CPC · California Plumbing Code

General requirements & materials for storm drainage

Chapter 11 of the California Plumbing Code establishes the scope, approved materials, sizing, controlled‑flow and testing requirements for storm drainage systems.

Last reviewed: July 6, 2026

Overview

Chapter 11 of the California Plumbing Code (CPC) sets the scope and baseline rules for storm‑water drainage systems — what must be drained, where it may be discharged, and the required separation from sanitary systems (see §1101.1–§1101.3) . This chapter is the starting point for designers and installers to ensure drains, leaders, roof outlets, subsoil drains and related appurtenances meet the Authority Having Jurisdiction’s expectations.

Material and installation requirements describe acceptable piping and fittings for conductors, underground drains and subsoil drains, plus limits on plastic use in specific occupancies (see §1101.4 and Table 1101.4.6) . Roof drains and strainers have their own materials and flashing rules in §1102.1–§1102.3, while sizing, controlled‑flow rules, engineered (including siphonic) systems, and testing requirements are addressed in §§1103–1107, with supporting tables and appendices for sizing guidance .

In this section

Code references

Grounded in the retrieved California Plumbing Code — click a citation to read the verbatim passage:

  • CPC § 4.2.1 High relevance — show source text

    4|X|||X|X|||||X||X|X|X|X|||||||||| |1101.4.2.1||||X||||||||||||||||||||| |1101.4.2.2||||||||||X||X|X|X|X|||||||||| |1101.6_ Exception_||||X|X||||||||||||||||||||

    This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.

    2025 CALIFORNIA PLUMBING CODE 203

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    204 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CHAPTER 11

    STORM DRAINAGE

    1101.0 General.

    1101.1 Applicability. This chapter shall govern the materials, design, and installation of storm water drainage systems. 1101.2 Where Required. Roofs, paved areas, yards, courts, courtyards, vent shafts, light wells, or similar areas having rainwater, shall be drained into a separate storm sewer system, or into a combined sewer system where a separate storm sewer system is not available, or to some other place of disposal satisfactory to the Authority Having Jurisdiction. In the case of one- and two-family dwellings, storm water shall be permitted to be discharged on flat areas, such as streets or lawns, so long as the storm water shall flow away from the building and away from adjoining property, and shall not create a nuisance. 1101.3 Storm Water Drainage to Sanitary Sewer Pro- hibited. Storm water shall not be drained into sewers intended for sanitary drainage. 1101.4 Material Uses. Pipe, tube, and fittings conveying rainwater shall be of such materials and design as to perform their intended function to the satisfaction of the Authority Having Jurisdiction. Conductors within a vent or shaft shall be of cast-iron, galvanized steel, wrought iron, copper, copper alloy, lead, Schedule 40 ABS DWV, Schedule 40 PVC DWV, stainless steel 304 or 316L [stainless steel 304 pipe and fittings shall not be installed underground and shall be kept not less than 6 inches (152 mm) aboveground], or other approved materials, and changes in direction shall be in accordance with the requirements of Section 706.0. ABS and PVC DWV piping installations shall be installed in accordance with applicable standards referenced in Chapter 17 and the firestop protection requirements in the California Building Code . Except for individual single-family dwelling units, materials exposed within ducts or plenums shall have a flame-spread index of not more than 25 and a smoke-developed index of not more than 50, where tested in accordance with ASTM E84 or UL 723. Plastic piping installed in plenums shall be tested in accordance with all requirements of ASTM E84 or UL 723. Mounting methods, supports and sample sizes of materials for testing that are not specified in ASTM E84 or UL 723 shall be prohibited.

