CHBC · California Historical Building Code
What is the purpose, intent and scope of the CHBC Means of Egress?
If your building is a qualified historical building and the CHBC applies, the CHBC requires that the building be provided with exits under the CHBC and lets the enforcing agency accept reasonably equivalent alternatives to modern egress requirements—but only where those alternatives still provide an adequate means of egress and do not create a life‑safety hazard (see **§ 8-501.1–.3**).
Last reviewed: July 6, 2026
What the code requires — 2-4 sentences
The CHBC establishes minimum means of egress regulations for qualified historical buildings and requires the enforcing agency to accept reasonably equivalent alternatives to the regular code when those alternatives provide equivalent life‑safety outcomes. This is the stated purpose of the chapter in § 8-501.1. The intent is simply to provide an adequate means of egress (see § 8-501.2). The scope is that every qualified historical building (or portion) must be provided with exits under the CHBC when CHBC application is triggered by § 8-102, as stated in § 8-501.3.
If a building is a qualified historical building and the CHBC applies, the building must have exits as required by the CHBC, and the enforcing agency will accept reasonably equivalent solutions that provide equivalent life safety.
Requirements in detail
Core rules (plain language)
- Purpose: Provide minimum egress regulations for qualified historical buildings and allow the enforcing agency to accept alternatives that are reasonably equivalent to the regular code (§ 8-501.1).
- Intent: Ensure an adequate means of egress—the focus is life safety rather than strict historical alteration of every egress component (§ 8-501.2).
- Scope: CHBC egress provisions apply to every qualified historical building or portion thereof when the CHBC is required to be used under § 8-102; that is the trigger for when CHBC egress rules control (§ 8-501.3).
Decision-relevant dimensions (quick reference table)
| Decision dimension | What to check/measure | Typical value / outcome | Code Reference |
|---|---|---|---|
| Applicability (Is CHBC used?) | Has owner/evaluating authority elected CHBC or does project fall under CHBC application rules? | CHBC applies when Section 8-102 requires or the owner elects CHBC solutions | § 8-501.3 — ; § 8-102 — |
| Purpose / allowable flexibility | Can alternatives be proposed vs. strict regular code compliance? | Enforcing agency must accept reasonably equivalent alternatives where appropriate | § 8-501.1 — |
| Safety standard (policy bar) | Is life safety maintained (adequate egress)? | Alternatives are acceptable only when they provide adequate means of egress | § 8-501.2 — |
| When exits are required | Does the CHBC require exits for this building/portion? | Exits required when CHBC application is triggered per § 8-102 | § 8-501.3 — ; § 8-102 — |
| Enforcement discretion | May the enforcing agency grant exceptions where not adverse to life safety? | Enforcing agency grants reasonable exceptions where life safety is not adversely affected | See § 8-502.1 (related) — |
(Every row above is based on the CHBC text cited in the Code Reference column.)
How to use these rules in practice
- First determine whether the building is a qualified historical building and whether CHBC applies under § 8-102. If yes, treat the CHBC egress chapter as the controlling minimum standard (§ 8-501.3).
- If the CHBC applies, the enforcing agency must accept reasonably equivalent alternatives to the regular egress requirements — but only to the extent they still provide an adequate means of egress and do not create a distinct hazard (§ 8-501.1, § 8-501.2).
Exceptions & special cases
- The CHBC does not universally remove egress requirements — it establishes the CHBC as the minimum egress regulatory framework for qualified historical buildings and applies when triggered by § 8-102; if the CHBC is not the applicable standard, regular code may control. See § 8-501.3 and § 8-102.
- The CHBC expressly accommodates reasonably equivalent alternatives rather than requiring strict replication of modern egress geometry; however, alternatives must achieve adequate egress per § 8-501.1 and § 8-501.2.
- Related provisions in the CHBC give enforcing agencies explicit authority to grant reasonable exceptions or allow existing nonconforming openings and stairs where they do not create a distinct hazard (see § 8-502.1, § 8-502.2, § 8-502.3 for those operational examples). While these are not part of § 8-501, they commonly inform how § 8-501 is applied.
Common mistakes
- Assuming the CHBC removes the need for exits: The CHBC provides minimum egress rules and requires exits when CHBC applies — it does not eliminate egress requirements (§ 8-501.3).
