CPC · California Plumbing Code

Indirect waste piping: materials, sizing, traps and venting

This hub summarizes CPC Chapter 8 guidance on acceptable materials, minimum sizes and lengths, air‑gap/air‑break requirements, and the trap/vent rules that apply to indirect waste piping.

Last reviewed: July 6, 2026

Overview

Chapter 8 (Indirect Wastes) in the California Plumbing Code (CPC) governs indirect waste piping, receptors, and connections — including air gaps/air breaks, condensate and specialty wastes, and the layout and sizing needed to avoid cross‑contamination or sewer backflow . The chapter establishes when an air gap or air break is required (§801.2) and which types of equipment and spaces (food handling, refrigeration, sterilizers, etc.) must use indirect connections or separate receptors .

Material, sizing and routing rules for indirect waste piping are set out in §§803–805: §803.1 requires approved materials and design, §803.3 ties minimum diameters and maximum developed lengths to the fixture outlet and limits (for example, indirect wastes ≤15 ft must be at least the unit outlet size and some runs between 5–15 ft must be trapped) and §804.1 covers standpipe receptor sizing and location requirements . Condensate and appliance drains have their own sizing and material rules (see §814.3 and related provisions), including minimum diameters and acceptable materials for <1¼" lines (PVC, CPVC, PE, PP, copper, etc.) .

Traps and venting for indirect wastes are coordinated with the CPC Vent and Traps chapters: venting principles are in Chapter 9 and trap/interceptor requirements in Chapter 10. The CPC explicitly requires that vents from indirect waste piping be routed separately to outdoors and not combined with sewer‑connected vents, and it describes when direct trapping is required (see §803.3) .

In this section

Code references

Grounded in the retrieved California Plumbing Code — click a citation to read the verbatim passage:

  • CPC § 2025 High relevance — show source text

    Chapter 7 Sanitary Drainage.

    This chapter regulates the design and installation of sanitary drainage systems to ensure they will work as intended. Drainage piping should not be oversized nor undersized, and constructed of approved materials to guard against fouling, deposit of solids, clogging, and with cleanouts so arranged that the pipes may be readily cleaned. The purpose of the sanitary drainage system is to remove effluent discharged from plumbing fixtures and other equipment to an approved point of disposal, such as a public sanitary system or private sewage disposal system.

    The basics of a sanitary drainage system include public and private sewage disposal; selection of materials; installation of the building drain and sewer; joining methods for pipe and fittings; drainage fixture units for sizing the drainage system; sumps and ejectors; vent sizing and length of vents; and testing.

    Chapter 8 Indirect Wastes.

    Chapter 8 regulates indirect waste connections that are required for plumbing fixtures and plumbing appliances dealing with food preparation, dishwashing, potable liquids, and similar equipment. An indirect connection prevents sewage from backing up into a fixture or appliance, thus providing protection against potential health hazards. The waste pipe discharges through an air gap or air break into a waste receptor or standpipe. The protection in the form of an air gap is necessary when the contamination is a potential health hazard or cross connection with the potable water system. Where there is no possibility of contaminating the potable water (nonpotable discharge), the indirect waste pipe may connect in the form of an air break. This method is often preferred to prevent splashing. In addition, health care facilities and special wastes must be protected from contamination that may result from the connection to the drainage system. The waste must be treated to prevent any damage to the piping or sewage treatment process. Waste receptors are sized and designed to prevent splashing and allow for peak discharge conditions.

    Chapter 9 Vents.

    Chapter 9 regulates the material, design, and installation of vents. A vent system is a pipe or pipes installed in a drainage system that provide a flow of air to and from the system to ventilate it, provide a circulation of air to eliminate trap siphonage, and reduce back-pressure and vacuum surge. In addition, vents provide the rapid and silent flow of waste without exposing occupants of the building to any sewer gases. Proper installation of vents is crucial, as a telltale sign that there is a problem in the drain and vent system is related to the elevation of the horizontal portion of the venting. Venting is not limited to sanitary drainage systems. Venting methods are applicable to other drainage systems such as those for chemical waste, graywater waste, and clear water waste. Sizing the venting system is directly tied to the design of the drainage system. For example, the velocities in the drainage system and its peak flow rates affect the diameters in the venting system. Where the vertical distance between a fixture outlet and trap is excessive, velocities in the entire drainage system will be greater than those in the vent sizing table. All venting methods in this chapter are categorized as either dry vents or wet vents. Vent stacks, stack vents, branch vents, island vents, relief vents, and individual vents are dry vents. Wet vents (horizontal or vertical), circuit vents, combination drain and vents are versions of “wet venting” in which the vent is wetted by drainage flow.

