CPC · California Plumbing Code
System sizing & fixture units
This hub explains how the California Plumbing Code uses fixture units and the key sections/tables (Chapter 6, Chapter 7, Appendices A/C/M) to size water, drainage and vent systems.
Last reviewed: July 6, 2026
Overview
This area of the California Plumbing Code covers how potable‑water and sanitary drainage systems are hydraulically sized using fixture units as the basic demand metric. Water‑supply sizing (Chapter 6) uses water‑supply fixture units (WSFU) and prescriptive tables and procedures (see §610.3–§610.10 and Tables 610.3 and 610.4) to select meter, building‑supply and branch sizes and to account for pressure, length and elevation effects .
Sanitary drainage, venting and trap sizing (Chapter 7 and Appendix C) use drainage fixture units (DFU) and tables that limit the number of fixture units on branches, stacks, building drains and sewers (see §702, §703 and Table 703.2) and provide specific DFU values for individual traps and fixtures (Table 702.1(1)) . The code also recognizes alternate (engineered) methods and worked examples in Appendix A and Appendix C (and Appendix M for alternate water sizing) for projects that need a method beyond the prescriptive tables .
Understanding fixture units and the associated sizing tables matters because correct sizing ensures adequate flow and pressure to fixtures, prevents trap siphonage or clogging, and avoids unnecessary oversizing that can impair system performance; the CPC ties these requirements to the specific sections and tables cited above so designers and reviewers can apply the appropriate rules and exceptions file.
In this section
Code references
Grounded in the retrieved California Plumbing Code — click a citation to read the verbatim passage:
CPC § 422.1 High relevance — show source text
6 Assembly [Public Use (see Table 422.1)]. 7 Reduced fixture unit loading for additional hose bibbs is to be used where sizing total building demand and for pipe sizing where more than one hose bibb is supplied by a segment of water distribution pipe. The fixture branch to each hose bibb shall be sized by 2.5 fixture units.
2025 CALIFORNIA PLUMBING CODE 369
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX A
CHART A 103.1(1)
ESTIMATE CURVES FOR DEMAND LOAD
FIXTURE UNITS
For SI units: 1 gallon per minute = 0.06 L/s
CHART A 103.1(2)
ENLARGED SCALE DEMAND LOAD
FIXTURE UNITS
For SI units: 1 gallon per minute = 0.06 L/s
370 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX A
TABLE A 104.4(1) ALLOWANCE IN EQUIVALENT LENGTH OF PIPE FOR FRICTION LOSS IN VALVES AND THREADED FITTINGS*
EQUIVALENT LENGTH OF PIPE FOR VARIOUS FITTINGS
DIAMETER OF
FITTING
(inches)90° STANDARD
ELBOW
(feet)45° STANDARD
ELBOW
(feet)90° STANDARD
TEE
(feet)COUPLING OR
STRAIGHT RUN
OF TEE
(feet)GATE VALVE
(feet)GLOBE VALVE
(feet)ANGLE VALVE
(feet)3⁄8 1.0 0.6 1.5 0.3 0.2 8 4 1⁄2 2.0 1.2 3.0 0.6 0.4 15 8 3⁄4 2.5 1.5 4.0 0.8 0.5 20 12 1 3.0 1.8 5.0 0.9 0.6 25 15 11⁄4 4.0 2.4 6.0 1.2 0.8 35 18 11⁄2 5.0 3.0 7.0 1.5 1.0 45 22 2 7.0 4.0 10.0 2.0 1.3 55 28 21⁄2 8.0 5.0 12.0 2.5 1.6 65 34 3 10.0 6.0 15.0 3.0 2.0 80 40 4 14.0 8.0 21.0 4.0 2.7 125 55 5 17.0 10.0 25.0 5.0 3.3 140 70 6 20.0 12.0 30.0 6.0 4.0 165 80 CPC § 0.06 High relevance — show source text
INTERMITTENT FLOW ONLY*
GPM FIXTURE UNITS
Up to 71⁄2Equals 1 Fixture Unit
Greater than 71⁄2 to 15Equals 2 Fixture Units
Greater than 15 to 30Equals 4 Fixture Units
Greater than 30 to 50Equals 6 Fixture Units For SI units: 1 gallon per minute = 0.06 L/s
- Discharge capacity exceeding 50 gallons per minute (3.15 L/s) shall be determined by the Authority Having Jurisdiction.
