CMC · California Mechanical Code

What are the rules for single‑wall metal pipe connectors and clearances?

For nonresidential uses where allowed, single‑wall metal pipe must be kept the minimum distances from combustible materials shown in Table 802.7.3.3 (see § 802.7.3.3). Listed appliance instructions and specific vent‑connector protection rules can require different or reduced clearances; single‑wall pipe may not originate in attics or pass through concealed spaces.

Last reviewed: July 6, 2026

What the code requires — 2-4 sentences

Single‑wall metal pipe connectors must maintain minimum clearances to combustible materials as listed in § 802.7.3.3; those minimum distances come from Table 802.7.3.3. Single‑wall metal pipe is limited to direct runs from the appliance to the outdoors (not through attics or concealed spaces) and is subject to termination, thimble and wall‑penetration requirements elsewhere in § 802.7. These clearance requirements are mandatory unless a specific appliance or connector listing or a permitted protection system reduces the clearance per the vent‑connector rules.

The most important rule: keep the minimum clearances in § 802.7.3.3 (see Table 802.7.3.3) between a single‑wall metal pipe (and its connector) and any combustible material unless a permitted, code‑specified protection reduces it.

Requirements in detail

Where these requirements live

  • The clearance rule is stated in § 802.7.3.3 (see Table 802.7.3.3) of the CMC.
  • The table of numeric minimum clearances is reproduced as Table 802.7.3.3 in the code.

Key plain‑English points

  • Single‑wall metal pipe may only be used where allowed by Section § 802.7 and must run directly from the appliance to the roof or exterior wall — it cannot originate or pass through unoccupied attics, concealed spaces, inside walls or floors. § 802.7.3.1 and § 802.7.3.2.
  • Minimum clearances to combustible materials vary by appliance category / heat class; the table (below) gives the controlling distances for single‑wall metal pipe. § 802.7.3.3.
  • Where the appliance or connector is listed with different clearances, the appliance/listing instructions control (i.e., listed clearances take precedence). § 802.7.3.3.

Decision‑relevant dimensions (quick reference)

Appliance / situation Minimum clearance to single‑wall metal pipe (inches) Code Reference
Listed appliances with draft hoods and appliances listed for use with Type B gas vents 6 in § 802.7.3.3
Residential boilers & furnaces with listed gas conversion burner and draft hood 9 in § 802.7.3.3
Residential appliances listed for use with Type L vents 9 in § 802.7.3.3
Unlisted residential appliances with draft hood 9 in § 802.7.3.3
Residential and low‑heat appliances (other than above) 18 in § 802.7.3.3
Medium‑heat appliances 36 in § 802.7.3.3

Notes:

  • These clearances are the minimum distances to combustible material when no special protection is used; where a listed appliance or connector gives different clearances, that listing controls. § 802.7.3.3.

Protection and reduced clearances

  • The code allows reduced clearances only as specified for vent connectors (i.e., by the vent‑connector protection tables and rules). The general allowance for reduction is stated in § 802.7.3.3: "Reduced clearances ... shall be as specified for vent connectors." For the specifics of how much clearance can be reduced and what protection is required, consult the vent‑connector protection tables and text for vent connectors (see § 802.10.4 and the connector protection tables).

Exceptions & special cases

  • Single‑wall metal pipe shall not be used as a vent in dwellings and residential occupancies unless specifically permitted by Section § 802.4; verify allowed appliance types before applying the clearances. § 802.7.3 (installation with appliances permitted by § 802.4).
  • Where single‑wall pipe passes through a roof of combustible construction, a noncombustible, non‑ventilating roof thimble is required; the thimble sizing and extension requirements are in § 802.7.3.4 and § 802.7.3.5.
  • Where a single‑wall pipe passes through a combustible exterior wall, a ventilated metal thimble (sized per § 802.7.3.5) or removal of combustible material to provide the required clearance is required. § 802.7.3.5.
  • If the appliance or connector is listed with its own clearance requirements, those listed instructions control over the generic table distances. § 802.7.3.3.