    2025 CALIFORNIA PLUMBING CODE xv

  • CPC § 803.0 High relevance — show source text

    803.0 Indirect Waste Piping.

    803.1 Materials. Pipe, tube, and fittings conveying indirect waste shall be of such materials and design as to perform their intended function to the satisfaction of the Authority Having Jurisdiction.

    803.2 Copper and Copper Alloys. Joints and connections in copper and copper alloy pipe and tube shall be installed in accordance with Section 705.3.

    803.3 Pipe Size and Length. Except as hereinafter provided, the size of indirect waste piping shall be in accordance with other sections of this code applicable to drainage and vent piping. No vent from indirect waste piping shall combine with a sewer-connected vent. Vents from indirect waste piping shall extend separately to the outside air. Indirect waste pipes exceeding 5 feet (1524 mm), but less than 15 feet (4572 mm) in length shall be directly trapped, but such traps need not be vented.

    Indirect waste pipes less than 15 feet (4572 mm) in length shall be not less than the diameter of the drain outlet or

    2025 CALIFORNIA PLUMBING CODE 181

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    INDIRECT WASTES

    tailpiece of the fixture, appliance, or equipment served, and in no case less than [1] ⁄ 2 of an inch (15 mm). Angles and changes of direction in such indirect waste pipes shall be provided with cleanouts to permit flushing and cleaning.

    804.0 Indirect Waste Receptors.

    804.1 Standpipe Receptors. Plumbing fixtures or other receptors receiving the discharge of indirect waste pipes shall be approved for the use proposed and shall be of such shape and capacity as to prevent splashing or flooding and shall be located where they are readily accessible for inspection and cleaning. No standpipe receptor for a clothes washer shall extend more than 30 inches (762 mm), or not less than 18 inches (457 mm) above its trap weir. No trap for a clothes washer standpipe receptor shall be installed below the floor, but shall be roughed in not less than 6 inches (152 mm) and not more than 18 inches (457 mm) above the floor. No indirect waste receptor shall be installed in a toilet room, closet, cupboard, or storeroom, or in a portion of a building not in general use by the occupants thereof; except standpipes for clothes washers shall be permitted to be installed in toilet and bathroom areas where the clothes washer is installed in the

    same room.

    805.0 Pressure Drainage Connections. 805.1 General. Indirect waste connections shall be provided for drains, overflows, or relief vents from the water supply system, and no piping or equipment carrying wastes or producing wastes or other discharges under pressure shall be directly connected to a part of the drainage system.

    The preceding shall not apply to an approved sump pump or to an approved pressure-wasting plumbing fixture or device where the Authority Having Jurisdiction has been satisfied that the drainage system is adequately sized to accommodate the anticipated discharge thereof.

    806.0 Sterile Equipment.

    806.1 General. Appliances, devices, or apparatus such as stills, sterilizers, and similar equipment requiring water and waste and used for sterile materials shall be drained through an air gap.

    807.0 Appliances.

  • CPC § 801.4 High relevance — show source text

    The piping from the equipment to the receptor shall be not less than the drain on the unit and in no case less than [1] ⁄ 2 of an inch (15 mm).

    801.4 Bar and Fountain Sink Traps. Where the sink in a bar, soda fountain, or counter is so located that the trap serving the sink cannot be vented, the sink drain shall discharge through an air gap or air break (see Section 801.3.3) into an approved receptor that is vented. The developed length from the fixture outlet to the receptor shall not exceed 5 feet (1524 mm). 801.5 Connections from Water Distribution System. Indirect waste connections shall be provided for drains, overflows, or relief pipes from potable water pressure tanks, water heaters, boilers, and similar equipment that is connected to the potable water distribution system. Such indirect waste connections shall be made using a water-distribution air gap constructed in accordance with Table 603.3.1.

    801.6 Sterilizers. Lines, devices, or apparatus such as stills, sterilizers, and similar equipment requiring waste connections and used for sterile materials shall be indirectly connected using an air gap. Each such indirect waste pipe shall be separately piped to the receptor and shall not exceed 15 feet (4572 mm). Such receptors shall be located in the same room. 801.7 Drip or Drainage Outlets. Appliances, devices, or apparatus not regularly classified as plumbing fixtures, but which have a drip or drainage outlets, shall be permitted to be drained by indirect waste pipes discharging into an open receptor through either an air gap or air break (see Section 801.3.1).