702.3 Continuous Flow. For a continuous flow into a drainage system, such as from a pump, sump ejector, air conditioning equipment, or similar device, 2 fixture units shall be equal to each gallon per minute (gpm) (L/s) of flow.
703.0 Size of Drainage Piping. 703.1 Minimum Size. The minimum sizes of vertical, horizontal, or both drainage piping shall be determined from the total of fixture units connected thereto, and additionally, in the case of vertical drainage pipes, in accordance with their length.
703.2 Maximum Number of Fixture Units. Table 703.2
shows the maximum number of fixture units allowed on a vertical or horizontal drainage pipe, building drain, or building sewer of a given size; the maximum number of fixture units allowed on a branch interval of a given size; and the maximum length (in feet and meters) of a vertical drainage pipe of a given size. 703.3 Sizing per Appendix C. For alternate method of sizing drainage piping, see Appendix C.
704.0 Fixture Connections (Drainage). 704.1 Inlet Fittings. Drainage piping shall be provided with approved inlet fittings for fixture connections, correctly located according to the size and type of fixture proposed to be connected.
704.2 Single Vertical Drainage Pipe. Two fixtures set back-to-back, or side-by-side, within the distance allowed between a trap and its vent, shall be permitted to be served by a single vertical drainage pipe provided that each fixture wastes separately into an approved double-fixture fitting having inlet openings at the same level. 704.3 Commercial Sinks. Pot sinks, scullery sinks, dishwashing sinks, silverware sinks, and other similar fixtures shall be connected directly to the drainage system. A floor drain shall be provided adjacent to the fixture and shall be connected on the sewer side of the sink. No other drainage
168 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
SANITARY DRAINAGE
TABLE 703.2
MAXIMUM UNIT LOADING AND MAXIMUM LENGTH OF DRAINAGE AND VENT PIPING
SIZE OF PIPE (inches) 11⁄4 11⁄2 2 3 4 5 6 8 10 12 Maximum Units
Drainage Piping1
Vertical
Horizontal
1
1
22,CPC § 2.2 High relevance — show source text
For drainage fixture unit values related to lots within special occupancy parks in all parts of the State of Cal-_ ifornia, see California Code of Regulations, Title 25, Division 1, Chapter 2.2, Article 5, Section 2268.
required, and the unit equivalent of fixtures and devices not shown in Table 702.1 shall be based on the size of trap or trap
arm.
Maximum drainage fixture units for a fixture trap and trap arm loadings for sizes up to 4 inches (100 mm) shall be in accordance with Table 702.1(1).
TABLE 702.1(1) MAXIMUM DRAINAGE FIXTURE UNITS FOR A
TRAP AND TRAP ARM*
SIZE OF TRAP AND
TRAP ARM (inches)DRAINAGE FIXTURE UNIT
VALUES (DFU)
11⁄41 unit
11⁄23 units
24 units 3 6 units
48 units For SI Units: 1 inch = 25 mm
*** Exception:** On self-service laundries.
702.2 Intermittent Flow. Drainage fixture units for intermittent flow into the drainage system shall be computed on the rated discharge capacity in gallons per minute (gpm) (L/s) in accordance with Table 702.2.
TABLE 702.1(1) MAXIMUM DRAINAGE FIXTURE UNITS FOR A
TRAP AND TRAP ARM*
For SI Units: 1 inch = 25 mm
*** Exception:** On self-service laundries.
TABLE 702.2
DISCHARGE CAPACITY IN GALLONS PER MINUTE FOR
INTERMITTENT FLOW ONLY*
GPM FIXTURE UNITS
Up to 71⁄2Equals 1 Fixture Unit
Greater than 71⁄2 to 15Equals 2 Fixture Units
Greater than 15 to 30Equals 4 Fixture Units
Greater than 30 to 50Equals 6 Fixture Units For SI units: 1 gallon per minute = 0.06 L/s
- Discharge capacity exceeding 50 gallons per minute (3.15 L/s) shall be determined by the Authority Having Jurisdiction.
702.3 Continuous Flow. For a continuous flow into a drainage system, such as from a pump, sump ejector, air conditioning equipment, or similar device, 2 fixture units shall be equal to each gallon per minute (gpm) (L/s) of flow.