  • CPC § 1101.16 High relevance — show source text

    1101.16 Leaders, Conductors, and

    Connections . . . . . . . . . . . . . . . . .207

    1102.0 Roof Drains . . . . . . . . . . . . . . . . . .207

    1102.1 Applications . . . . . . . . . . . . . . . . .207

    1102.2 Dome Strainers Required . . . . . . .207

    1102.3 Roof Drain Flashings . . . . . . . . . .207

    1103.0 Size of Leaders, Conductors,

    and Storm Drains . . . . . . . . . . . . .207

    1103.1 Vertical Conductors and

    Leaders . . . . . . . . . . . . . . . . . . . . .207

    1103.2 Size of Horizontal Storm

    Drains and Sewers . . . . . . . . . . . .207

    1103.3 Size of Roof Gutters . . . . . . . . . . .207

    1103.4 Side Walls Draining onto a Roof . . . . . . . . . . . . . . . . . .207

    Table 1103.1 Sizing Roof Drains, Leaders, and Vertical Rainwater Piping . . .208

    1104.0 Values for Continuous Flow . . . . .208

    1104.1 General . . . . . . . . . . . . . . . . . . . . .208

    1105.0 Controlled-Flow Roof

    Drainage . . . . . . . . . . . . . . . . . . . .208

    1105.1 Application . . . . . . . . . . . . . . . . . .208

    Table 1105.1(1) Controlled-Flow Maximum Roof Water Depth . . . . . . . . . . . . .209

    Table 1105.1(2) Distance of Scupper Bottoms Above Roof . . . . . . . . . . . . . . . . . .209

    xxxviii 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    TABLE OF CONTENTS

    1105.2 Setback Roofs . . . . . . . . . . . . . . .209

    1106.0 Engineered Storm Drainage System . . . . . . . . . . . . . . . . . . . . .209

    1106.1 General . . . . . . . . . . . . . . . . . . . . .209

    1106.2 Siphonic Roof Drainage Systems . . . . . . . . . . . . . . . . . . . .209

    1106.3 Siphonic Roof Drains . . . . . . . . . .209

    1107.0 Testing . . . . . . . . . . . . . . . . . . . . .209

    1107.1 Testing Required . . . . . . . . . . . . .209

    1107.2 Methods of Testing Storm Drainage Systems . . . . . . . . . . . .209

    Table 1103.2 Sizing of Horizontal Rainwater Piping . . . . . . . . . . . . .210

    Table 1103.3 Size of Gutters . . . . . . . . . . . . . . .211

  • CPC § 1103.1. High relevance — show source text

    (9) Scupper openings shall be not less than 4 inches (102 mm) high and have a width equal to the circumference of

    208 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    STORM DRAINAGE

    the roof drain required for the area served, sized in accordance with Table 1103.1.

    (10)Flashings shall extend above the top of the scuppers.

    (11)At a wall or parapet, 45 degree (0.79 rad) cants shall be installed.

    (12)Separate storm and sanitary drainage systems shall be provided within the building.

    (13)Calculations for the roof drainage system shall be submitted along with the plans to the Authority Having Jurisdiction for approval.

    TABLE 1105.1(1) CONTROLLED-FLOW MAXIMUM ROOF WATER DEPTH

    ROOF RISE*
    (inches)
    MAXIMUM WATER DEPTH AT
    DRAIN
    (inches)

    Flat
    3

    2
    4

    4
    5

    6
    6

    For SI units: 1 inch = 25.4 mm

    • Vertical measurement from the roof surface at the drain to the highest point of the roof surface served by the drain, ignoring a local depression immediately adjacent to the drain.

    TABLE 1105.1(2) DISTANCE OF SCUPPER BOTTOMS ABOVE ROOF

    ROOF RISE*
    (inches)
    ABOVE ROOF LEVEL
    AT DRAIN
    (inches)

    Flat
    3

    2
    4

    4
    5

    6
    6

    For SI units: 1 inch = 25.4 mm

    • Vertical measurement from the roof surface at the drain to the highest point of the roof surface served by the drain, ignoring a local depression immediately adjacent to the drain.

    1105.2 Setback Roofs. Drains on setback roofs shall be permitted to be connected to the controlled-flow drainage systems provided:

    (1) The setback is designed for storing water, or

    (2) The square footage of the setback drainage area is converted as outlined in Section 1105.0 to gpm, and the storm-water pipe sizes in the controlled-flow system are based on the sum of the loads.