    802.0 Approvals. 802.1 General. No plumbing fixtures served by indirect waste pipes or receiving discharge therefrom shall be installed until first approved by the Authority Having Jurisdiction.

    803.0 Indirect Waste Piping.

    803.1 Materials. Pipe, tube, and fittings conveying indirect waste shall be of such materials and design as to perform their intended function to the satisfaction of the Authority Having Jurisdiction.

    803.2 Copper and Copper Alloys. Joints and connections in copper and copper alloy pipe and tube shall be installed in accordance with Section 705.3.

    803.3 Pipe Size and Length. Except as hereinafter provided, the size of indirect waste piping shall be in accordance with other sections of this code applicable to drainage and vent piping. No vent from indirect waste piping shall combine with a sewer-connected vent. Vents from indirect waste piping shall extend separately to the outside air. Indirect waste pipes exceeding 5 feet (1524 mm), but less than 15 feet (4572 mm) in length shall be directly trapped, but such traps need not be vented.

    Indirect waste pipes less than 15 feet (4572 mm) in length shall be not less than the diameter of the drain outlet or

    2025 CALIFORNIA PLUMBING CODE 181

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    INDIRECT WASTES

    tailpiece of the fixture, appliance, or equipment served, and in no case less than [1] ⁄ 2 of an inch (15 mm). Angles and changes of direction in such indirect waste pipes shall be provided with cleanouts to permit flushing and cleaning.

    804.0 Indirect Waste Receptors.

    **804.1 Standpipe Receptors.

  • CPC § 801.3.1 High relevance — show source text

    801.3.1 Size of Indirect Waste Pipes. Except for refrigeration coils and ice-making machines, the size of the indirect waste pipe shall be not smaller than the drain on the unit, but shall be not smaller than 1 inch (25 mm), and the maximum developed length shall not exceed 15 feet (4572 mm). Indirect waste pipe for ice-making machines shall be not less than the drain on the unit and in no case less than [3] ⁄ 4 of an inch (20 mm). 801.3.2 Walk-In Coolers. For walk-in coolers, floor drains shall be permitted to be connected to a separate drainage line discharging into an outside receptor. The flood-level rim of the receptor shall be not less than 6 inches (152 mm) lower than the lowest floor drain. Such floor drains shall be trapped and individually vented. Cleanouts shall be provided at 90 degree (1.57 rad) turns and shall be accessibly located. Such waste shall discharge through an air gap or air break into a trapped and vented receptor, except that a full-size air gap is required where the indirect waste pipe is under vacuum. 801.3.3 Food-Handling Fixtures. Food-preparation sinks, steam kettles, potato peelers, ice cream dipper wells, and similar equipment shall be indirectly connected to the drainage system by means of an air gap. Bins, sinks, and other equipment having drainage connections and used for the storage of unpackaged ice used for human ingestion, or used in direct contact with ready-to-eat food, shall be indirectly connected to the drainage system by means of an air gap. Each indirect waste pipe from foodhandling fixtures or equipment shall be separately piped to the indirect waste receptor and shall not combine with other indirect waste pipes. The piping from the equipment to the receptor shall be not less than the drain on the unit and in no case less than [1] ⁄ 2 of an inch (15 mm).

    801.4 Bar and Fountain Sink Traps. Where the sink in a bar, soda fountain, or counter is so located that the trap serving the sink cannot be vented, the sink drain shall discharge through an air gap or air break (see Section 801.3.3) into an approved receptor that is vented. The developed length from the fixture outlet to the receptor shall not exceed 5 feet (1524 mm). 801.5 Connections from Water Distribution System. Indirect waste connections shall be provided for drains, overflows, or relief pipes from potable water pressure tanks, water heaters, boilers, and similar equipment that is connected to the potable water distribution system. Such indirect waste connections shall be made using a water-distribution air gap constructed in accordance with Table 603.3.1.

    801.6 Sterilizers. Lines, devices, or apparatus such as stills, sterilizers, and similar equipment requiring waste connections and used for sterile materials shall be indirectly connected using an air gap. Each such indirect waste pipe shall be separately piped to the receptor and shall not exceed 15 feet (4572 mm). Such receptors shall be located in the same room. 801.7 Drip or Drainage Outlets. Appliances, devices, or apparatus not regularly classified as plumbing fixtures, but which have a drip or drainage outlets, shall be permitted to be drained by indirect waste pipes discharging into an open receptor through either an air gap or air break (see Section 801.3.1).

  • CPC § 1.11.0. High relevance — show source text

    This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.