703.0 Size of Drainage Piping. 703.1 Minimum Size. The minimum sizes of vertical, horizontal, or both drainage piping shall be determined from the total of fixture units connected thereto, and additionally, in the case of vertical drainage pipes, in accordance with their length.
703.2 Maximum Number of Fixture Units. Table 703.2
shows the maximum number of fixture units allowed on a vertical or horizontal drainage pipe, building drain, or building sewer of a given size; the maximum number of fixture units allowed on a branch interval of a given size; and the maximum length (in feet and meters) of a vertical drainage pipe of a given size. 703.3 Sizing per Appendix C. For alternate method of sizing drainage piping, see Appendix C.
CPC § 610.3 High relevance — show source text
No water filter, water softener, backflow prevention device, or similar device regulated by this code shall be installed in a potable water supply piping where the installation of such device produces an excessive pressure drop in such water supply piping. In the absence of specific pressure drop information, the diameter of the inlet or outlet of such device or its connecting piping shall be not less than the diameter of such water distribution piping to the fixtures served by the device.
156 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
WATER SUPPLY AND DISTRIBUTION
Such devices shall be of a type approved by the Authority Having Jurisdiction and shall be tested for flow rating and pressure loss by an approved laboratory or recognized testing agency to standards consistent with the intent of this chapter. 610.3 Quantity of Water. The quantity of water required to be supplied to every plumbing fixture shall be represented by fixture units, as shown in Table 610.3. Equivalent fixture values shown in Table 610.3 include both hot and cold water demand.
610.4 Sizing Water Supply and Distribution Systems. Systems within the range of Table 610.4 shall be permitted to be sized from that table or by the method in accordance with Section 610.5.
Listed parallel water distribution systems shall be installed in accordance with their listing, but at no time shall a portion of the system exceed the maximum velocities allowed by the code. 610.5 Sizing per Appendices A, C, and M . Except as provided in Section 610.4, the size of each water piping system shall be determined in accordance with the procedure set forth in Appendix A. For alternative methods of sizing water supply systems, see Appendix C or Appendix M . 610.6 Friction and Pressure Loss. Except where the type of pipe used and the water characteristics are such that no decrease in capacity due to the length of service (age of system) is expected, friction-loss data shall be obtained from the “Fairly Rough” or “Rough” charts in Appendix A of this code. Friction or pressure losses in a water meter, valve, and fittings shall be obtained from the same sources. Pressure losses through water-treating equipment, backflow prevention devices, or other flow-restricting devices shall be computed in accordance with Section 610.2. 610.7 Conditions for Using Table 610.4. On a proposed water piping installation sized using Table 610.4, the following conditions shall be determined:
(1) Total number of fixture units as determined from Table 610.3, Equivalent Fixture Units, for the fixtures to be installed.
(2) Developed length of supply pipe from meter to the most remote outlet.
(3) Difference in elevation between the meter or other source of supply and the highest fixture or outlet.
(4) Pressure in the street main or another source of supply at the locality where the installation is to be made.
(5) In localities where there is a fluctuation of pressure in the main throughout the day, the water piping system shall be designed on the basis of the minimum pressure available. 610.8 Size of Meter and Building Supply Pipe Using Table 610.4. The size of the meter and the building supply pipe shall be determined as follows:
(1) Determine the available pressure at the water meter or other source of supply.