- Treating “reasonably equivalent alternatives” as a license to ignore life‑safety: alternatives accepted under the CHBC still must provide an adequate means of egress (§ 8-501.1, § 8-501.2).
- Failing to confirm CHBC applicability: Always confirm whether § 8-102 makes the CHBC the controlling standard for the work in question before applying CHBC egress relaxations.
- Not coordinating with the enforcing agency early: many CHBC allowances depend on the enforcing agency’s acceptance of alternatives — get approval and document the equivalence rationale. See § 8-501.1.
Worked example — concrete scenario with numbers
Scenario: A property owner has a qualified historical boarding house and seeks to use the CHBC for a repair/alteration project. The existing front corridor is 36 inches wide; the current regular code (for new work) would require a larger corridor in that occupancy type, but the owner wants to retain the historic corridor.
Step 1 — Applicability: Because the building is a qualified historical building and the owner elects to use CHBC remedies, the CHBC egress chapter applies per § 8-501.3 (triggered through § 8-102).
Step 2 — Evaluate alternatives: Under § 8-501.1 the enforcing agency must accept reasonably equivalent alternatives; under § 8-501.2 the standard is whether the corridor and overall exiting system still provide an adequate means of egress. If the enforcing agency determines the 36‑inch corridor still allows occupants to exit safely for the building’s occupant load, it may accept that alternative.
Step 3 — Document and obtain approval: The owner should document occupant loads, egress distances, and any compensating measures (e.g., improved signage, emergency lighting), submit the equivalence justification to the enforcing agency, and obtain written acceptance before final approval — consistent with the CHBC approach to alternatives (§ 8-501.1).
(Notes: this example illustrates the decision process required by § 8-501.1–.3. Specific numeric minimums for corridor widths are set by the regular code; the CHBC allows the enforcing agency to accept equivalent solutions.)
Related provisions
- § 8-102 — Application (triggers when CHBC applies).
- § 8-502.1 — General: enforcing agency to grant reasonable exceptions where life safety is not adversely affected.
- § 8-502.2 — Existing openings and corridor widths: allowed where sufficient width/height exists.
- § 8-503 — Escape or rescue windows and doors (related egress openings).
- § 8-504 — Railings and guardrails (addresses related egress safety elements).
Code references
Grounded in the retrieved California Historical Building Code — click a citation to read the verbatim passage:
CHBC § 8-410.3 High relevance — show source text
Buildings with floors above 75 feet, NFPA 13.
When the building is free standing or with property line separation, two floors and 1500 square feet per floor or less, NFPA 13D.
For exterior wall and opening protection. As required by this chapter.
Exception: When the automatic sprinkler systems are used to reach compliance using this code, in three or more occasions, NFPA 13D standard shall be increased to NFPA 13R standard, or NFPA 13R standard shall be increased to a NFPA 13 standard.
8-410.3 Automatic sprinkler systems shall not be used to substitute for or act as an alternate to the required number of exits from any facility. (See Chapter 8-5 for exiting requirements.)
8-410.4 An automatic sprinkler system shall be provided in all detention facilities.
SECTION 8-411 — OTHER TECHNOLOGIES
Fire alarm systems, smoke and heat detection systems, occupant notification and annunciation systems, smoke control systems and fire modeling, timed egress analysis and modeling, as well as other engineering methods and technologies may be accepted by the enforcing agency to address areas of nonconformance.
SECTION 8-412 — HIGH-RISE BUILDINGS
Qualified historical buildings having floors for human occupancy located more than 75 feet above the lowest floor level having building access shall conform to the provisions of the regular code for existing high-rise buildings as amended by the CHBC.
8 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-5 MEANS OF EGRESS
SECTION 8-501 — PURPOSE, INTENT AND SCOPE
8-501.1 Purpose. The purpose of this chapter is to establish minimum means of egress regulations for qualified historical buildings or properties. The CHBC requires enforcing agencies to accept reasonably equivalent alternatives to the means of egress requirements in the regular code.
8-501.2 Intent. The intent of these regulations is to provide an adequate means of egress.
8-501.3 Scope. Every qualified historical building or portion thereof shall be provided with exits as required by the CHBC when required by the provisions of Section 8-102.
SECTION 8-502 — GENERAL
8-502.1 General. The enforcing agency shall grant reasonable exceptions to the specific provisions of applicable egress regulations where such exceptions will not adversely affect life safety.