    2025 CALIFORNIA PLUMBING CODE 179

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    180 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CHAPTER 8

    INDIRECT WASTES

    801.0 General.

    801.1 Applicability. This chapter shall govern the materials, design, and installation of indirect waste piping, receptors, and connections; and provisions for discharge and disposal of condensate wastes, chemical wastes, industrial wastes, and clear water wastes.

    801.2 Air Gap or Air Break Required. Indirect waste piping shall discharge into the building drainage system through an air gap or air break as set forth in this code. Where a drainage air gap is required by this code, the minimum vertical distance as measured from the lowest point of the indirect waste pipe or the fixture outlet to the flood-level rim of the receptor shall be not less than 1 inch (25.4 mm). 801.3 Food and Beverage Handling Establishments. Establishments engaged in the storage, preparation, selling, serving, processing, or other handling of food and beverage involving the following equipment that requires drainage shall provide indirect waste piping for refrigerators, refrigeration coils, freezers, walk-in coolers, iceboxes, ice-making machines, steam tables, egg boilers, coffee urns and brewers, hot-and-cold drink dispensers, and similar equipment. 801.3.1 Size of Indirect Waste Pipes. Except for refrigeration coils and ice-making machines, the size of the indirect waste pipe shall be not smaller than the drain on the unit, but shall be not smaller than 1 inch (25 mm), and the maximum developed length shall not exceed 15 feet (4572 mm). Indirect waste pipe for ice-making machines shall be not less than the drain on the unit and in no case less than [3] ⁄ 4 of an inch (20 mm). 801.3.2 Walk-In Coolers. For walk-in coolers, floor drains shall be permitted to be connected to a separate drainage line discharging into an outside receptor. The flood-level rim of the receptor shall be not less than 6 inches (152 mm) lower than the lowest floor drain. Such floor drains shall be trapped and individually vented. Cleanouts shall be provided at 90 degree (1.57 rad) turns and shall be accessibly located. Such waste shall discharge through an air gap or air break into a trapped and vented receptor, except that a full-size air gap is required where the indirect waste pipe is under vacuum. 801.3.3 Food-Handling Fixtures. Food-preparation sinks, steam kettles, potato peelers, ice cream dipper wells, and similar equipment shall be indirectly connected to the drainage system by means of an air gap.

  • CPC § 2025 High relevance — show source text

    The waste must be treated to prevent any damage to the piping or sewage treatment process. Waste receptors are sized and designed to prevent splashing and allow for peak discharge conditions.

    Chapter 9 Vents.

    Chapter 9 regulates the material, design, and installation of vents. A vent system is a pipe or pipes installed in a drainage system that provide a flow of air to and from the system to ventilate it, provide a circulation of air to eliminate trap siphonage, and reduce back-pressure and vacuum surge. In addition, vents provide the rapid and silent flow of waste without exposing occupants of the building to any sewer gases. Proper installation of vents is crucial, as a telltale sign that there is a problem in the drain and vent system is related to the elevation of the horizontal portion of the venting. Venting is not limited to sanitary drainage systems. Venting methods are applicable to other drainage systems such as those for chemical waste, graywater waste, and clear water waste. Sizing the venting system is directly tied to the design of the drainage system. For example, the velocities in the drainage system and its peak flow rates affect the diameters in the venting system. Where the vertical distance between a fixture outlet and trap is excessive, velocities in the entire drainage system will be greater than those in the vent sizing table. All venting methods in this chapter are categorized as either dry vents or wet vents. Vent stacks, stack vents, branch vents, island vents, relief vents, and individual vents are dry vents. Wet vents (horizontal or vertical), circuit vents, combination drain and vents are versions of “wet venting” in which the vent is wetted by drainage flow.

    2025 CALIFORNIA PLUMBING CODE xv

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    FORMAT OF THE UNIFORM PLUMBING CODE

    Chapter 10 Traps and Interceptors.

    Chapter 10 regulates the material, design, and installation of traps, interceptors, and separators. Traps are required on drainage type plumbing fixtures and must be self-scouring without interior partitions. Interceptors, on the other hand, are designed to control what goes down a drain. Interceptors are used to keep harmful substances from entering the sanitary drainage system, such as grease, sand, oil and other materials. The retained materials need periodic removal to maintain efficiency and function of the separating device. The capacity of an interceptor is based on retention and flow rate. There are many types of interceptors that are used at beauty salons, hospitals, meat, fish or foul packaging, refineries, repair garages, gas stations, car washing facilities, various plants, factories, and processing sites. The designer of the building is responsible for locating interceptors with the expectation for the frequency of maintenance, ease of cleaning and floor space for equipment.