    (3) The branch from each of the roof drains that are not provided with controlled flow shall be sized in accordance

    with Table 1103.1.

    1106.0 Engineered Storm Drainage System. 1106.1 General. The design and sizing of a storm drainage system shall be permitted to be determined by accepted engineering practices. The system shall be designed by a regis

    TABLE 1105.1(1) CONTROLLED-FLOW MAXIMUM ROOF WATER DEPTH

    For SI units: 1 inch = 25.4 mm

    • Vertical measurement from the roof surface at the drain to the highest point of the roof surface served by the drain, ignoring a local depression immediately adjacent to the drain.

    TABLE 1105.1(2) DISTANCE OF SCUPPER BOTTOMS ABOVE ROOF

    For SI units: 1 inch = 25.4 mm

  • CPC § 26-2019 High relevance — show source text

    POLYETHYLENE (PE) PIPE FOR SEWER LATERALS

    IAPMO IS 26-2019 [e4]

    The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

    1 Scope

    1.1 General

    This standard shall govern the trenchless installation of polyethylene (PE) pipe for use in sanitary and storm sewers. The installed pipe shall comply with the requirements of the Uniform Plumbing Code (UPC [TM] ) published by the International Association of Plumbing and Mechanical Officials (IAPMO) as to grade and connections to existing pipe and shall also comply with this standard. This standard specifies requirements for the installation of the trenchless insertion of polyethylene (PE) pipe for use in sanitary and storm sewers. 1.2 Terminology

    In this Standard,

    (a) “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy to comply with the Standard;

    (b) “should” is used to express a recommendation, but not a requirement;

    (c) “may” is used to express an option or something permissible within the scope of the Standard; and

    (d) “can” is used to express a possibility or a capability.

    Notes accompanying sections of the Standard do not specify requirements or alternative requirements; their purpose is to separate explanatory or informative material from the text. Notes to tables and figures are considered part of the table or figure and can be written as requirements.

    2 Reference Publications

    This Standard refers to the following publications, and where such reference is made, it shall be to the current edition of those publications, including all amendments published thereto.

    ASTM International

    ASTM D3261

    Standard Specification for Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing

    ASTM F714

    Standard Specification for Polyethylene (PE) Plastic Pipe (DR-PR) Based on Outside Diameter

    ASTM F894

    Standard Specification for Polyethylene (PE) Large Diameter Profile Wall Sewer and Drain Pipe

    ASTM F1055

    Standard Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene and Crosslinked Polyethylene (PEX) Pipe and Tubing

    ASTM F2620

    Standard Practice for Heat Fusion Joining of Polyethylene Pipe and Fittings

    3 Abbreviations

    The following abbreviations apply in this Standard:

    PE — Polyethylene

    HDPE — High Density Polyethylene

    4 General

    4.1 Product Requirements

    Polyethylene (PE) sewer pipe or tubing and fitting joining methods shall be installed in accordance

    2025 CALIFORNIA PLUMBING CODE 451

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    IS 26

    with the manufacturer’s installation instructions and comply with ASTM F714, ASTM F894 the applicable nationally recognized standard.

    4.2 HDPE Materials

    HDPE Extra High Molecular Weight 3408 SDR 17 Pipe Socket-Type PE Fittings for Outside Diameter Controlled.

  • CPC § 1602.2 High relevance — show source text

    ** The installation, construction, alteration, and repair of rainwater catchments systems intended to supply uses such as water closets, urinals, trap primers for floor drains and floor sinks, irrigation, industrial processes, water features, cooling tower makeup and other uses shall be approved by the Authority Having Jurisdiction. Rainwater catchment systems for collecting precipitation from rooftops shall comply with ARCSA/ASPE/ANSI 63. 1602.2 Plumbing Plan Submission. No permit for a rainwater catchment system shall be issued until complete plumbing plans, with data satisfactory to the Authority Having Jurisdiction, have been submitted and approved. 1602.3 System Changes. No changes or connections shall be made to either the rainwater catchment system or the potable water system within a site containing a rainwater catchment system requiring a permit without approval by the Authority Having Jurisdiction. 1602.4 Connections to Potable or Reclaimed (Recy- cled) Water Systems. Rainwater catchment systems shall have no direct connection to a potable water supply or alternate water source system. Exceptions: (1) Potable water, on-site treated nonpotable gray water, or reclaimed (recycled) water is permitted to be used as makeup water for a rainwater catchment system provided the connection is protected by an air gap in accordance with this code.