CPC § 609.4 High relevance — show source text
609.4 Testing . . . . . . . . . . . . . . . . . . . . .155
609.5 Unions . . . . . . . . . . . . . . . . . . . . .155
609.6 Location . . . . . . . . . . . . . . . . . . . .155
609.7 Abutting Lot . . . . . . . . . . . . . . . . .155
609.8 Pumps . . . . . . . . . . . . . . . . . . . . .155
609.9 Low-Pressure Cutoff Required on Booster Pumps for Water Distribution Systems . . . . . . . . . . .156
2025 CALIFORNIA PLUMBING CODE xxxiii
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
TABLE OF CONTENTS
609.10 Disinfection of Potable Water System . . . . . . . . . . . . . . . . . . . . .156
609.11 Water Hammer . . . . . . . . . . . . . . .156
609.12 Pipe Insulation . . . . . . . . . . . . . . .156
610.0 Size of Potable Water Piping . . . .156
610.1 Size . . . . . . . . . . . . . . . . . . . . . . . .156
610.2 Pressure Loss . . . . . . . . . . . . . . . .156
610.3 Quantity of Water . . . . . . . . . . . . .157
610.4 Sizing Water Supply and Distribution Systems . . . . . . . . . . .157
610.5 Sizing per Appendices A, C, and M . . . . . . . . . . . . . . . . .157
610.6 Friction and Pressure Loss . . . . . .157
610.7 Conditions for Using Table 610.4 . . . . . . . . . . . . . . . . . .157
610.8 Size of Meter and Building Supply Pipe Using Table 610.4 . .157
610.9 Size of Branches . . . . . . . . . . . . .157
610.10 Sizing for Flushometer Valves . . .157
Table 610.10 Flushometer Fixture Units for Water Sizing Using Table 610.3 . . . . . . . . . . . . . . . . . .157
Table 610.3 Water Supply Fixture Units (WSFU) and Minimum Fixture Branch Pipe Sizes . . . . . . . . . . . .158
Table 610.4 Fixture Unit Table for
Determining Water Pipe and Meter Sizes . . . . . . . . . . . . . .159
610.11 Sizing Systems for Flushometer Tanks . . . . . . . . . . . .160
610.12 Sizing for Velocity . . . . . . . . . . . . .160
610.13 Exceptions . . . . . . . . . . . . . . . . . .160
611.0 Drinking Water Treatment Units . . . . . . . . . . . . . . . . . . . . . . .160
611.1 Application . . . . . . . . . . . . . . . . . .160
CPC § 3.0 High relevance — show source text
0 GPF Flushometer Valve|3⁄4|3.0|4.0|5.0| |Urinal, greater than 1.0 GPF Flushometer Valve|3⁄4|4.0|5.0|6.0| |Urinal, flush tank|1⁄2|2.0|2.0|3.0| |Wash Fountain, circular spray|3⁄4|–|4.0|–| |Water Closet, 1.6 GPF Gravity Tank|1⁄2|2.5|2.5|3.5| |Water Closet, 1.6 GPF Flushometer Tank|1⁄2|2.5|2.5|3.5| |Water Closet, 1.6 GPF Flushometer Valve|1|5.0|5.0|8.0| |Water Closet, greater than 1.6 GPF Gravity Tank|1⁄2|3.0|5.5|7.0| |Water Closet, greater than 1.6 GPF Flushometer Valve|1|7.0|8.0|10.0|
For SI units: 1 inch = 25 mm
Notes: 1 Size of the cold branch pipe, or both the hot and cold branch pipes. 2 Appliances, appurtenances, or fixtures not included in this table shall be permitted to be sized by reference to fixtures having a similar flow rate and frequency of use. 3 The listed fixture unit values represent their total load on the cold water building supply. The separate cold water and hot water fixture unit value for fixtures having both cold and hot water connections shall be permitted to be three-quarters of the listed total value of the fixture. 4 The listed minimum supply branch pipe sizes for individual fixtures are the nominal (I.D.) pipe size. 5 For fixtures or supply connections likely to impose continuous flow demands, determine the required flow in gallons per minute (gpm) (L/s) and add it separately to the demand in gpm (L/s) for the distribution system or portions thereof. 6 Assembly [Public Use (see Table 422.1)]. 7 Reduced fixture unit loading for additional hose bibbs is to be used where sizing total building demand and for pipe sizing where more than one hose bibb is supplied by a segment of water distribution pipe. The fixture branch to each hose bibb shall be sized by 2.5 fixture units.