    Chapter 11 Storm Drainage.

    Chapter 11 regulates the removal of stormwater from roofs, yards, paved areas, and similar areas. The objective of storm drainage systems is to provide a conduit or channel through which runoff will be carried from a point of collection to a point of disposal; this protects the property and the public from the uncontrolled flow of runoff and ensures that drains and inlets are adequately sized to receive the volume of runoff that flows to the drains. For the purpose of system design, it’s necessary to specify the duration of a selected storm.

  • CPC § 814.3 High relevance — show source text

    814.3 Condensate Waste Pipe Material and Sizing. Condensate waste pipes from air-cooling coils shall be sized in accordance with the equipment capacity as specified in Table 814.3. The material of the piping shall comply with the pressure and temperature rating of the appliance or equipment and shall be approved for use with the liquid being discharged.

    TABLE 814.3

    MINIMUM CONDENSATE PIPE SIZE

    EQUIPMENT CAPACITY IN TONS
    OF REFRIGERATION
    MINIMUM CONDENSATE PIPE
    DIAMETER
    (inches)
    Up to 20 3⁄4


    21 – 40
    1


    41 – 90
    11⁄4

    91 – 125
    11⁄2

    126 – 250
    2

    For SI units: 1 ton of refrigerant = 3.52 kW, 1 inch = 25 mm

    The size of condensate waste pipes is for one unit or a combination of units, or as recommended by the manufacturer. The capacity of waste pipes assumes a [1] ⁄ 8 inch per foot (10.4 mm/m) or 1 percent slope, with the pipe running threequarters full at the following pipe conditions:

    Outside Air – 20% Col2 Room Air – 80% Col4


    DB
    WB
    DB
    WB

    90°F
    73°F 75°F 62.5°F

    For SI units: °C = (°F-32)/1.8

    Condensate drain sizing for other slopes or other conditions shall be approved by the Authority Having Jurisdiction.

    Air-conditioning waste pipes, 1¼ of an inch (32 mm) and larger in size, shall be constructed of materials specified in Chapter 7. Condensate waste piping less than 1¼ of an inch (32 mm) in size shall be permitted to be PVC, CPVC, PE, PP, copper, or other rigid materials approved by the Authority Having Jurisdiction.

    814.3.1 Cleanouts. Condensate drain lines shall be configured or provided with a cleanout to permit the clearing of blockages and for maintenance without requiring the drain line to be cut. 814.4 Appliance Condensate Drains. Condensate drain lines from individual condensing appliances shall be sized as required by the manufacturer’s instructions. Condensate drain lines serving more than one appliance connecting to a common indirect waste pipe shall have the connections to the indirect waste pipe protected by a sanitary waste valve complying with ASME A112.18.8, condensate trap complying with IAPMO IGC 196, or trap with a trap primer. 814.5 Point of Discharge. Air-conditioning condensate waste pipes shall connect indirectly to the drainage system through an air gap or air break to trapped and vented receptors, dry wells, mop sinks, leach pits, or the tailpiece of plumbing fixtures. An individual condensate drain shall be trapped in accordance with the appliance manufacturer’s instructions or in accordance with Section 814.4.

    TABLE 814.3

    MINIMUM CONDENSATE PIPE SIZE

    For SI units: 1 ton of refrigerant = 3.52 kW, 1 inch = 25 mm

  • CPC § 310.2.1 High relevance — show source text

    310.2.1 Protection of Appurtenances. Where insulation or appurtenances are installed where damage is capable of resulting from a condensate drain pan overfill, such installations shall occur above the rim of the drain

    pan with supports. Where the supports are in contact with the condensate waste, the supports shall be of approved corrosion-resistant material.

    310.3 Condensate Waste Pipe Material and Sizing. Condensate waste pipes from air-cooling coils shall be sized in accordance with the equipment capacity as specified in Table 310.3. The material of the piping shall comply with the pressure and temperature rating of the appliance or equipment, and shall be approved for use with the liquid being discharged.

    TABLE 310.3

    MINIMUM CONDENSATE PIPE SIZE

    2025 CALIFORNIA MECHANICAL CODE 57

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    GENERAL REGULATIONS

    Condensate drain sizing for other slopes or other conditions shall be approved by the Authority Having Jurisdiction.

    Air-conditioning waste pipes, 1¼ of an inch (32 mm) and larger in size, shall be constructed of materials specified in the plumbing code. Condensate waste piping less than 1¼ of an inch (32 mm) in size shall be permitted to be PVC, CPVC, PE, PP, copper, or other rigid materials approved by the Authority Having Jurisdiction.