Common mistakes

  • Assuming single‑wall pipe clearances are the same for all appliances — clearance depends on appliance category / heat class; check the table in § 802.7.3.3.
  • Trying to run single‑wall pipe through attics, concealed spaces or interior walls — the code forbids those uses for single‑wall pipe. § 802.7.3.1 / § 802.7.3.2.
  • Reducing clearances without applying the specific vent‑connector protection methods listed in the code — reductions are only allowed when the specific protection for vent connectors is used and permitted. § 802.7.3.3 and vent‑connector sections.
  • Forgetting that listed appliances/connector manufacturer instructions can override the generic table — the listing/instructions may require larger or different clearances. § 802.7.3.3.

Worked example — concrete scenario

Scenario: A commercial laundry room has a medium‑heat gas dryer appliance (not a residential occupancy). A 6‑inch diameter single‑wall metal pipe runs vertically from the dryer up through the roof. There is a combustible framed partition located nearby.

Step 1 — Determine appliance category: "medium‑heat appliance." Check the single‑wall pipe clearance for medium‑heat appliances: 36 inches to combustible material per Table 802.7.3.3 (controlled by § 802.7.3.3). So the pipe must be at least 36 in from the combustible partition.

Step 2 — Consider reductions: If the installer wants to place the pipe closer, they must apply a code‑permitted protection system for vent connectors (for example, a listed wall protector or specified insulation/air‑gap system). The allowable reduction and the required protector construction are given in the vent‑connector protection rules/tables; consult the vent‑connector provisions before reducing clearance. § 802.7.3.3 and vent‑connector sections.

Step 3 — Check other requirements: ensure the pipe does not originate in an attic or pass through concealed spaces, and that roof thimble and termination requirements are met (see § 802.7.3.2, § 802.7.3.4 and § 802.7.2).

Result: Without protection, keep at least 36 in clearance. To reduce, follow the vent connector protection tables and manufacturer/listing instructions.

Related provisions

  • § 802.7.1 — Cold climate restriction for uninsulated single‑wall pipe.
  • § 802.7.2 — Termination height requirements for single‑wall metal pipe.
  • § 802.7.3.1 — Limitations: single‑wall pipe runs must be direct to roof/exterior.
  • § 802.7.3.2 — Prohibition on originating or passing through attics, concealed spaces, inside walls or floors.
  • § 802.7.3.4 — Roof thimble requirements where single‑wall pipe passes through combustible roofs.
  • § 802.7.3.5 — Combustible exterior wall thimble sizing and alternatives.
  • § 802.7.4 — Sizing rules for single‑wall metal pipe.
  • § 802.7.5 — Support requirements for single‑wall metal pipe.
  • § 802.10.4 — Clearance rules for vent connectors and reference to protection/reduction provisions.

Code references

Grounded in the retrieved California Mechanical Code — click a citation to read the verbatim passage:

  • CMC § 802.7.3.2 High relevance — show source text

    802.7.3.2 Attic or Concealed Space. Singlewall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. [NFPA 54:12.8.4.3]

    802.7.3.3 Clearances. Minimum clearances from

    single-wall metal pipe to combustible material shall be in accordance with Table 802.7.3.3. Reduced

    clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors. [NFPA 54:12.8.4.4]

    802.7.3.4 Roof Thimble. Where a single-wall metal pipe passes through a roof constructed of combustible material, a noncombustible, nonventilating thimble shall be used at the point of passage. The thimble shall extend at least 18 inches (457 mm) above and 6 inches (152 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 802.7.3.5. [NFPA 54:12.8.4.5] 802.7.3.5 Combustible Exterior Wall. Singlewall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following:

    (1) For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be a minimum of 4 inches (102 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet

    (1829 mm) of metal pipe in the opening between the draft hood outlet and the thimble, the thimble shall be a minimum of 2 inches (51 mm) larger in diameter than the metal pipe.

    (2) For unlisted appliances having draft hoods, the thimble shall be a minimum of 6 inches (152 mm) larger in diameter than the metal pipe.

    (3) For residential and low-heat appliances, the thimble shall be a minimum of 12 inches (305 mm) larger in diameter than the metal pipe.

    Exception: In lieu of thimble protection, all combustible material in the wall shall be removed a suffi cient distance from the metal pipe to provide the

    «

    «

    2025 CALIFORNIA MECHANICAL CODE 159

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    CHIMNEYS AND VENTS

    specified clearance from such metal pipe to combustible material. Any material used to close up such opening shall be noncombustible. [NFPA 54:12.8.4.6] 802.7.4 Size of Single-Wall Metal Pipe. Single-wall metal piping shall comply with the following require ments:

    (1) A venting system of a single-wall metal pipe shall be sized in accordance with one of the following methods and the appliance manufacturer’s instructions:

    (a) For a draft hood-equipped appliance, in accordance with Section 803.0.