2025 CALIFORNIA PLUMBING CODE 369
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX A
CHART A 103.1(1)
ESTIMATE CURVES FOR DEMAND LOAD
FIXTURE UNITS
For SI units: 1 gallon per minute = 0.06 L/s
CHART A 103.1(2)
ENLARGED SCALE DEMAND LOAD
FIXTURE UNITS
For SI units: 1 gallon per minute = 0.06 L/s
370 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX A
TABLE A 104.4(1) ALLOWANCE IN EQUIVALENT LENGTH OF PIPE FOR FRICTION LOSS IN VALVES AND THREADED FITTINGS*
EQUIVALENT LENGTH OF PIPE FOR VARIOUS FITTINGS
CPC § 1.6 Medium relevance — show source text
PLUMBING APPLIANCES, APPURTENANCES, OR FIXTURES MINIMUM SIZE TRAP
AND TRAP ARM7
(inches)PRIVATE PUBLIC ASSEMBLY8 Water Closet, greater than 1.6 GPF Gravity Tank6 3 4.0 6.0 8.0 Water Closet, greater than 1.6 GPF Flushometer Valve6 3 4.0 6.0 8.0 For SI units: 1 inch = 25 mm
Notes: 1 Indirect waste receptors shall be sized based on the total drainage capacity of the fixtures that drain thereinto, in accordance with Table 702.2. 2 Provide a 2 inch (50 mm) minimum drain. 3 For refrigerators, coffee urns, water stations, and similar low demands. 4 For commercial sinks, dishwashers, and similar moderate or heavy demands. 5 Buildings having a clothes-washing area with clothes washers in a battery of three or more clothes washers shall be rated at 6 fixture units each for purposes of sizing common horizontal and vertical drainage piping. 6 Water closets shall be computed as 6 fixture units where determining septic tank sizes based on Appendix H of this code. 7 Trap sizes shall not be increased to the point where the fixture discharge is capable of being inadequate to maintain their self-scouring properties. 8 Assembly [Public Use (see Table 422.1)]. 9 For a bathtub to shower retrofit, a 1 1 / 2 inch (40 mm) trap and trap arm shall be permitted with a maximum shower size of 36 inches (914 mm) in width and 60 inches (1524 mm) in length. See Section 408.6 and Section 408.7. 10 For drainage fixture unit values related to lots within mobilehome parks in all parts of the State of California, see California Code of Regulations, Title 25, Division 1, Chapter 2, Article 5, Section 1268. For drainage fixture unit values related to lots within special occupancy parks in all parts of the State of Cal- ifornia, see California Code of Regulations, Title 25, Division 1, Chapter 2.2, Article 5, Section 2268.
required, and the unit equivalent of fixtures and devices not shown in Table 702.1 shall be based on the size of trap or trap
arm.
Maximum drainage fixture units for a fixture trap and trap arm loadings for sizes up to 4 inches (100 mm) shall be in accordance with Table 702.1(1).
TABLE 702.1(1) MAXIMUM DRAINAGE FIXTURE UNITS FOR A
TRAP AND TRAP ARM*
SIZE OF TRAP AND
TRAP ARM (inches)DRAINAGE FIXTURE UNIT
VALUES (DFU)
11⁄41 unit
11⁄23 units
24 units 3 6 units
48 units For SI Units: 1 inch = 25 mm
*** Exception:** On self-service laundries.
702.2 Intermittent Flow. Drainage fixture units for intermittent flow into the drainage system shall be computed on the rated discharge capacity in gallons per minute (gpm) (L/s) in accordance with Table 702.2.
TABLE 702.1(1) MAXIMUM DRAINAGE FIXTURE UNITS FOR A
TRAP AND TRAP ARM*
CPC § 610.4. Medium relevance — show source text
(3) Use the “pressure range” group within which this pressure will fall using Table 610.4.
(4) Select the “length” column that is equal to or longer than the required length.
(5) Follow down the column to a fixture unit value equal to or exceeding the total number of fixture units required by the installation.
(6) Having located the proper fixture unit value for the required length, sizes of meter and building supply pipe as found in the two left-hand columns shall be applied.
No building supply pipe shall be less than [3] ⁄ 4 of an inch (20 mm) in diameter.
610.9 Size of Branches. Where Table 610.4 is used, the minimum size of each branch shall be determined by the total fixture units served by that branch and then following the steps in Section 610.8. No branch piping shall exceed the total demand in fixture units for the system computed from Table 610.3.
610.10 Sizing for Flushometer Valves. Where using Table 610.4 to size water supply systems serving flushometer valves, the number of flushometer fixture units assigned to every section of pipe, whether branch or main, shall be determined by the number and category of flushometer valves served by that section of pipe, in accordance with Table 610.10. Piping supplying a flushometer valve shall be not less in size than the valve inlet.