    310.3.1 Cleanouts. Condensate drain lines shall be configured or provided with a cleanout to permit the clearing of blockages and for maintenance without requiring the drain line to be cut.

    310.4 Appliance Condensate Drains. Condensate drain lines from individual condensing appliances shall be sized as required by the manufacturer’s instructions. Condensate drain lines serving more than one appliance connecting to a common indirect waste pipe shall have the connections to the indirect waste pipe protected by a sanitary waste valve complying with ASME A112.18.8, condensate trap complying with IAPMO IGC 196, or trap with a trap primer.

    310.5 Point of Discharge. Air-conditioning condensate waste pipes shall connect indirectly to the drainage system through an air gap or air break to trapped and vented receptors, dry wells, mop sinks, leach pits, or the tailpiece of plumbing fixtures. An individual condensate drain shall be trapped in accordance with the appliance manufacturer’s instructions or in accordance with Section 310.4.

    310.6 Condensate Waste from Air-Conditioning Coils. Where the condensate waste from air-conditioning coils discharges by direct connection to a lavatory tailpiece or to an approved accessible inlet on a bathtub overflow, the connection shall be located in the area controlled by the same person controlling the air-conditioned space. 310.7 Female Plastic Connections. Female plastic screwed fittings shall be used with plastic male fittings and plastic male threads. Female plastic threaded connections shall not be allowed to be used when threaded onto a male

    metallic connection.

    311.0 Heating or Cooling Air System. 311.1 Source. A heating or cooling air system shall be provided with return air, outside air, or both. A heating or cooling air system regulated by this code and designed to replace required ventilation shall be arranged to discharge into a conditioned space not less than the amount of outside air specified in Chapter 4.

  • CPC § 814.3.1 High relevance — show source text

    Condensate drain sizing for other slopes or other conditions shall be approved by the Authority Having Jurisdiction.

    Air-conditioning waste pipes, 1¼ of an inch (32 mm) and larger in size, shall be constructed of materials specified in Chapter 7. Condensate waste piping less than 1¼ of an inch (32 mm) in size shall be permitted to be PVC, CPVC, PE, PP, copper, or other rigid materials approved by the Authority Having Jurisdiction.

    814.3.1 Cleanouts. Condensate drain lines shall be configured or provided with a cleanout to permit the clearing of blockages and for maintenance without requiring the drain line to be cut. 814.4 Appliance Condensate Drains. Condensate drain lines from individual condensing appliances shall be sized as required by the manufacturer’s instructions. Condensate drain lines serving more than one appliance connecting to a common indirect waste pipe shall have the connections to the indirect waste pipe protected by a sanitary waste valve complying with ASME A112.18.8, condensate trap complying with IAPMO IGC 196, or trap with a trap primer. 814.5 Point of Discharge. Air-conditioning condensate waste pipes shall connect indirectly to the drainage system through an air gap or air break to trapped and vented receptors, dry wells, mop sinks, leach pits, or the tailpiece of plumbing fixtures. An individual condensate drain shall be trapped in accordance with the appliance manufacturer’s instructions or in accordance with Section 814.4.

    TABLE 814.3

    MINIMUM CONDENSATE PIPE SIZE

    For SI units: 1 ton of refrigerant = 3.52 kW, 1 inch = 25 mm

    For SI units: °C = (°F-32)/1.8

    184 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    INDIRECT WASTES

    814.6 Condensate Waste from Air-Conditioning Coils. Where the condensate waste from air-conditioning coils discharges by direct connection to a lavatory tailpiece or to an approved accessible inlet on a bathtub overflow, the connection shall be located in the area controlled by the same person controlling the air-conditioned space. 814.7 Plastic Fittings. Female plastic screwed fittings shall be used with male plastic fittings and plastic threads.

    2025 CALIFORNIA PLUMBING CODE 185

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    186 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CALIFORNIA PLUMBING CODE – MATRIX ADOPTION TABLE

    CHAPTER 9 - VENTS

    (Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

  • CPC § 418.4 High relevance — show source text

    (3) Laundry rooms in commercial buildings and common laundry facilities in multi-family dwelling buildings. (4) Boiler rooms. 418.4 Food Storage Areas. Where drains are provided in storerooms, walk-in freezers, walk-in coolers, refrigerated equipment, or other locations where food is stored, such drains shall have indirect waste piping. Separate waste pipes shall be run from each food storage area, each with an indirect connection to the building sanitary drainage system. Traps shall be provided in accordance with Section 801.3.2 of this code and shall be vented.