8-502.2. Existing door openings and corridor widths of less than dimensions required by regular code shall be permitted where there is sufficient width and height for the occupants to pass through the opening or traverse the exit.
8-502.3 Stairs. Existing stairs having risers and treads or width at variance with the regular code are allowed if determined by the enforcing agency to not constitute a distinct hazard. Handrails with nonconforming grip size or extensions are allowed if determined by the enforcing agency to not constitute a distinct hazard.
8-502.4 Main entry doors. The front or main entry doors need not be rehung to swing in the direction of exit travel, provided other means or conditions of exiting, as necessary to serve the total occupant load, are provided.
CHBC § 8-5 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-5 MEANS OF EGRESS
SECTION 8-501 — PURPOSE, INTENT AND SCOPE
8-501.1 Purpose. The purpose of this chapter is to establish minimum means of egress regulations for qualified historical buildings or properties. The CHBC requires enforcing agencies to accept reasonably equivalent alternatives to the means of egress requirements in the regular code.
8-501.2 Intent. The intent of these regulations is to provide an adequate means of egress.
8-501.3 Scope. Every qualified historical building or portion thereof shall be provided with exits as required by the CHBC when required by the provisions of Section 8-102.
SECTION 8-502 — GENERAL
8-502.1 General. The enforcing agency shall grant reasonable exceptions to the specific provisions of applicable egress regulations where such exceptions will not adversely affect life safety.
8-502.2. Existing door openings and corridor widths of less than dimensions required by regular code shall be permitted where there is sufficient width and height for the occupants to pass through the opening or traverse the exit.
8-502.3 Stairs. Existing stairs having risers and treads or width at variance with the regular code are allowed if determined by the enforcing agency to not constitute a distinct hazard. Handrails with nonconforming grip size or extensions are allowed if determined by the enforcing agency to not constitute a distinct hazard.
8-502.4 Main entry doors. The front or main entry doors need not be rehung to swing in the direction of exit travel, provided other means or conditions of exiting, as necessary to serve the total occupant load, are provided.
8-502.5 Existing fire escapes. Existing previously approved fire escapes and fire escape ladders shall be acceptable as one of the required means of egress, provided they extend to the ground and are easily negotiated, adequately signed and in good working order. Access shall be by an opening having a minimum width of 29 inches (737 mm) when open with a sill no more than 30 inches (762 mm) above the adjacent floor, landing or approved step.
8-502.6 New fire escapes and fire escape ladders. New fire escapes and fire escape ladders which comply with this section shall be acceptable as one of the required means of egress. New fire escapes and new fire escape ladders shall comply with the following:
- Access from a corridor shall not be through an intervening room.
- All openings within 10 feet (3048 mm) shall be protected by three-fourths-hour fire assemblies. When located within a recess or vestibule, adjacent enclosure walls shall be of not less than one-hour fire-resistive construction.
- Egress from the building shall be by a clear opening having a minimum dimension of not less than 29 inches (737 mm). Such openings shall be openable from the inside without the use of a key or special knowledge or effort. The sill of an opening giving access shall not be more than 30 inches (737 mm) above the floor, step or landing of the building or balcony.
- Fire escape stairways and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot (4.79 kN/m [2] ) and shall be provided with a top and intermediate handrail on each side. The pitch of the stairway shall not exceed 72 degrees with a minimum width of 18 inches (457 mm).
CHBC § 8-503 High relevance — show source text
2025 CALIFORNIA HISTORICAL BUILDING CODE 9
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
SECTION 8-503 — ESCAPE OR RESCUE WINDOWS AND DOORS
Basements in dwelling units and every sleeping room below the fourth floor shall have at least one openable window or door approved for emergency escape which shall open directly into a public street, public way, yard or exit court. Escape or rescue windows or doors shall have a minimum clear area of 3.3 square feet (0.31 m [2] ) and a minimum width or height dimension of 18 inches (457 mm) and be operable from the inside to provide a full, clear opening without the use of special tools.
SECTION 8-504 — RAILINGS AND GUARDRAILS
The height of railings and guard railings and the spacing of balusters may continue in their historical height and spacing unless a distinct hazard has been identified or created by a change in use or occupancy.
10 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-6 ACCESSIBILITY
SECTION 8-601 — PURPOSE, INTENT AND SCOPE
8-601.1 Purpose. The purpose of the CHBC is to provide alternative regulations to facilitate access and use by persons with disabilities to and throughout facilities designated as qualified historical buildings or properties. These regulations require enforcing agencies to accept alternatives to regular code when dealing with qualified historical buildings or properties.