Where using Table 610.10 to size water piping, care shall be exercised to assign flushometer fixture units based on the number and category of fixtures served.
TABLE 610.10 FLUSHOMETER FIXTURE UNITS FOR WATER SIZING USING TABLE 610.3 Col2 Col3 FIXTURE CATEGORY: WATER CLOSET WITH FLUSHOMETER VALVES FIXTURE CATEGORY: WATER CLOSET WITH FLUSHOMETER VALVES FIXTURE CATEGORY: WATER CLOSET WITH FLUSHOMETER VALVES
NUMBER OF
FLUSHOMETER
VALVESINDIVIDUAL
FIXTURE UNITS
ASSIGNED IN
DECREASING
VALUEFIXTURE UNITS ASSIGNED
FOR WATER CLOSETS AND
SIMILAR 10-UNIT FIXTURES IN
ACCUMULATIVE VALUES
140 40
230 70
320 90 4 15 105
5 or more10 each 115 plus 10 for each additional
fixture in excess of 5
FIXTURE CATEGORY: URINALS WITH FLUSHOMETER VALVES
FIXTURE CATEGORY: URINALS WITH FLUSHOMETER VALVES
FIXTURE CATEGORY: URINALS WITH FLUSHOMETER VALVES
NUMBER OF
FLUSHOMETER
VALVESINDIVIDUAL
FIXTURE UNITS
ASSIGNED IN
DECREASING
VALUEFIXTURE UNITS ASSIGNED
FOR URINALS AND SIMILAR
**5-UNIT FIXTURESCPC § 1.0 Medium relevance — show source text
0| |Nonwater Urinal with Drain Cleansing Action|1⁄2|1.0|1.0|1.0| |Wash Fountain, circular spray|3⁄4|––|4.0|––| |Water Closet, 1.6 GPF Gravity Tank|1⁄2|2.5|2.5|3.5| |Water Closet, 1.6 GPF Flushometer Tank|1⁄2|2.5|2.5|3.5| |Water Closet, 1.6 GPF Flushometer Valve|1|See Footnote7|See Footnote7|––| |Water Closet, greater than 1.6 GPF Gravity Tank|1⁄2|3.0|5.5|7.0| |Water Closet, greater than 1.6 GPF Flushometer Valve|1|See Footnote7|See Footnote7|––|
For SI units: 1 inch = 25 mm
Notes: 1 Size of the cold branch pipe, or both the hot and cold branch pipes. 2 Appliances, appurtenances, or fixtures not referenced in this table shall be permitted to be sized by reference to fixtures having a similar flow rate and frequency of use. 3 The listed fixture unit values represent their load on the cold water building supply. The separate cold water and hot water fixture unit value for fixtures having both hot and cold water connections shall be permitted to be each taken as three-quarter of the listed total value of the fixture. 4 The listed minimum supply branch pipe sizes for individual fixtures are the nominal (I.D.) pipe size. 5 For fixtures or supply connections likely to impose continuous flow demands, determine the required flow in gallons per minute (gpm) (L/s), and add it separately to the demand in gpm (L/s) for the distribution system or portions thereof. 6 Assembly [Public Use (See Table 422.1)]. 7 Where sizing flushometer systems, see Section 610.10. 8 Reduced fixture unit loading for additional hose bibbs is to be used where sizing total building demand and for pipe sizing where more than one hose bibb is supplied by a segment of water distribution pipe. The fixture branch to each hose bibb shall be sized on the basis of 2.5 fixture units. 9 For water supply fixture unit values related to lots within mobilehome parks in all parts of the State of California, see California Code of Regulations, Title 25, Division 1, Chapter 2, Article 5, Section 1278. For water supply fixture unit values related to lots within special occupancy parks in all parts of the State of California, see California Code of Regulations, Title 25, Division 1, Chapter 2.2, Article 5, Section 2278.