  • CMC § 802.7.1 High relevance — show source text

    802.7.1 Cold Climate. Uninsulated single-wall metal pipe shall not be used outdoors for venting appliances in regions where the 99 percent winter design temperature is below 32°F (0°C). [NFPA 54:12.8.2]

    802.7.2 Termination. The termination of single-wall metal pipe shall meet the following requirements:

    (1) Single-wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar.

    (2) Single-wall metal pipe shall extend at least 2 feet (610 mm) above the highest point where it passes through a roof of a building and at least 2 feet (610 mm) higher than any portion of a building within a horizontal distance of 10 feet (3048 mm).

    (3) An approved cap or roof assembly shall be attached to the terminus of a single-wall metal pipe. [NFPA 54:12.8.3]

    802.7.3 Installation with Appliances Permitted by Section 802.4. Single-wall metal pipe shall not be used as a vent in dwellings and residential occupancies.

    [NFPA 54:12.8.4.1]

    802.7.3.1 Limitations. Single-wall metal pipe shall be used only for runs directly from the space in which the appliance is located through the roof or exterior wall to the outer air. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jacket, or roof thimble. [NFPA 54:12.8.4.2]

    802.7.3.2 Attic or Concealed Space. Singlewall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. [NFPA 54:12.8.4.3]

    802.7.3.3 Clearances. Minimum clearances from

    single-wall metal pipe to combustible material shall be in accordance with Table 802.7.3.3. Reduced

    clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors. [NFPA 54:12.8.4.4]

    802.7.3.4 Roof Thimble. Where a single-wall metal pipe passes through a roof constructed of combustible material, a noncombustible, nonventilating thimble shall be used at the point of passage. The thimble shall extend at least 18 inches (457 mm) above and 6 inches (152 mm) below the roof with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 802.7.3.5. [NFPA 54:12.8.4.5] 802.7.3.5 Combustible Exterior Wall. Singlewall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following:

    (1) For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be a minimum of 4 inches (102 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet

  • California Mechanical Code High relevance — show source text

    **|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    **CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.

  • CMC § 509.7.3.4 High relevance — show source text

    DISTANCE SPECIFIED AS THE**
    REQUIRED CLEARANCE WITH NO
    PROTECTION [SEE FIGURE
    509.7.3.4(1) THROUGH FIGURE
    509.7.3.4(3)]|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.| |TYPE OF PROTECTION APPLIED TO
    AND COVERING ALL SURFACES OF
    COMBUSTIBLE MATERIAL WITHIN
    THE DISTANCE SPECIFIED AS THE
    REQUIRED CLEARANCE WITH NO
    PROTECTION [SEE FIGURE
    509.7.3.4(1) THROUGH FIGURE
    **509.7.3.

  • CMC § 802.1 High relevance — show source text

    802.1 Listing . . . . . . . . . . . . . . . . . . . . . . 153

    802.2 Connection to Venting Systems . . 153

    802.3 Minimum Safe Performance . . . . . 153

    802.4 Type of Venting System to be Used . . . . . . . . . . . . . . . . . . . . . . . 154

    802.5 Masonry, Metal, and Factory-Built Chimneys . . . . . . . . . . . . . . . . . . . 154

    Table 802.4 Type of Venting System to be Used . . . . . . . . . . . . . . . . . . . . . . . 155

    802.6 Gas Vents. . . . . . . . . . . . . . . . . . . 157

    Table 802.6.1 Roof Slope Heights. . . . . . . . . . . . 158

    802.7 Single-Wall Metal Pipe . . . . . . . . . 159

    Table 802.7.3.3 Clearance for Connectors. . . . . . . 160

    802.8 Through-the-Wall Vent Termination . . . . . . . . . . . . . . . . . . 160

    802.9 Condensation Drain . . . . . . . . . . . 160

    802.10 Vent Connectors for Category I Appliances . . . . . . . . . . . . . . . . . . 160

    Table 802.10.1.3 Minimum Thickness for Galvanized

    Steel Vent Connectors for Low Heat Appliances . . . . . . . . . . . . . . 161

    Table 802.10.1.4 Minimum Thickness for Steel

    Vent Connectors for Medium Heat Appliances . . . . . . . . . . . . . . 161

    Table 802.8.1 Through-the-Wall Direct Vent Termination Clearances . . . . . . . . 162

