|4200
|8560
| |800
|62
|129
|243
|499
|747
|1440
|2290
|4050
|8270
| |850
|60
|125
|235
|483
|723
|1390
|2220
|3920
|8000
| |900
|58
|121
|228
|468
|701
|1350
|2150
|3800
|7760
| |950
|56
|118
|221
|454
|681
|1310
|2090
|3690
|7540
| |1000
|55
|114
|215
|442
|662
|1280
|2030
|3590
|7330
| |1100
|52
|109CRSC § 39966-39973. High relevance — show source text
- Resistance to combustion. Surface-burning characteristics shall be determined according to ANSI/ASTM E84-79, and shall not exceed the following values:
Flame spread. . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Smoke developed. . . . . . . . . . . . . . . . . . . . . . . 50 (d) Cellulose fiber in loose fill form.
- Composition. The basic material shall consist of virgin or recycled wood-based cellulosic fiber and may be made from related paper or paperboard stock, excluding contaminated materials and extraneous foreign materials such as metals and glass which
2025 CALIFORNIA REFERENCED STANDARDS CODE 91
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
STANDARDS FOR INSULATING MATERIAL
may reasonably be expected to be retained in the finished product. Suitable chemicals may be introduced to improve flame resistance, processing and handling characteristics. The particles shall not be so fine as to create a dust hazard, and the added chemicals shall not create a health hazard. The materials used must be capable of proper adhesion to the additive chemicals. 2. Thermal performance. Determination of the thermal performance shall be in accordance with ANSI/ASTM C177-76, ANSI/ASTM C236-66 or ANSI/ASTM C518-76 at the manufacturer’s option. 3. Density. The density shall be determined according to the United States General Services Administration insulation standard HH-I-515D dated June 15, 1978, or as amended October 11, 1979, at the manufacturer’s option. Cellulose insulation made from newsprint may use a 13 percent settling percentage along with the drop box procedure in place of the humidity cycling procedure described in HH-I-515D dated June 15, 1978. All other tests for loose fill cellulose fiber insulation prescribed by this section shall be conducted at the settled density as determined herein. 4. Resistance to combustion. Flammability characteristics shall comply with the standard for flammability and smoldering combustion in 44 Fed. Reg. pages 39966-39973. 5. Resistance to fungi. Resistance to fungi shall be determined according to Method 508 of the March 10, 1975, edition of the Military Standard for Environmental Test Methods known as MIL-STD-810C, except the spore suspensions shall be prepared using distilled water. The core of gypsum wall board shall be used as the control. After the test exposure, the test samples shall show no more fungal growth than the control material when examined at 40 times magnification. 6. Corrosiveness. The product shall comply with the standard for corrosiveness set forth in 44 Fed. Reg. pages 39966-39973. 7. Odor emission. Odor emission shall be determined according to Test Description Number 3. A detectable odor of objectionable nature observed by two or more of the panel members shall be cause for rejection. 8. Identification. Each insulation container shall be marked with the type (pouring or pneumatic), net weight and the manufacturer’s recommendations for installation including minimum thickness, maximum coverage and settled density to provide the levels of thermal performance shown. Manufacturer’s installation recommendations shall include precautions according to the California Electrical Code Section 410-66.
California Referenced Standards Code High relevance — show source text
|1280
|2030
|3590
|7330
| |550
|52
|109
|204
|420
|629
|1210
|1930
|3410
|6960
| |600
|50
|104
|195
|400
|600
|1160
|1840
|3260
|6640
| |650
|47
|99
|187
|384
|575
|1110
|1760
|3120
|6360
| |700
|46
|95
|179
|368
|552
|1060
|1690
|3000
|6110
| |750
|44
|92
|173
|355
|532
|1020
|1630
|2890
|5890
| |800
|42
|89
|167
|343
|514
|989
|1580
|2790
|5680
| |850
|41
|86
|162
|332
|497
|957
|1530
|2700
|5500
| |900
|40
|83
|157
|322
|482
|928
|1480
|2610
|5330
| |950
|39
|81
|152
|312
|468
|901
|1440
|2540
|5180
| |1000<bCRSC § 12-10 High relevance — show source text
2025 CALIFORNIA REFERENCED STANDARDS CODE 79
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EXITS
number or letter designation identifying the listed product shall be legibly marked on the latch or case. Such identification may be an approved marking or label on the case.