158 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
WATER SUPPLY AND DISTRIBUTION
Col1 Col2 TABLE 610.4 FIXTURE UNIT TABLE FOR DETERMINING WATER PIPE AND METER SIZES Col4 Col5 Col6 Col7 Col8 Col9 Col10 Col11 Col12 Col13 Col14 Col15 Col16 Col17 **METER CPC § 610.6 Medium relevance — show source text
610.6 Friction and Pressure Loss. Except where the type of pipe used and the water characteristics are such that no decrease in capacity due to the length of service (age of system) is expected, friction-loss data shall be obtained from the “Fairly Rough” or “Rough” charts in Appendix A of this code. Friction or pressure losses in a water meter, valve, and fittings shall be obtained from the same sources. Pressure losses through water-treating equipment, backflow prevention devices, or other flow-restricting devices shall be computed in accordance with Section 610.2. 610.7 Conditions for Using Table 610.4. On a proposed water piping installation sized using Table 610.4, the following conditions shall be determined:
(1) Total number of fixture units as determined from Table 610.3, Equivalent Fixture Units, for the fixtures to be installed.
(2) Developed length of supply pipe from meter to the most remote outlet.
(3) Difference in elevation between the meter or other source of supply and the highest fixture or outlet.
(4) Pressure in the street main or another source of supply at the locality where the installation is to be made.
(5) In localities where there is a fluctuation of pressure in the main throughout the day, the water piping system shall be designed on the basis of the minimum pressure available. 610.8 Size of Meter and Building Supply Pipe Using Table 610.4. The size of the meter and the building supply pipe shall be determined as follows:
(1) Determine the available pressure at the water meter or other source of supply.
(2) Add or subtract depending on positive or negative elevation change, [1] ⁄ 2 psi (3.4 kPa) for each foot (305 mm) of difference in elevation between such source of supply and the highest water supply outlet in the building or on the premises.
(3) Use the “pressure range” group within which this pressure will fall using Table 610.4.
(4) Select the “length” column that is equal to or longer than the required length.
(5) Follow down the column to a fixture unit value equal to or exceeding the total number of fixture units required by the installation.
(6) Having located the proper fixture unit value for the required length, sizes of meter and building supply pipe as found in the two left-hand columns shall be applied.
No building supply pipe shall be less than [3] ⁄ 4 of an inch (20 mm) in diameter.
610.9 Size of Branches. Where Table 610.4 is used, the minimum size of each branch shall be determined by the total fixture units served by that branch and then following the steps in Section 610.8. No branch piping shall exceed the total demand in fixture units for the system computed from Table 610.3.
610.10 Sizing for Flushometer Valves. Where using Table 610.4 to size water supply systems serving flushometer valves, the number of flushometer fixture units assigned to every section of pipe, whether branch or main, shall be determined by the number and category of flushometer valves served by that section of pipe, in accordance with Table 610.10. Piping supplying a flushometer valve shall be not less in size than the valve inlet.
Where using Table 610.10 to size water piping, care shall be exercised to assign flushometer fixture units based on the number and category of fixtures served.
|TABLE 610.
CPC § 422.1 Medium relevance — show source text
6 Assembly [Public Use (See Table 422.1)]. 7 Where sizing flushometer systems, see Section 610.10. 8 Reduced fixture unit loading for additional hose bibbs is to be used where sizing total building demand and for pipe sizing where more than one hose bibb is supplied by a segment of water distribution pipe. The fixture branch to each hose bibb shall be sized on the basis of 2.5 fixture units. 9 For water supply fixture unit values related to lots within mobilehome parks in all parts of the State of California, see California Code of Regulations, Title 25, Division 1, Chapter 2, Article 5, Section 1278. For water supply fixture unit values related to lots within special occupancy parks in all parts of the State of California, see California Code of Regulations, Title 25, Division 1, Chapter 2.2, Article 5, Section 2278.
158 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
WATER SUPPLY AND DISTRIBUTION
Col1 Col2 TABLE 610.4 FIXTURE UNIT TABLE FOR DETERMINING WATER PIPE AND METER SIZES Col4 Col5 Col6 Col7 Col8 Col9 Col10 Col11 Col12 Col13 Col14 Col15 Col16 Col17 METER AND
STREET
SERVICE
(inches)BUILDING
SUPPLY
AND
BRANCHES
(inches)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)MAXIMUM ALLOWABLE LENGTH
(feet)METER AND
STREET
SERVICE
(inches)BUILDING
SUPPLY
AND
BRANCHES
(inches)40 60 80 100 150 200 250 300 400 500 600 700 800 900 1000 PRESSURE RANGE – 30 to 45 psi1 PRESSURE RANGE – 30 to 45 psi1 **PRESSURE RANGE CPC § 304.3.1 Medium relevance — show source text
be sized based on the total accumulated connected load at each story or branch interval.