    802.11 Vent Connectors for Category II, Category III, and Category IV Appliances . . . . . . . . . . . . . . . . . . 164

    802.12 Appliances Requiring Draft Hoods . . . . . . . . . . . . . . . . . . 164

    802.13 Manually Operated Dampers . . . . 165

    802.14 Automatically Operated Vent Dampers . . . . . . . . . . . . . . . . . . . . 165

    802.15 Obstruction of Flow. . . . . . . . . . . . 165

    803.0 Sizing of Category I Venting Systems . . . . . . . . . . . . . . . . . . . . 165

    803.1 Additional Requirements to Single Appliance Vent . . . . . . . . . 165

    803.2 Additional Requirements to Multiple-Appliance Vent.. . . . . . . . 167

    Table 803.2.1 Vent Connector Maximum

    Length. . . . . . . . . . . . . . . . . . . . . . 167

    Table 803.1.2(1) Type B Double-Wall Gas Vent . . . 172

    Table 803.1.2(2) Type B Double-Wall Gas Vent . . . 175

  • California Mechanical Code High relevance — show source text

    (INCHES)**|18 (INCHES)|12 (INCHES)|12 (INCHES)|9 (INCHES)|9 (INCHES)|6 (INCHES)|6 (INCHES)| |TYPE OF PROTECTION
    APPLIED TO AND COVERING
    ALL SURFACES OF COM-
    BUSTIBLE MATERIAL
    WITHIN THE DISTANCE
    SPECIFIED AS THE
    REQUIRED CLEARANCE
    WITH NO PROTECTION|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)| |TYPE OF PROTECTION
    APPLIED TO AND COVERING
    ALL SURFACES OF COM-
    BUSTIBLE MATERIAL
    WITHIN THE DISTANCE
    SPECIFIED AS THE
    REQUIRED CLEARANCE
    WITH NO PROTECTION|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
    **CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.

  • CMC § 7.3.4 High relevance — show source text

    7.3.4(3)]**|36 (inches)|36 (inches)|18 (inches)|18 (inches)|12 (inches)|12 (inches)|9 (inches)|9 (inches)|6 (inches)|6 (inches)| |TYPE OF PROTECTION APPLIED TO
    AND COVERING ALL SURFACES OF
    COMBUSTIBLE MATERIAL WITHIN
    THE DISTANCE SPECIFIED AS THE
    REQUIRED CLEARANCE WITH NO
    PROTECTION [SEE FIGURE
    509.7.3.4(1) THROUGH FIGURE
    509.7.3.4(3)]|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)|ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (inches)| |TYPE OF PROTECTION APPLIED TO
    AND COVERING ALL SURFACES OF
    COMBUSTIBLE MATERIAL WITHIN
    THE DISTANCE SPECIFIED AS THE
    REQUIRED CLEARANCE WITH NO
    PROTECTION [SEE FIGURE
    509.7.3.4(1) THROUGH FIGURE
    509.7.3.4(3)]|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2
    FOR CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.|**USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR.

  • CMC § 509.1 High relevance — show source text

    509.1 Listing . . . . . . . . . . . . . . . . . . . . . . .91

    509.2 Connection to Venting Systems . . .91

    509.3 Minimum Safe Performance . . . . . .91

    509.4 Type of Venting System to be Used . . . . . . . . . . . . . . . . . . . . .92

    Table 509.4 Type of Venting System to be Used . . . . . . . . . . . . . . . . . . .92

    509.5 Masonry, Metal, and Factory-Built Chimneys . . . . . . . . .93

    509.6 Gas Vents . . . . . . . . . . . . . . . . . . . .94

    Table 509.6.1 Roof Slope Heights . . . . . . . . . . . .95

    509.7 Single-Wall Metal Pipe . . . . . . . . . .97

    Table 509.7.3.4(1) Clearances for Connectors . . . . . . .97

    Table 509.7.3.4(2) Reduction of Clearances with Specified Forms of Protection . . . .99