8-601.2 Intent. The intent of this chapter is to preserve the integrity of qualified historical buildings and properties while providing access to and use by persons with disabilities.
8-601.3 Scope. The CHBC shall apply to every qualified historical building or property that is required to provide access to persons with disabilities.
- Provisions of this chapter do not apply to new construction or reconstruction/replicas of historical buildings.
- Where provisions of this chapter apply to alteration of qualified historical buildings or properties, alteration is defined in California Building Code (CBC), Chapter 2.
8-601.4 General application. The provisions in the CHBC apply to local, state and federal governments (Title II entities); alteration of commercial facilities and places of public accommodation (Title III entities); and barrier removal in commercial facilities and places of public accommodation (Title III entities). Except as noted in this chapter.
SECTION 8-602 — BASIC PROVISIONS
8-602.1 Regular code. The regular code for access for people with disabilities (Title 24, Part 2, Vol. 1, Chapter 11B) shall be applied to qualified historical buildings or properties unless strict compliance with the regular code will threaten or destroy the historical significance or character-defining features of the building or property.
8-602.2 Alternative provisions. If the historical significance or character-defining features are threatened, alternative provisions for access may be applied pursuant to this chapter, provided the following conditions are met:
- These provisions shall be applied only on an item-by-item or a case-by-case basis.
- Documentation is provided, including meeting minutes or letters, stating the reasons for the application of the alternative provisions. Such documentation shall be retained in the permanent file of the enforcing agency.
SECTION 8-603 — ALTERNATIVES
CHBC § 8-801 High relevance — show source text
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.
8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.
SECTION 8-802 — GENERAL ENGINEERING APPROACHES
Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.
SECTION 8-803 — NONSTRUCTURAL ARCHAIC MATERIALS
Where nonstructural historical materials exist in uses which do not meet the requirements of the regular code, their continued use is allowed by this code, provided that any public health and life safety hazards are mitigated subject to the concurrence of the enforcing agency.
SECTION 8-804 — ALLOWABLE CONDITIONS FOR SPECIFIC MATERIALS
Archaic materials which exist and are to remain in qualified historical buildings or structures shall be evaluated for their condition and for loads required by this code. The structural survey required in Section 8-703 of the CHBC shall document existing conditions, reinforcement, anchorage, deterioration and other factors pertinent to establishing allowable stresses, strength levels and adequacy of the archaic materials. The remaining portion of this chapter provides additional specific requirements for commonly encountered archaic materials.
SECTION 8-805 — MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls of any type, except adobe, may be allowed, without testing, a maximum ultimate strength of 9 pounds per square inch (62.1 kPa) in shear where there is a qualifying statement by the architect or engineer that an inspection has been made, that mortar joints are filled and that both brick and mortar are reasonably good. The shear stress above applies to unreinforced masonry, except adobe, where the maximum ratio of unsupported height or length to thickness does not exceed 13, and where minimum quality mortar is used or exists. Wall height or length is measured to supporting or resisting elements that are at least twice as stiff as the tributary wall. Stiffness is based on the gross section. Shear stress may be increased by the addition of 10 percent of the axial direct stress due to the weight of the wall directly above.
CHBC § 12.7 High relevance — show source text
Values are for strength level loads as defined in regular code standards.
2. Values may be adjusted for other fasteners when approved by the enforcing authority.
3. In addition to existing sheathing value.
4. Bolts to be1/2-inch (12.7 mm) minimum diameter.
5. Other bolt sizes, values and installation methods may be used provided a testing program is conducted in accordance with regular code standards. Bolt spacing shall not
exceed 6 feet (1830 mm) on center and shall not be less than 12 inches (305 mm) on center.
6. Other masonry based on tests or other substantiated data.
7. Embedded bolts to be tested as specified in regular code standards.
8. Stresses given may be increased for combinations of loads as specified in the regular code.
9. Adhesives shall be approved by the enforcing agency and installed in accordance with the manufacturer’s recommendations. All drilling dust shall be removed from drilled
holes prior to installation.|1. Values are for strength level loads as defined in regular code standards.