    (2) A potable water supply may be connected temporarily for the initial cross-connection test of the rainwater catchment system as required in Section 1605.3.2. 1602.5 Initial Cross-Connection Test. Where a portion of a rainwater catchment system is installed within a building, a cross-connection test is required in accordance with Section 1605.3. Before the building is occupied or the system is activated, the installer shall perform the initial cross-connection test in the presence of the Authority Having Jurisdiction and other authorities having jurisdiction. The test shall be ruled successful by the Authority Having Jurisdiction before final approval is granted. 1602.6 Sizing. The design and size of rainwater drains, gutters, conductors, and leaders shall comply with Chapter 11 of this code.

    328 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    NONPOTABLE RAINWATER CATCHMENT SYSTEMS

    1602.7 Rainwater Catchment System Materials. Rain- 1603.3 Rainwater Catchment Collection Surfaces. water catchment system materials shall comply with Section Rainwater shall be collected from roof surfaces or other 1602.7.1 through Section 1602.7.3 . impervious manmade, aboveground collection surfaces. 1602.7.1 Water Supply and Distribution Materi- 1603.3.1 Other Surfaces. Natural precipitation colals. Rainwater catchment water supply and distribution lected from surface water runoff, vehicular parking surmaterials shall comply with the requirements of this code faces, or manmade surfaces at or below grade shall be in for potable water supply and distribution systems unless accordance with the water quality requirements for onotherwise provided for in this section. site treated nonpotable gray water systems in Section

    1506.0.

    1602.7.2 Rainwater Catchment System Drainage Materials. Materials used in rainwater catchment Exception: Collected rainwater or storm water used

  • CPC § 715.2 High relevance — show source text

    715.2 Joining Methods and Materials. Joining methods and materials shall be as prescribed in this code.

    715.3 Existing Sewers. Where permitted by the Authority Having Jurisdiction, trenchless methods of rehabilitation of existing building sewer and building storm sewers shall be installed in accordance with Section 715.3.1 or Section 715.3.2.

    715.3.1 Sewer Pipe Lining. For trenchless installation of resin-impregnated flexible tubing to line existing building sewers and building storm sewers installation shall be in accordance with ASTM F1216, ASTM F2561, ASTM F2599, or ASTM F3240.

    715.3.2 Sewer Pipe Replacement. For trenchless installation of polyethylene (PE) pipe using the pipe bursting method to replace existing building sewers and building storm sewers materials shall be in accordance with ASTM F714.

    716.0 Markings.

    716.1 General. Pipe, brick, block, prefabricated septic tanks, prefabricated septic tank or seepage pit covers, or other parts or appurtenances incidental to the installation of building sewers or private sewage disposal systems shall be in accordance with the approval requirements of Chapter 3 of this code.

    717.0 Size of Building Sewers. 717.1 General. The minimum size of a building sewer shall be determined on the basis of the total number of fixture units drained by such sewer, in accordance with Table 717.1. No building sewer shall be smaller than the building drain.

    For alternate methods of sizing building sewers, see Appendix C.