    509.8 Through-the-Wall Vent Termination . . . . . . . . . . . . . . . . . .100

    509.9 Condensation Drain . . . . . . . . . . .100

    509.10 Vent Connectors for

    Category I Appliances . . . . . . . . .100

    Table 509.8.1 Through-the-Wall Direct-Vent Termination Clearances . . . . . . . .101

    Table 509.10.1.3 Minimum Thickness for

    Galvanized Steel Vent

    Connectors for Low-Heat

    Appliances . . . . . . . . . . . . . . . . . .102

    Table 509.10.1.4 Minimum Thickness for Steel

    Vent Connectors for

    Medium-Heat Appliances . . . . . . .102

    509.11 Vent Connectors for

    Category II, Category III, and Category IV Appliances . . . . . . . .104

    509.12 Appliances Requiring Draft Hoods . . . . . . . . . . . . . . . . . . . . . .104

    509.13 Manually Operated Dampers . . . .104

    509.14 Automatically Operated Vent Dampers . . . . . . . . . . . . . . . .104

    509.15 Obstructions . . . . . . . . . . . . . . . . .104

    510.0 Sizing of Category I Venting Systems . . . . . . . . . . . . . . . . . . . .104

    510.1 Additional Requirements to Single Appliance Vent . . . . . . . . .104

    510.2 Additional Requirements to Multiple-Appliance Vent . . . . . . . . .106

    Table 510.2.1 Vent Connector Maximum

    Length . . . . . . . . . . . . . . . . . . . . . .106

    Table 510.1.2(1) Type B Double-Wall Gas Vent . . .110

    Table 510.1.2(2) Type B Double-Wall Gas Vent . . .113

    Table 510.1.2(3) Masonry Chimney . . . . . . . . . . . . .115

  • CMC § 12.8.5 High relevance — show source text

    (c) Engineering methods.

    (2) Where a single-wall metal pipe is used and has a shape other than round, it shall have an equivalent effective area equal to the effective area of the round pipe for which it is substituted and the minimum internal dimension of the pipe shall be 2 inches (51 mm).

    (3) The vent cap or a roof assembly shall have a venting capacity not less than that of the pipe to which it is attached. [NFPA 54:12.8.5]

    802.7.5 Support of Single-Wall Metal Pipe. All portions of single-wall metal pipe shall be supported for the design and weight of the material employed. [NFPA 54:12.8.6]

    802.7.6 Marking. Single-wall metal pipe shall comply with the marking provisions of Section 802.6.5. [NFPA 54:12.8.7]

    802.8 Through-the-Wall Vent Termination. Throughthe-wall vent termination shall be in accordance with Section

    802.8.1 through Section 802.8.3.

    802.8.1 Clearance for Through-the-Wall Vent Ter- mination. The clearance for through-the-wall direct vent and non-direct vent terminals shall be in accordance with

    Table 802.8.1 and Figure 802.8.1.

    Exception: The clearances in Table 802.8.1 shall not apply to the combustion air intake of a direct vent appliance. [NFPA 54:12.9.1]

    802.8.2 Annular Spaces. Where vents, including those for direct vent appliances or combustion air intake pipes, penetrate outside walls of buildings, the annular spaces around such penetrations shall be permanently sealed using approved materials to prevent entry of combustion products into the building. [NFPA 54:12.9.2]

    802.8.3 Vent Terminals. Vent systems for Category IV appliances that terminate through an outside wall of a building and discharge flue gases perpendicular to the adjacent wall shall be located not less than 10 feet (3048 mm) horizontally from an operable opening in an adjacent building.

    Exception: This shall not apply to vent terminals that are 2 feet (610 mm) or more above or 25 feet (7620 mm) or more below operable openings. [NFPA 54:12.9.3]

    802.9 Condensation Drain. Provision shall be made to

    collect and dispose of condensate from venting systems serving Category II and Category IV appliances and noncategorized condensing appliances. [NFPA 54:12.10.1]

    802.9.1 Installation. Drains for condensate shall be

    installed in accordance with the appliance and vent manufacturers’ installation instructions. [NFPA 54:12.10.2]

    802.10 Vent Connectors for Category I Appliances. A vent connector shall be used to connect an appliance to a gas vent, chimney, or single-wall metal pipe, except where the gas vent, chimney, or single-wall metal pipe is directly connected to the appliance. [NFPA 54:12.11.1]

    802.10.1 Materials. A vent connector shall be made of

    noncombustible, corrosion-resistant material capable of

    «

    «

    |TABLE 802.7.3.3 CLEARANCE FOR CONNECTORS* [NFPA 54: TABLE 12.8.4.