FIGURE 12-10-2.1 — STATIC LOADING FIXTURE
80 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EXITS
FIGURE 12-10-2-2—ENDURANCE LIFE TESTING APPARATUS
2025 CALIFORNIA REFERENCED STANDARDS CODE 81
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
82 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EMERGENCY EXIT AND PANIC HARDWARE
STANDARD 12-10-3
STATE FIRE MARSHAL
SCOPE
Sec. 12-10-300.
(a) Exit door hardware. These requirements and methods of test apply to releasing devices actuated by a crossbar for outwardopening doors intended for use on exit doors.
(b) Fire-exit hardware. Releasing devices intended for use on doors bearing a fire-retardant classification shall also conform to the construction standards and performance tests specified in Fire Door Assembly Tests, SFM 12-7-4, Section 12-7-400.
(c) Listing by approved listing agency. Listing by an approved listing agency shall not be construed as necessarily indicating compliance in all respects with the requirements of these Construction Standards and Performance Tests for Emergency Exit and Panic Hardware. The test report of the listing agency may be filed for review and after evaluation, if it is found to provide evidence of conformance, the releasing device assembly may be recognized for approval and listing.
INSTRUCTIONS
Sec. 12-10-301. Approved installation instructions shall be provided by the manufacturer. Instructions shall be illustrated and shall include directions and information adequate for obtaining proper and safe installation of the equipment.
DESIGN
Sec. 12-10-302.
(a) Releasing pressure. Exit panic hardware mechanisms shall be designed to release the door latch or latches when pressure not to exceed 15 pounds is applied at any point along the cross-bar perpendicular to the door in the direction of exit travel. The cross-bar shall extend across not less than one-half the width of the door.
(b) Locking device. A locking device employed as part of the mechanism shall not prevent release of the door latch or latches when pressure of not to exceed 15 pounds is applied to the cross-bar in the direction of exit travel.
(c) Dead locking bolt. A dead locking bolt shall not be provided as a part of the mechanism unless it is released and retracted, and does not prevent release of the door latch or latches, or release of the door to swing outward when pressure not to exceed 15 pounds is applied to the cross-bar in the direction of exit travel.
(d) Cross bar. The ends of the cross-bar shall be curved, guarded or otherwise designed to prevent catching on the clothing of persons during egress.
CRSC § 25.4 High relevance — show source text
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
- Failure mode—collapse.
- Failed on furnace removal.
TABLE 2.1.11
HEXAGONAL REINFORCED CONCRETE COLUMNS
MINIMUM DIMENSION—20″ TO LESS THAN 22″Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 ITEM
CODEMINIMUM
DIMENSIONCONSTRUCTION DETAILS PERFORMANCE PERFORMANCE REFERENCE NUMBER REFERENCE NUMBER REFERENCE NUMBER NOTES REC.
HOURSITEM
CODEMINIMUM
DIMENSIONCONSTRUCTION DETAILS LOAD TIME PRE- BMS-92 BMS-92 POST-BMS-92 POST-BMS-92 POST-BMS-92 C-20-HRC-1 20″ 20″ hexagonal columns; gravel concrete
(6080 psi); reinforcement: vertical,3/4″
rebars; horizontal,5/16″ helical winding on
13/4″ pitch; cover:1/2″.211
tons2 hrs 7 1 2 C-20-HRC-2 20″ 20″ hexagonal columns; gravel concrete
(5080 psi); reinforcement: vertical,3/4″
rebars; horizontal,5/16″ wire on 13/4″ pitch;
cover:1/2″.184
tons2 hrs
15 min7 2–4 21/4 For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 ton = 8.896 kN.
Notes:
Column collapsed on furnace removal.
Passed 2 [1] / 4 -hour fire test.
Passed hose stream test.
Withstood reload after 48 hours.
TABLE 2.2
ROUND CAST IRON COLUMNSCol2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 ITEM
CODEMINIMUM
DIMENSIONCONSTRUCTION DETAILS PERFORMANCE PERFORMANCE REFERENCE NUMBER REFERENCE NUMBER REFERENCE NUMBER NOTES REC.