    TABLE 717.1

    MAXIMUM/MINIMUM FIXTURE UNIT LOADING

    Col1 ON BUILDING SEWER PIPING* Col3 Col4



    SIZE OF PIPE
    (inches)
    SLOPE
    (inches per foot)
    SLOPE
    (inches per foot)
    SLOPE
    (inches per foot)



    SIZE OF PIPE
    (inches)
    1⁄16 1⁄8 1⁄4


    6 and smaller
    (As specified in Table 703.2/
    No minimum loading)
    (As specified in Table 703.2/
    No minimum loading)
    (As specified in Table 703.2/
    No minimum loading)

    8
    1950/1500 2800/625 3900/275

    10
    3400/1600 4900/675 6800/300

    12
    5600/1700 8000/725 11 200/325

    For SI units: 1 inch = 25 mm, 1 inch per foot = 83.3 mm/m

    • See also Appendix H, Private Sewage Disposal Systems. For alternate methods of sizing drainage piping, see Appendix C.

    717.2 Meat and Poultry Processing Plants. [AGR] The sewer system shall have the capacity to remove all waste from the various processing and cleaning operations and to mini- mize or prevent stoppage and surcharging at the system.

    718.0 Grade, Support, and Protection of Building Sewers.

  • CPC § 1101.4.2.2 High relevance — show source text

    1101.4.2.2 [OSHPD 1, 2, 3, 4 & 5] ABS and PVC installations are not allowed.

    1101.4.3 Leaders. Leaders installed outside shall comply with the applicable standards referenced in Table 701.2 for aboveground drain, waste, and vent pipe; aluminum sheet metal; galvanized steel sheet metal; or copper sheet metal. 1101.4.4 Underground Building Storm Drains. Underground building storm drains shall comply with the applicable standards referenced in Table 701.2 for underground drain, waste, and vent pipe. 1101.4.5 Building Storm Sewers. Building storm sewers shall comply with the applicable standards referenced in Table 701.2 for building sewer pipe. 1101.4.6 Subsoil Drains. Subsoil drains shall be open jointed, perforated, or both and constructed of materials in conformance with Table 1101.4.6.

    TABLE 1101.4.6

    MATERIALS FOR SUBSOIL DRAINPIPE AND FITTINGS

    MATERIAL REFERENCED STANDARD(S)

    PE
    ASTM F667

    PVC
    ASTM D2729
    Vitrified Clay (Extra strength) ASTM C4, ASTM C700

    1101.5 Expansion Joints Required. Expansion joints or sleeves shall be provided where warranted by temperature variations or physical conditions. 1101.6 Subsoil Drains. Subsoil drains shall be provided around the perimeter of buildings having basements, cellars, crawl spaces, or floors below grade. Such subsoil drains shall be permitted to be positioned inside or outside of the footing, shall be of perforated or open-jointed approved drain tile or pipe, not less than 3 inches (80 mm) in diameter, and shall be laid in gravel, slag, crushed rock, approved [3] ⁄ 4 of an inch (19.1 mm) crushed, recycled glass aggregate, or other approved porous material with not less than 4 inches (102 mm) surrounding the pipe. Filter media shall be provided for exterior subsoil piping. Exception: [HCD 1 & HCD 2] Subsoil drains are mandatory only when required by the Authority Having Jurisdiction due to geological conditions.

    TABLE 1101.4.6

    MATERIALS FOR SUBSOIL DRAINPIPE AND FITTINGS

    2025 CALIFORNIA PLUMBING CODE 205

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    STORM DRAINAGE

    1101.6.1 Discharge. Subsoil drains shall be piped to a storm drain, to an approved water course, to the front street curb or gutter, to an alley, or the discharge from the subsoil drains shall be conveyed to the alley by a concrete gutter. Where a continuously flowing spring or groundwater is encountered, subsoil drains shall be piped to a storm drain or an approved water course. 1101.6.2 Sump. Where it is not possible to convey the drainage by gravity, subsoil drains shall discharge to an accessible sump provided with an approved automatic electric pump.