  • CMC § 0.79 High relevance — show source text

    (2) The connectors shall be attached to the vertical portion of the chimney or vent at an angle of 45 degrees (0.79 rad) or less relative to the vertical. [NFPA 54:12.11.4.1]

    509.10.3.1 Height of Connector. Where two or more vent connectors enter a common vent, chimney flue, or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material. [NFPA 54:12.11.4.2]

    509.10.3.2 Pressure. Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or Category IV appliances. [NFPA 54:12.11.4.3]

    509.10.4 Clearance. Minimum clearances from vent

    connectors to combustible material shall be in accordance with Table 509.7.3.4(1).

    Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 509.7.3.4(2). [NFPA 54:12.11.5]

    509.10.5 Joints. Joints between sections of connector piping and connections to flue collars or draft hood outlets shall be fastened in accordance with one of the following methods:

    (1) Mechanically fastened by means of not less than three sheet-metal screws equally spaced around the joint.

    (2) Vent connectors of listed vent material assembled and connected to flue collars or draft hood outlets in

    accordance with the manufacturer’s instructions.

    (3) Other approved means. {NFPA 54:12.11.6}

    509.10.6 Connector Junctions. Where vent connectors are joined together, the connection shall be made with a manufactured tee or wye fitting. [NFPA 54:12.11.7]

    509.10.7 Slope. A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least [1] ⁄ 4 inch per foot (20.8 mm/m).

    Exception: Vent connectors attached to a mechanical draft system installed in accordance with appliance and the draft system manufacturers’ instructions. [NFPA 54:12.11.8]

    509.10.8 Length of Vent Connector. The length of vent connectors shall comply with Section 509.10.8.1 or Section 509.10.8.2.

    509.10.8.1 Single Wall Connector. The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent, except for engineered systems. [NFPA 54:12.11.9.1] 509.10.8.2 Type B Double Wall Connector. The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent, except for engineered systems. The maximum length of an individual connector for a chimney or vent system serving multiple appliances, from the appliance outlet to the junction with the common vent or another connector, shall be 100 percent of the height of the chimney or vent.

    [NFPA 54:12.11.9.2]

  • CMC § 509.7.2 High relevance — show source text

    509.7.2 Termination. The termination of single-wall metal pipe shall meet the following requirements:

    (1) Single-wall metal pipe shall terminate at least 5 feet (1524 mm) in vertical height above the highest connected appliance draft hood outlet or flue collar.

    [NFPA 54:12.8.3(1)]

    (2) Single-wall metal pipe shall extend at least 2 feet (610 mm) above the highest point where it passes through a roof of a building and at least 2 feet (610 mm) higher than any portion of a building within a horizontal distance of 10 feet (3048 mm). [NFPA 54:12.8.3(2)]

    (3) An approved cap or roof assembly shall be attached to the terminus of a single-wall metal pipe. [NFPA 54:12.8.3(3)]

    509.7.3 Installation with Appliances Permitted by Section 509.4. Single-wall metal pipe shall not be used as a vent in dwellings and residential occupancies.

    [NFPA 54:12.8.4.1]

    509.7.3.1 Limitations. Single-wall metal pipe shall be used only for runs directly from the space in

    which the appliance is located through the roof or exterior wall to the outer air. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jacket, or roof thimble. [NFPA 54:12.8.4.2]

    509.7.3.2 Attic or Concealed Space. Singlewall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through any attic, inside wall, concealed space, or floor. [NFPA 54:12.8.4.3]

    509.7.3.3 Incinerator. Single-wall metal pipe used for venting an incinerator shall be exposed and readily examinable for its full length and shall have required clearances maintained.