2. Values may be adjusted for other fasteners when approved by the enforcing authority.
3. In addition to existing sheathing value.
4. Bolts to be1/2-inch (12.7 mm) minimum diameter.
5. Other bolt sizes, values and installation methods may be used provided a testing program is conducted in accordance with regular code standards. Bolt spacing shall not
exceed 6 feet (1830 mm) on center and shall not be less than 12 inches (305 mm) on center.
6. Other masonry based on tests or other substantiated data.
7. Embedded bolts to be tested as specified in regular code standards.
8. Stresses given may be increased for combinations of loads as specified in the regular code.
9. Adhesives shall be approved by the enforcing agency and installed in accordance with the manufacturer’s recommendations. All drilling dust shall be removed from drilled
holes prior to installation.|18 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-9 MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
SECTION 8-901 — PURPOSE, INTENT AND SCOPE
8-901.1 Purpose. The purpose of the CHBC is to provide regulations for the mechanical, plumbing and electrical systems of buildings designated as qualified historical buildings or properties. The CHBC requires enforcing agencies to accept any reasonable equivalent solutions to the regular code when dealing with qualified historical buildings or properties.
8-901.2 Intent. The intent of the CHBC is to preserve the integrity of qualified historical buildings or properties while providing a reasonable level of protection from fire, health and life safety hazards (hereinafter referred to as safety hazards) for the building occupants.
8-901.3 Scope. The CHBC shall be applied in conjunction with the regular code whenever compliance with the regular code is required for qualified historical buildings or properties.
CHBC § 8-6 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A Col2 Col3 Col4 CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY Title II
Public EntitiesTitle III
Private EntitiesTitle III
Barrier RemovalSECTION 8-601 PURPOSE, INTENT, SCOPE
**8-601.1 Purpose.**The purpose of the CHBC is to provide alternative regulations to facilitate
access and use by persons with disabilities to and throughout facilities designated as quali-
fied historical buildings or properties. These regulations require enforcing agencies to
accept alternatives to regular code when dealing with qualified historical buildings or
properties.
**8-601.2 Intent.**The intent of this chapter is to preserve the integrity of qualified historical
buildings and properties while providing access to and use by persons with disabilities.
**8-601.3 Scope.**The CHBC shall apply to every qualified historical building or property that
is required to provide access to persons with disabilities.
1.Provisions of this chapter do not apply to new construction or reconstruction/replicas of
historical buildings.
2. Where provisions of this chapter apply to alteration of qualified historical buildings or
properties, alteration is defined in_ California Building Code_ (CBC), Chapter 2.
8-601.4 General application. The provisions in the CHBC apply to local, state and federal
governments (Title II entities); alteration of commercial facilities and places of public
accommodation (Title III entities); and barrier removal in commercial facilities and places of
public accommodation (Title III entities). Except as noted in this chapter.Applies Applies Applies SECTION 8-602 — BASIC PROVISIONS
8-602.1 Regular code. The regular code for access for people with disabilities (Title 24, Part
2, Vol.1, Chapter 11B) shall be applied to qualified historical buildings or properties unless
strict compliance with the regular code will threaten or destroy the historical significance or
character-defining features of the building or property.
**8-602.2 Alternative provisions.**If the historical significance or character-defining features
are threatened, alternative provisions for access may be applied pursuant to this chapter,
provided the following conditions are met:
1.These provisions shall be applied only on an item-by-item or case-by-case basis.
2.Documentation is provided, including meeting minutes or letters, stating the reasons
for the application of the alternative provisions. Such documentation shall be retained
in the permanent file of the enforcing agency.Applies Applies Applies Section 8-603 — ALTERNATIVES
**8-603.1 Alternative minimum standards.**The alternative minimum standards for alter-
ations of qualified historical buildings or facilities are referenced in Section 202.5 of the_ 2010_
ADA Standards for Accessible Design, as incorporated and set forth in federal regulation 28
CFR Pt. 36.
**8-603.2 Entry.CHBC § 8-1002.1 High relevance — show source text
8-1002.1 The CHBC shall apply to all sites and districts and their features associated with qualified historical buildings or qualified historical districts as outlined in 8-1001.2 Scope.
8-1002.2 Where the application of regular code may impact the associated features of qualified historical properties beyond their footprints, by work performed secondarily, those impacts shall also be covered by the CHBC.
8-1002.3 This chapter shall be applied for all issues regarding code compliance or other standard or regulation as they affect the purpose of this chapter.