  • CPC § 1105.1 High relevance — show source text

    Table 1105.1(2) Distance of Scupper Bottoms Above Roof . . . . . . . . . . . . . . . . . .209

    xxxviii 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    TABLE OF CONTENTS

    1105.2 Setback Roofs . . . . . . . . . . . . . . .209

    1106.0 Engineered Storm Drainage System . . . . . . . . . . . . . . . . . . . . .209

    1106.1 General . . . . . . . . . . . . . . . . . . . . .209

    1106.2 Siphonic Roof Drainage Systems . . . . . . . . . . . . . . . . . . . .209

    1106.3 Siphonic Roof Drains . . . . . . . . . .209

    1107.0 Testing . . . . . . . . . . . . . . . . . . . . .209

    1107.1 Testing Required . . . . . . . . . . . . .209

    1107.2 Methods of Testing Storm Drainage Systems . . . . . . . . . . . .209

    Table 1103.2 Sizing of Horizontal Rainwater Piping . . . . . . . . . . . . .210

    Table 1103.3 Size of Gutters . . . . . . . . . . . . . . .211

    CHAPTER 12 FUEL GAS PIPING . . . . . . . . . . .213

    1201.0 General . . . . . . . . . . . . . . . . . . . . .215

    1201.1 Applicability . . . . . . . . . . . . . . . . . .215

    1202.0 Coverage of Piping System . . . . .215

    1202.1 General . . . . . . . . . . . . . . . . . . . . .215

    1202.2 Piping System Requirements . . . .215

    1202.3 Applications . . . . . . . . . . . . . . . . .215

    1203.0 Inspection . . . . . . . . . . . . . . . . . . .215

    1203.1 Inspection Notification . . . . . . . . .215

    1203.2 Excavation . . . . . . . . . . . . . . . . . .215

    1203.3 Type of Inspections . . . . . . . . . . .215

    1203.4 Inspection Waived . . . . . . . . . . . .216

    1204.0 Certificate of Inspection . . . . . . . .216

    1204.1 Issuance . . . . . . . . . . . . . . . . . . . .216

    1204.2 Gas Supplier . . . . . . . . . . . . . . . . .216

    1204.3 Unlawful . . . . . . . . . . . . . . . . . . . .216

    1205.0 Authority to Render Gas Service . . . . . . . . . . . . . . . . . . . . .216

    1205.1 Authorized Personnel . . . . . . . . . .216

  • CPC § 31-2022 Medium relevance — show source text

    2025 CALIFORNIA PLUMBING CODE 453

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    454 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    "The information contained in this appendix is not part of this American National Standard (ANS) and has not been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that has not been subjected to public review or a consensus process. In addition, it does not contain requirements necessary for conformance to the standard."

    The following IAPMO Installation Standard is included here for the convenience of the users of the Uniform Plumbing Code. It is not considered as a part of the Uniform Plumbing Code unless formally adopted as such. This Installation Standard is an independent, stand-alone document published by the International Association of Plumbing and Mechanical Officials and is printed herein by the expressed written permission of IAPMO.

    INSTALLATION STANDARD FOR PEX TUBING SYSTEMS

    FOR HOT- AND COLD-WATER DISTRIBUTION

    IAPMO IS 31-2022

    The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

    1 Scope

    1.1 General

    1.1.1 This Standard specifies requirements for the installation of SDR 9 CTS crosslinked polyethylene (PEX) tubing and fittings, including cold-expansion, crimp, press, and mechanical compression fittings, intended for hot- and cold-water distribution systems within buildings.

    1.1.2 This Standards applies to

    (a) SDR 9 CTS PEX tubing complying with ASTM F876 and pressure-rated in accordance with PPI TR-3; and (b) PEX fitting systems complying with (i) ASTM F877, for mechanical compression fittings and metal or plastic insert fittings with stainless steel press sleeves; (ii) ASTM F1807 or ASTM F2159, for metal or plastic insert fittings with copper crimp rings; (iii) ASTM F1960, for cold expansion fittings with PEX reinforced rings; or (iv) ASTM F2080, for cold expansion fittings with metal compression sleeves. 1.2 Terminology

    In this Standard,

    (a) “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy to comply with the Standard; (b) “should” is used to express a recommendation, but not a requirement; (c) “may” is used to express an option or something permissible within the scope of the Standard; and (d) “can” is used to express a possibility or a capability. Notes accompanying sections of the Standard do not specify requirements or alternative requirements; their purpose is to separate explanatory or informa

    tive material from the text. Notes to tables and figures are considered part of the table or figure and can be written as requirements.