    Indirect drains shall be permitted to be located in freezers or other spaces where freezing temperatures are maintained, provided that traps, where supplied, shall be located where the seal will not freeze. Otherwise, the floor of the freezer shall be sloped to a floor drain located outside of the storage compartment. 418.5 Floor Slope. Floors shall be sloped to floor drains.

    419.0 Food Waste Disposers. 419.1 Application. Food waste disposal units shall comply with UL 430. Residential food waste disposers shall also comply with ASSE 1008. 419.2 Drainage Connection. Approved wye or other directional-type branch fittings shall be installed in continuous wastes connecting or receiving the discharge from a food waste disposer. No dishwasher drain shall be connected to a sink tailpiece, continuous waste, or trap on the discharge side of a food waste disposer. 419.3 Water Supply. A cold water supply shall be provided for food waste disposers. Such connection to the water supply shall be protected by an air gap or backflow prevention device in accordance with Section 603.2.

    420.0 Sinks.

    420.1 Application. Sinks shall comply with ASME A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1, ASME A112.19.3/CSA B45.4, CSA B45.5/IAPMO Z124, CSA B45.8/IAPMO Z403, or CSA B45.12/IAPMO Z402. Moveable sink systems shall comply with ASME A112.19.12. Sink assemblies with automatic soap dispensers, faucets, or hand dryers shall comply with IAPMO IGC 127. 420.2 Water Consumption. Sink faucets shall have a maximum flow rate of not more than 2.2 gpm at 60 psi (8.3 L/m at 414 kPa).

    Exceptions: (1) Clinical sinks (2) Laundry sinks (3) Service sinks

    420.2.1 Kitchen Faucets. [BSC-CG & DSA-SS] Kitchen faucets shall have a maximum flow rate of not more than 1.8 gallons (6.81 L) per minute at 60 psi (414 kPa). Kitchen faucets may temporarily increase the flow above the maximum rate, but not to exceed 2.2 gallons (8.3 L) per minute at 60 psi (414 kPa), and must default to a maximum flow rate of 1.8 gallons (6.81 L) per minute at 60 psi (414 kPa) in compliance with Chapter 5, Division 5.3 of the California Green Building Stan- dards Code (CALGreen). _**420.2.2 Kitchen Faucets.

  • CPC § 722.3 High relevance — show source text

    722.3 Filling . . . . . . . . . . . . . . . . . . . . . .178

    722.4 Ownership . . . . . . . . . . . . . . . . . .178

    722.5 Disposal Facilities . . . . . . . . . . . . .178

    723.0 Building Sewer Test . . . . . . . . . . .178

    723.1 General . . . . . . . . . . . . . . . . . . . . .178

    724.0 Meat and Poultry Processing Plant Drainage . . . . . . . . . . . . . . .178

    725.0 Collection Center and

    Facilities Drainage . . . . . . . . . . . .178

    726.0 Drainage and Plumbing, General . . . . . . . . . . . . . . . . . . . . .178

    727.0 Emergency Sanitary Drainage . . .178

    CHAPTER 8 INDIRECT WASTES . . . . . . . . . .179

    801.0 General . . . . . . . . . . . . . . . . . . . . .181

    801.1 Applicability . . . . . . . . . . . . . . . . . .181

    801.2 Air Gap or Air Break Required . . .181

    801.3 Food and Beverage Handling Establishments . . . . . . .181

    801.4 Bar and Fountain Sink Traps . . . .181

    801.5 Connections from Water Distribution System . . . . . . . . . . . .181

    801.6 Sterilizers . . . . . . . . . . . . . . . . . . .181

    801.7 Drip or Drainage Outlets . . . . . . . .181

    802.0 Approvals . . . . . . . . . . . . . . . . . . .181

    802.1 General . . . . . . . . . . . . . . . . . . . . .181

    803.0 Indirect Waste Piping . . . . . . . . . .181

    803.1 Materials . . . . . . . . . . . . . . . . . . . .181

    803.2 Copper and Copper Alloys . . . . . .181

    803.3 Pipe Size and Length . . . . . . . . . .181

    804.0 Indirect Waste Receptors . . . . . . .182

    804.1 Standpipe Receptors . . . . . . . . . .182

    805.0 Pressure Drainage Connections . . . . . . . . . . . . . . . . .182

    805.1 General . . . . . . . . . . . . . . . . . . . . .182

    806.0 Sterile Equipment . . . . . . . . . . . . .182

    806.1 General . . . . . . . . . . . . . . . . . . . . .182

    807.0 Appliances . . . . . . . . . . . . . . . . . .182

    807.1 Non-Classed Apparatus . . . . . . . .182

    807.2 Undiluted Condensate Waste . . . .182

    807.3 Domestic Dishwashing Machine . . . . . . . . . . . . . . . . . . . .182

  • CPC § 2025 High relevance — show source text

    Appendix A Recommended Rules for Sizing the Water Supply System.