C 304.3.1 Horizontal Stack Offsets. Horizontal
stack offsets shall be sized in accordance with Table C 304.2 as required for building drains.
C 304.3.2 Vertical Stack Offsets. Vertical stack off sets shall be sized in accordance with Table C 304.3 as required for stacks.
C 304.4 Horizontal Stack Offset and Horizontal Branch
Connections. Horizontal branch connections shall not connect to a horizontal stack offset or within 2 feet (610 mm) above or below the offset where such horizontal offset is located more than four branch intervals below the top of the stack.
C 401.0 Vent System Sizing. C 401.1 Size of Vents. The size of vent piping shall be determined from the developed length and the total number of drainage fixture units connected in accordance with Table C 401.1. Vents shall be not less than one-half the required size of the drainage pipe size served as determined by Table C 304.3 for horizontal fixture branches and stacks nor less than 1 [1] ⁄ 4 inches
(32 mm) in diameter. The drainage system shall be vented by not less than one vent pipe which shall be not less than one-half the size of the required building drain and which shall extend from the building drain or extension of building drain to the outdoors. Vents shall be installed in accordance with Chapter 9. C 401.2 Vent Stack. A vent stack shall be required for a drainage stack that extends five or more branch intervals above the building drain or horizontal branch. The developed length of the vent stack shall be measured from the lowest connection of a branch vent to the termination outdoors.
C 401.3 Branch Vents. Where branch vents exceed 40 feet (12 192 mm) in developed length, such vent shall be increased by one pipe size for the entire developed length of the vent pipe. C 401.4 Venting Horizontal Offsets. Drainage stacks with horizontal offsets shall be vented where five or more branch intervals are located above the offset. The upper and lower section of the horizontal offset shall be vented in accordance
with Section C 401.4.1 and Section C 401.4.2.
C 401.4.1 Venting Upper Section. The vent for the upper section of the stack shall be vented as a separate stack with a vent stack connection installed at the base of the drainage stack. Such vent stack shall connect below the lowest horizontal branch or building drain. Where vent stack connects to the building drain, the connection shall be located downstream of the drainage stack and within a distance of 10 times the diameter of the drainage stack. C 401.4.2 Venting Lower Section. The vent for the lower section of the stack shall be vented by a yoke vent connecting between the offset and the next lower horizontal branch using a wye-branch fitting. The size of the yoke vent and connection shall be not less in diameter
388 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX C
TABLE C 303.3 DRAINAGE FIXTURE UNIT VALUES (DFU) FOR BATHROOM GROUPS [1, 2]
Frequently asked questions
What is a "fixture unit" in the CPC and where is it defined?
A fixture unit is an indexing value that represents the probable demand (water or drainage) of a fixture for sizing purposes; water‑supply fixture units are given in Table 610.3 and described in §610.3, and drainage fixture unit values and methods are set out in Chapter 7 (see Table 702.1(1) and related sections) file.
Which tables/sections do I use to size a building supply or meter?
Use Table 610.3 to total fixture units and Table 610.4 with the procedure in §610.7–§610.8 (determine available pressure, developed length and elevation, then read the appropriate pressure/length column) to select meter and building‑supply sizes; Appendix A provides a more detailed calculation method if required file.
Can I use an alternate (engineered) sizing method?
Yes — the CPC permits alternate sizing procedures where justified: Appendix A provides recommended rules for detailed hydraulic sizing and Appendices C and M offer alternate methods that may be used with AHJ approval .
More in California Plumbing Code
- Administration
- Definitions
- General Regulations
- Plumbing Fixtures and Fixture Fittings
- Water Heaters
- Water Supply and Distribution
- Sanitary Drainage (Drain, Waste, and Vent)
- Indirect Wastes
- Vents
- Traps and Interceptors
- Storm Drainage
- Fuel Gas Piping
- Health Care Facilities — Medical Gas and Medical Vacuum Systems
- Alternate Water Sources and Nonpotable Rainwater Catchment Systems
Ask about the CPC
Get cited, plain-English answers on the California Plumbing Code for your project — any code section, any scenario.
Start Free Trial