    1.3 Units of Measurement

    SI units are the primary units of record in global commerce. In this Standard, the inch/pound units are shown in parentheses. The values stated in each measurement system are equivalent in application, but each unit system is to be used independently. All references to gallons are to U.S. gallons.

    2 Reference Publications

  • CPC § 112.5 Medium relevance — show source text

    x 8’ 6” x 6’ 0”|Incidental|Quick-Release
    Aluminum|043411| |Equipment3|4’ 6” x 8’ 6” x 6’ 0”|Full-Traffic|Quick-Release Steel|041666| |Equipment3|4’ 6” x 8’ 6” x 7’ 0”|Heavy Full-Traffic|Concrete|041441| |UCD Transformer4|4’ 6” x 8’ 6” x 7’ 6”|Incidental|Quick-Release
    Aluminum|040325| |UCD Transformer4|4’ 6” x 8’ 6” x 7’ 6”|Full-Traffic|Quick-Release Steel|041662| |UCD Transformer4|4’ 6” x 8’ 6” x 8’ 6”|Heavy Full-Traffic|Concrete|040324|

    1 Code includes body, extension (as appropriate), frame, and cover assembly. When extra depth is required, order additional extension from Table 12 on Page 19. 2 See Document 051776. 3 600-amp non-lead splices, 600-amp switches, 600-amp separable connectors. 4 112.5 through 500 kVA UCD transformers with 4-hole secondary spades will fit into existing 4’ 6” x 8’ 6” x 6’ 0” enclosures.

    062000 Page 18 of 26 Rev. #25: 03-25-22

    UG-1: Enclosures Greenbook Primary Electric Underground Enclosures

    4’ 6” x 8’ 6” (#7) Enclosure and Extensions

    Notes

    1. Do not break out sump.

    2. Joints must be interchangeable with those shown in Detail B and approved by PG&E electric distribution personnel.

    4-1/4”

    1-1/4” x 1-1/2” Hole Not Required

    Tongue and Groove

    CL

    1-3/8”

    1-3/4”

    3”

    4-1/4”

    Width = 30”

    Length = 54”

    2-1/4”

    1-1/2”

    1/2” ∅ Brass Insert with Rod Attached to Rebar Cage

    Col1 M 4-1/4”
    Flush Pull Iron
    Five Places
    1”∅ Hole for
    Ground Rod Two
    Places (blind)
    14”∅ Sump
    4” Deep Reqd.
    (see Note 8 on
    Page 1)
    6”
    6”
    15”
    1/2”∅ Brass Insert
    with Rod Attached to
    Rebar Cage

    2-1/4”

  • CPC § 1101.4 Medium relevance — show source text

    (Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting Agency BSC BSC-
    CG
    SFM HCD Col6 Col7 DSA Col9 Col10 OSHPD Col12 Col13 Col14 Col15 Col16 Col17 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting Agency BSC BSC-
    CG
    SFM 1 2 1-AC AC ** SS** SS/CC 1 1R 2 3 4 5 6 6 6 6 6 6 6 6 6
    Adopt Entire Chapter X X X
    Adopt Entire Chapter as
    amended (amended
    sections listed below)
    X X X X X X X X
    Adopt only those sections
    that are listed below
    Chapter/Section
    1101.4 X X X X X X X X
    1101.4.2.1 X
    1101.4.2.2 X X X X X
    1101.6_ Exception_ X X

    This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.

    2025 CALIFORNIA PLUMBING CODE 203

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    204 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CHAPTER 11

    STORM DRAINAGE

    1101.0 General.

    1101.1 Applicability. This chapter shall govern the materials, design, and installation of storm water drainage systems. 1101.2 Where Required. Roofs, paved areas, yards, courts, courtyards, vent shafts, light wells, or similar areas having rainwater, shall be drained into a separate storm sewer system, or into a combined sewer system where a separate storm sewer system is not available, or to some other place of disposal satisfactory to the Authority Having Jurisdiction.