    Appendix A provides a method of sizing the water supply and distribution system that provides precise calculations to establish the proper pressures and flow to the system’s fixtures. The goal of sizing the system is to deliver an acceptable volume of water to the most hydraulically remote fixture during minimum pressure and maximum flow conditions; provide satisfactory water pressure to the most hydraulically remote fixture during minimum pressure and maximum flow conditions; and to prevent excessive water velocity during maximum flow conditions.

    Appendix B Explanatory Notes on Combination Waste and Vent Systems.

    Appendix B contains general guidelines for the design and installation of combination waste and vent systems. These systems are designed for waste piping and are purposely oversized to serve as both a waste and vent pipe to avoid excessive pneumatic effects at fixture drains.

    Appendix C Alternate Plumbing Systems.

    The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate materials, and equipment that are not specifically covered in other parts of the code. Alternative methods are allowed to be used where approved by the authority having jurisdiction. Approval of alternatives is based on a demonstration showing that the method or material used is at least equivalent in strength, deflection, and capacity to that provided by the prescriptive methods and materials.

    Appendix D Sizing Storm Water Drainage Systems.

    Appendix D provides general guidelines for the sizing of stormwater drainage systems. There are two pieces of information that must always be a given. They are the roof size and the rate of rainfall for the area.

    2025 CALIFORNIA PLUMBING CODE xvii

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    FORMAT OF THE UNIFORM PLUMBING CODE

    Appendix E Manufactured/Mobile Home Parks and Recreational Vehicle Parks.

    The provisions of this appendix apply to the plumbing and drainage systems of mobile home and recreational vehicle parks. These provisions also apply to the use, maintenance, and installation for supplying fuel gas, water, electricity, and disposal of sewage from accessory buildings or structures, and building components.

    Appendix F Firefighter Breathing Air Replenishment Systems.

    Appendix F provides guidance on installing firefighter breathing air replenishment systems. System components include outside fire department connection panel, interior air fill panel or station, interconnected piping distribution system and pressure monitoring switch. Fire departments access the system through an outside connection panel and are able to pump air into the system. The firefighters inside the structure access the system at fill stations that are found throughout the building. The piping distribution system is made from stainless tubing or other approved materials. It delivers compressed air to the building’s interior air-fill stations and interior air-fill panels. The tubing also acts as a conduit in the interior of the building between the outside connection panel and the air storage system. If the system becomes over-pressurized, the air monitoring system also acts as a pressure relief. A system isolation valve is placed alongside each interior air fill station and interior air fill panel to isolate the system.

    Appendix G Sizing of Venting Systems.

    Appendix G provides added information on the sizing of gas vents. This appendix is useful to the end user for the proper sizing of venting systems. A series of examples are given that show how to use the tables and other requirements of Chapter 5.

    Appendix H Private Sewage Disposal Systems.

Frequently asked questions

When is an air gap required for an indirect waste?

An air gap is required where the code identifies a potential health hazard or cross‑connection risk; Chapter 8 requires indirect waste piping to discharge through an air gap or air break and §801.2 sets the minimum vertical clearance for required air gaps, with food‑handling equipment specifically mandated to use air gaps (§801.3.3) .

Do indirect waste traps always need to be vented?

Not always. The CPC requires direct traps on indirect waste runs that exceed 5 feet but are less than 15 feet in developed length, but those traps need not be vented in every case; however, vents from indirect waste piping must not combine with sewer‑connected vents and must extend separately to outside air (§803.3) .

What materials and minimum sizes apply to condensate and other indirect drains?

Condensate and appliance indirect waste piping must meet the equipment manufacturer’s sizing or the CPC tables (see §814.3 for minimum condensate pipe sizes). Air‑conditioning condensate lines 1¼" and larger must meet Chapter 7 materials; smaller lines may be PVC, CPVC, PE, PP, copper, or other approved rigid materials per §814.3 and related text .

More in California Plumbing Code

Ask about the CPC

Get cited, plain-English answers on the California Plumbing Code for your project — any code section, any scenario.

Start Free Trial

Related in the CPC