8-1002.4 The application of any code or building standard shall not unduly restrict the use of a qualified historical building or property that is otherwise permitted pursuant to Chapter 8-3 and the intent of the State Historical Building Code, Section 18956.
SECTION 8-1003 — SITE RELATIONS
The relationship between a building or property and its site, or the associated features of a district (including qualified historical landscape), site, objects and their features are critical components that may be one of the criteria for these buildings and properties to be qualified under the CHBC. The CHBC recognizes the importance of these relationships. This chapter shall be used to provide context sensitive solutions for treatment of qualified historical buildings, properties, district or their associated historical features, or when work to be performed secondarily impacts the associated historical features of a qualified historical building or property.
2025 CALIFORNIA HISTORICAL BUILDING CODE 23
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
24 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A Col2 Col3 Col4 CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY CHAPTER 8-6—TABLE 1—PROVISION APPLICABILITY Title II
Public EntitiesTitle III
Private EntitiesTitle III
Barrier RemovalSECTION 8-601 PURPOSE, INTENT, SCOPE
**8-601.1 Purpose.**The purpose of the CHBC is to provide alternative regulations to facilitate
access and use by persons with disabilities to and throughout facilities designated as quali-
fied historical buildings or properties. These regulations require enforcing agencies to
accept alternatives to regular code when dealing with qualified historical buildings or
properties.
**8-601.2 Intent.**The intent of this chapter is to preserve the integrity of qualified historical
buildings and properties while providing access to and use by persons with disabilities.
**8-601.3 Scope.**The CHBC shall apply to every qualified historical building or property that
is required to provide access to persons with disabilities.
1.Provisions of this chapter do not apply to new construction or reconstruction/replicas of
historical buildings.
2. Where provisions of this chapter apply to alteration of qualified historical buildings or
properties, alteration is defined in_ California Building Code_ (CBC), Chapter 2.
**8-601.4 General application.CHBC § 8-1001 High relevance — show source text
Section
8-1001 Purpose and Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 8-1002 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 8-1003 Site Relations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
APPENDIX A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
HISTORY NOTE APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2025 CALIFORNIA HISTORICAL BUILDING CODE ix
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
x 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-1 ADMINISTRATION
Note: The California Historical Building Code, Part 8 of Title 24, governs for all qualified historical buildings or properties in the State of California.
SECTION 8-101 — TITLE, PURPOSE AND INTENT
8-101.1 Title. These regulations shall be known as the California Historical Building Code and will be referred to herein as “the CHBC.”
8-101.2 Purpose. The purpose of the CHBC is to provide regulations for the preservation, restoration, rehabilitation, relocation or reconstruction of buildings or properties designated as qualified historical buildings or properties (as defined in Chapter 8-2). The CHBC is intended to provide solutions for the preservation of qualified historical buildings or properties, to promote sustainability, to provide access for persons with disabilities, to provide a cost-effective approach to preservation, and to provide for the reasonable safety of the occupants or users. The CHBC requires enforcing agencies to accept solutions that are reasonably equivalent to the regular code (as defined in Chapter 8-2) when dealing with qualified historical buildings or properties.
8-101.3 Intent. The intent of the CHBC is to facilitate the preservation and continuing use of qualified historical buildings or properties while providing reasonable safety for the building occupants and access for persons with disabilities.
SECTION 8-102 — APPLICATION
8-102.1 Application. The CHBC is applicable to all issues regarding code compliance for qualified historical buildings or properties. The CHBC may be used in conjunction with the regular code to provide solutions to facilitate the preservation of qualified historical buildings or properties. The CHBC shall be used by any agency with jurisdiction and whenever compliance with the code is required for qualified historical buildings or properties.
- State or local enforcing agency. The state or local enforcing agency shall apply the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, reconstruction, rehabilitation, relocation or continued use of a qualified historical building or property when so elected by the private property owner.
- **State agencies.
CHBC § 8-3 High relevance — show source text
TREATMENT. An act of work to carry out preservation, restoration, stabilization, rehabilitation or reconstruction.
4 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-3 USE AND OCCUPANCY
SECTION 8-301 — PURPOSE AND SCOPE
8-301.1 Purpose. The purpose of the CHBC is to provide regulations for the determination of occupancy classifications and conditions of use for qualified historical buildings or properties.