    509.7.3.4 Clearances. Minimum clearances from single-wall metal pipe to combustible material shall be in accordance with Table 509.7.3.4(1). Reduced clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors in Table 509.7.3.4(2). [NFPA 54:12.8.4.4]

    509.7.3.5 Combustible Exterior Wall. Singlewall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following:

    (1) For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be a minimum of 4 inches (100 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet (1829 mm) of metal pipe in the opening between the draft hood outlet and the thimble, the thimble shall be a minimum of 2 inches (50 mm) larger in diameter than the metal pipe.

    (2) For unlisted appliances having draft hoods, the thimble shall be a minimum of 6 inches (150 mm) larger in diameter than the metal pipe.

    |TABLE 509.7.3.4(1) CLEARANCES FOR CONNECTORS {NFPA 54: TABLE 12.8.4.

  • CMC § 509.7.3.3 High relevance — show source text

    509.7.3.3 Incinerator. Single-wall metal pipe used for venting an incinerator shall be exposed and readily examinable for its full length and shall have required clearances maintained.

    509.7.3.4 Clearances. Minimum clearances from single-wall metal pipe to combustible material shall be in accordance with Table 509.7.3.4(1). Reduced clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors in Table 509.7.3.4(2). [NFPA 54:12.8.4.4]

    509.7.3.5 Combustible Exterior Wall. Singlewall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following:

    (1) For listed appliances with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be a minimum of 4 inches (100 mm) larger in diameter than the metal pipe. Where there is a run of not less than 6 feet (1829 mm) of metal pipe in the opening between the draft hood outlet and the thimble, the thimble shall be a minimum of 2 inches (50 mm) larger in diameter than the metal pipe.

    (2) For unlisted appliances having draft hoods, the thimble shall be a minimum of 6 inches (150 mm) larger in diameter than the metal pipe.

    TABLE 509.7.3.4(1) CLEARANCES FOR CONNECTORS {NFPA 54: TABLE 12.8.4.4}* Col2 Col3 Col4 Col5
    MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches) MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches) MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches) MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches) MINIMUM DISTANCE FROM COMBUSTIBLE MATERIAL (inches)
    APPLIANCE LISTED TYPE B GAS
    VENT MATERIAL
    LISTED TYPE L VENT
    MATERIAL
    SINGLE-WALL METAL
    PIPE
    FACTORY-BUILT
    CHIMNEY SECTIONS
    Listed appliances with draft hoods and appli-
    ances listed for use with Type B gas vents
    As listed As listed 6 As listed
    Residential boilers and furnaces with listed gas
    conversion burner and with draft hood
    6 6 9 As listed
    Residential appliances listed for use with
    Type L vents
    Not permitted As listed 9 As listed
    Unlisted residential appliances with draft hood Not permitted 6 9 As listed
    Residential and low-heat appliances other than
    those above
    Not permitted 9 18 As listed
    Medium-heat appliances Not permitted Not permitted 36 As listed

    For SI units: 1 inch = 25.4 mm

    • These clearances shall apply unless the installation instructions of a listed appliance or connector specify different clearances, in which case the listed clearances shall apply.

    2025 CALIFORNIA PLUMBING CODE 97

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    WATER HEATERS

Frequently asked questions

Can single‑wall metal pipe be used in a house?

No—single‑wall metal pipe is generally not permitted as a vent in dwellings and residential occupancies except where Section § 802.4 specifically allows it; always confirm appliance type and applicable allowances. § 802.7.3 (installation with appliances permitted by § 802.4).

What if my appliance manufacturer gives different clearances?

Follow the listed appliance or connector instructions if they specify different clearances; listed instructions take precedence over the generic table in § 802.7.3.3.

Can I cover nearby combustible walls with metal to reduce clearance?

Potentially—clearance reductions are allowed only when the combustible surfaces are protected by a code‑approved protection system specified for vent connectors. Consult the vent‑connector protection tables and text for allowed methods and dimensions. § 802.7.3.3 and vent connector sections.

Are the clearance numbers absolute or minimums?

They are minimums; larger clearances are acceptable, and listed appliance/connector instructions may require larger clearances. § 802.7.3.3.

Where are the numeric clearances listed?

See Table 802.7.3.3 (the numeric minimum clearances to combustible material) referenced and required by § 802.7.3.3.

More in California Mechanical Code

Ask about the CMC

Get cited, plain-English answers on the California Mechanical Code for your project — any code section, any scenario.

Start Free Trial

Related in the CMC