  • CPC § 1701.1 Medium relevance — show source text

    Chapter 16 Nonpotable Rainwater Catchment Systems.

    Chapter 16 regulates nonpotable rainwater catchment systems that include irrigation; toilet and urinal flushing with proper treatment; provisions where permits are required; maintenance of alternate water sources; and minimum water quality. This chapter provides guidance on how to optimize rainwater use while ensuring there is a decrease of risk to consumers from poor design, installation, and maintenance. Rainwater harvesting is the process of capturing, channeling, and storing water runoff for later use. Most systems are constructed of three principal components: the catchment area, the collection device, and the conveyance system.

    Chapter 17 Referenced Standards.

    Chapter 17 provides two comprehensive tables with referenced standards. The standards listed in Table 1701.1 are applied as indicated in the applicable reference section(s). A list of additional approved standards, publications, practices, and guides that are not referenced in specific sections appear in Table 1701.2.

    Referenced standards set forth specific details of accepted practices, materials specifications, or test methods in many specialized applications. Standards provide an efficient method of conveying complex information and specifications on the performance requirements for materials, products, systems, application, and installation. The manner and purpose for a standard’s use and, in turn, code compliance, must be definitive in all references to the standard. If the standard is intended to be a requirement for judging code compliance, the code must state its intent for use. The standard should adequately address a defined need and at the same time specify the minimum performance requirements, technical characteristics and methods of testing, and required test results.

    The referenced standards tables are organized in a manner that makes it easy to find specific standards in alphabetical order, and by acronym of the publishing agency of the standard. The tables list the title of the standard, the edition, and any addenda. Contact information for each publishing agency is provided at the end of the chapter.

    Appendix A Recommended Rules for Sizing the Water Supply System.

    Appendix A provides a method of sizing the water supply and distribution system that provides precise calculations to establish the proper pressures and flow to the system’s fixtures. The goal of sizing the system is to deliver an acceptable volume of water to the most hydraulically remote fixture during minimum pressure and maximum flow conditions; provide satisfactory water pressure to the most hydraulically remote fixture during minimum pressure and maximum flow conditions; and to prevent excessive water velocity during maximum flow conditions.

    Appendix B Explanatory Notes on Combination Waste and Vent Systems.

    Appendix B contains general guidelines for the design and installation of combination waste and vent systems. These systems are designed for waste piping and are purposely oversized to serve as both a waste and vent pipe to avoid excessive pneumatic effects at fixture drains.

    Appendix C Alternate Plumbing Systems.

    The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate materials, and equipment that are not specifically covered in other parts of the code. Alternative methods are allowed to be used where approved by the authority having jurisdiction. Approval of alternatives is based on a demonstration showing that the method or material used is at least equivalent in strength, deflection, and capacity to that provided by the prescriptive methods and materials.

    Appendix D Sizing Storm Water Drainage Systems.

    Appendix D provides general guidelines for the sizing of stormwater drainage systems. There are two pieces of information that must always be a given. They are the roof size and the rate of rainfall f

Frequently asked questions

Which CPC section governs storm‑drain materials and basic requirements?

Chapter 11 is the controlling chapter; see §1101.1 for applicability and §1101.4 for material uses and permitted pipe/fitting types .

May storm water be discharged into the sanitary sewer?

No — the CPC prohibits draining storm water into sanitary sewers except where a combined sewer system is used; see §1101.3 for the prohibition and the limited combined‑sewer exception .

What materials are allowed for roof drains and strainers?

Roof drains are required to be constructed of approved metals or plastics (aluminum, cast iron, certain copper alloys, stainless steel, ABS, PVC, polyethylene, etc.) and must have domed strainers; see §1102.1–§1102.2 for the material list and strainer requirement .

More in California Plumbing Code

Ask about the CPC

Get cited, plain-English answers on the California Plumbing Code for your project — any code section, any scenario.

Start Free Trial

Related in the CPC