8-301.2 Scope. Every qualified historical building or property for which a permit or approval has been requested shall be classified prior to permit issuance according to its use or the character of its occupancy in accordance with the regular code and applicable provisions of this chapter.
SECTION 8-302 — GENERAL
8-302.1 Existing use. The use or character of occupancy of a qualified historical building or property, or portion thereof, shall be permitted to continue in use regardless of any period of time in which it may have remained unoccupied or in other uses, provided such building or property otherwise conforms to all applicable requirements of the CHBC.
8-302.2 Change in occupancy. The use or character of the occupancy of a qualified historical building or property may be changed from or returned to its historical use or character, provided the qualified historical building or property conforms to the requirements applicable to the new use or character of occupancy as set forth in the CHBC. Such change in occupancy shall not mandate conformance with new construction requirements as set forth in regular code.
8-302.3 Occupancy separations. Required occupancy separations of more than one hour may be reduced to one-hour fire-resistive construction with all openings protected by not less than three-fourths-hour fire-resistive assemblies of the self-closing or automatic-closing type when the building is provided with an automatic sprinkler system throughout the entire building in accordance with Section 8-410.2. Doors equipped with automatic-closing devices shall be of a type which will function upon activation of a device which responds to products of combustion other than heat.
Required occupancy separations of one hour may be omitted when the building is provided with an automatic sprinkler system throughout.
8-302.4 Maximum floor area. Regardless of the use or character of occupancy, the area of a one-story qualified historical building or property may have, but shall not exceed, a floor area of 15,000 square feet (1393.5 m [2] ) unless such an increase is otherwise permitted in regular code. Multistory qualified historical buildings (including basements and cellars) shall be in accordance with regular code requirements.
Exception: Historical buildings may be unlimited in floor area without fire-resistive area separation walls:
- When provided with an automatic sprinkler, or
- Residential occupancies of two stories or less when provided with a complete fire alarm and annunciation system and where the exiting system conforms to regular code.
8-302.5 Maximum height. The maximum height and number of stories of a qualified historical building or property shall not be limited because of construction type, provided such height or number of stories does not exceed that of its historical design.
CHBC § 33.3 High relevance — show source text
Stairway openings in such balconies shall not be less than 22 inches by 44 inches (559 by 1118 mm). The balustrade of each balcony shall not be less than 36 inches (914 mm) high with not more than 9 inches (287 mm) between balusters. 6. Fire escapes shall extend to the roof or provide an approved gooseneck ladder between the top floor landing and the roof when serving buildings four or more stories in height having roofs with less than 4 units vertical in 12 units horizontal (33.3 percent slope). Fire escape ladders shall be designed and connected to the building to withstand a horizontal force of 100 pounds (445 N) placed anywhere on the rung. All ladders shall be at least 15 inches (381 mm) wide, located within 12 inches (305 mm) of the building. Ladder rungs shall be [3] / 4 inch (19.1 mm) in diameter and shall be located 12 inches (305 mm) on center. Openings for roof access ladders through cornices and similar projections shall have minimum dimensions of 30 inches by 33 inches (762 by 838 mm). The length of fire escapes and exit ladder devices shall be limited to that approved by the building official based on products listed by a recognized testing laboratory. 7. The lowest balcony shall not be more than 18 feet (5486 mm) from the ground. Fire escapes shall extend to the ground or be provided with counterbalanced stairs reaching to the ground. 8. Fire escapes shall not take the place of stairways required by the codes under which the building was constructed. 9. Fire escapes shall be kept clear and unobstructed at all times and maintained in good working order.
2025 CALIFORNIA HISTORICAL BUILDING CODE 9
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MEANS OF EGRESS
SECTION 8-503 — ESCAPE OR RESCUE WINDOWS AND DOORS
Basements in dwelling units and every sleeping room below the fourth floor shall have at least one openable window or door approved for emergency escape which shall open directly into a public street, public way, yard or exit court. Escape or rescue windows or doors shall have a minimum clear area of 3.3 square feet (0.31 m [2] ) and a minimum width or height dimension of 18 inches (457 mm) and be operable from the inside to provide a full, clear opening without the use of special tools.
SECTION 8-504 — RAILINGS AND GUARDRAILS
The height of railings and guard railings and the spacing of balusters may continue in their historical height and spacing unless a distinct hazard has been identified or created by a change in use or occupancy.