HOURSITEM
CODEMINIMUM
DIMENSIONCONSTRUCTION DETAILS LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92 POST-BMS-92 POST-BMS-92 C-7-CI-1 7″ O.D. Column: 0.6″ minimum metal thickness;
unprotected.CRSC § 12-7 Medium relevance — show source text
(e) Furnace pressure. The pressure in the furnace chamber during the fire test shall be maintained as nearly equal to atmospheric pressure as possible. Horizontal furnaces may be operated at a slight negative pressure sufficient to reduce haze permitting visual observation. Furnace stacks shall be equipped with dampers to facilitate maintenance of furnace pressure.
CORRELATION
Sec. 12-7-305. Tests of specific assemblies of materials shall be conducted for correlation (or correlation factor) of furnace exposure by comparison with tests of identical assemblies and materials conducted in furnaces of “Approved Listing Agencies” which furnaces are deemed as conforming to the design and operating requirements of this standard.
Correlation tests of wall furnaces shall include tests of two assemblies, one combustible and one noncombustible.
Correlation tests of horizontal furnaces dependent on intended test specimens shall include at least one test for each type of assembly such as combustible ceiling-floor assembly, noncombustible assembly having a high thermal capacity floor for heat dissipation, noncombustible assembly having an insulating concrete floor or other type of design.
Comparison of test results shall provide evidence of equivalent exposure based on transmitted temperatures on the unexposed side, on structural framing members, on the underside of floor or roof decks, and in the plenum space.
28 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FIRE-RESISTIVE STANDARDS
2025 CALIFORNIA REFERENCED STANDARDS CODE 29
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
30 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-7-4 FIRE-RESISTIVE STANDARDS
FIRE DOOR ASSEMBLY TESTS
STANDARD 12-7-4
STATE FIRE MARSHAL
SCOPE
Sec. 12-7-400.
(a) Application. These methods of fire tests are applicable to door assemblies of various materials and types of construction for use in wall openings to retard the passage of fire (flame, heat and smoke).
(b) Performance. Tests made in conformity with these test methods will register performance during the test exposure, but such tests shall not be construed as determining suitability for use after exposure to fire.
(c) Suitability of assemblies. It is the intent that tests made in conformity with these test methods will develop data to enable enforcing agencies to determine the suitability of door assemblies for use in locations where fire resistance of a specified duration is required.
FIRE TESTING FURNACES AND CONTROL
Sec. 12-7-401.
(a) Furnaces. Fire testing furnaces and their control shall conform to SFM 12-7-3, Fire Testing Furnaces, Section 12-7-301 (a), Vertical Large-scale Wall Furnaces.
Frequently asked questions
What is an "environmental exposure" test under the CRSC?
Environmental exposure tests condition a sample in defined climates (for example, elevated ambient, low ambient and high‑humidity cycles) and then measure performance (such as opening forces or actuation) to confirm the product functions after realistic exposures; see Sec. 12‑3‑10 § for the required conditioning and subsequent manual‑actuation checks .
Where are marking and instruction requirements found, and what must they include?
Marking and instruction requirements are in Secs. 12‑3‑12–12‑3‑13 §; they require permanent identification (manufacturer, model, date), visible release/operation symbols or diagrams, testing‑agency identification and an illustrated installation/operation manual with maintenance and compatibility information .
Do CRSC performance tests include wildfire and large‑scale fire exposures?
Yes — the CRSC includes SFM standards for wildfire exposures and large‑scale fire tests (for example, the 12‑7A series for decking, eaves and window assemblies and the 12‑7 fire‑resistive standards); those standards specify burner intensities, durations, heat‑release criteria and report requirements used to determine acceptance .
More in California Referenced Standards Code
- Administration and scope — CRSC Chapter 12 overview
- Air filter standards (Chapter 12‑71)
- Building and facility access / accessibility standards (Chapters 12‑11A, 12‑11B)
- Engineering regulations — quality and design of construction materials (12‑16 series)
- Exits and means of egress (Chapters 12‑10 series)
- Protective signaling systems and detectors (Chapters 12‑72‑1, ‑2, ‑3)
- Radiation shielding standards (Chapter 12‑31C)
- Referenced standards index / cross‑reference table (Part 12 listing of referenced standards)
- Releasing systems for security bars (egress-release standards)
- Standards for insulating materials (Chapter 12‑13)
Ask about the CRSC
Get cited, plain-English answers on the California Referenced Standards Code for your project — any code section, any scenario.
Start Free Trial