10 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-6 ACCESSIBILITY
SECTION 8-601 — PURPOSE, INTENT AND SCOPE
8-601.1 Purpose. The purpose of the CHBC is to provide alternative regulations to facilitate access and use by persons with disabilities to and throughout facilities designated as qualified historical buildings or properties. These regulations require enforcing agencies to accept alternatives to regular code when dealing with qualified historical buildings or properties.
CHBC § 3.8 High relevance — show source text
3.8||||X|X|||||X|X|X|X|X|X|X||||||||| |110.3.10 – 110.3.11|||X|X|X|||||X|X|X|X|X|X|X||||||||| |110.3.12 – 110.3.12.1||||X|X|||||||||||||||||||| |110.3.12.2||||X|X|||||||||||||||||||| |110.4 – 110.6|||X|||||||X|X|X|X|X|X|X||||||||| |111 – 112|||X|||||||X|X|X|X|X|X|X||||||||| |113||||||||||X|X|X|X|X|X|X||||||||| |114.1 – 114.2|||X|||||||X|X|X|X|X|X|X||||||||| |114.3||||||||||X|X|X|X|X|X|X||||||||| |115 – 116|||X|||||||X|X|X|X|X|X|X|||||||||
The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
1-2 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
1 ADMINISTRATION
DIVISION I CALIFORNIA ADMINISTRATION
SECTION 1.1—GENERAL
1.1.1 Title. These regulations shall be known as the California Building Code, may be cited as such and will be referred to herein as “this code.” The California Building Code is Part 2 of thirteen parts of the official compilation and publication of the adoption, amendment and repeal of building regulations to the California Code of Regulations, Title 24, also referred to as the California Building Standards Code. This part incorporates by adoption the 2024 International Building Code of the International Code Council with necessary Califor- nia amendments.
1.1.2 Purpose. The purpose of this code is to establish the minimum requirements to safeguard the public health, safety and general welfare through structural strength, means of egress facilities, stability, access to persons with disabilities, sanitation, adequate lighting and ventilation and energy conservation; safety to life and property from fire and other hazards attributed to the built environment; and to provide safety to firefighters and emergency responders during emergency operations.
1.1.3 Scope. The provisions of this code shall apply to the construction, alteration, movement, enlargement, replacement, repair, equip- ment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures throughout the State of California.
1.1.3.1 Nonstate-regulated buildings, structures and applications. Except as modified by local ordinance pursuant to Section 1.1.8, the following standards in the California Code of Regulations, Title 24, Parts 2, 2.5, 3, 4, 5, 6, 7, 9, 10 and 11 shall apply to all occupancies and applications not regulated by a state agency.
CHBC § 8-408 High relevance — show source text
8-408 Roof Covering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 8-409 Fire Alarm Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8-410 Automatic Sprinkler Systems. . . . . . . . . . . . . . . . . . . . . 8 8-411 Other Technologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 8-412 High-rise Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
CHAPTER 8-5 MEANS OF EGRESS . . . . . . . . . . . . . . . . . . . . . . 9
Section
8-501 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . . 9 8-502 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8-503 Escape or Rescue Windows and Doors. . . . . . . . . . . . 10 8-504 Railings and Guardrails . . . . . . . . . . . . . . . . . . . . . . . . . 10
CHAPTER 8-6 ACCESSIBILITY . . . . . . . . . . . . . . . . . . . . . . . . 11
Section
8-601 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 11
8-602 Basic Provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-603 Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8-604 Equivalent Facilitation. . . . . . . . . . . . . . . . . . . . . . . . . . 12
CHAPTER 8-7 STRUCTURAL REGULATIONS. . . . . . . . . . . . . 13
Section
8-701 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 13 8-702 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8-703 Structural Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-704 Nonhistorical Additions and
Nonhistorical Alterations . . . . . . . . . . . . . . . . . . . . . . . 13
Frequently asked questions
Who decides whether the CHBC applies to my project?
The CHBC applies when the project involves a qualified historical building and the CHBC is elected or required under § 8-102; the enforcing agency confirms applicability.
Does the CHBC let me keep narrow historic corridors and doors?
Possibly — the CHBC requires adequate means of egress and allows the enforcing agency to accept reasonably equivalent alternatives under § 8-501.1 if life safety is maintained. Consult the enforcing agency and document equivalence.
If I accept CHBC solutions, do I ever need to meet regular code egress dimensions?
Not automatically. The CHBC sets minimum egress rules for qualified historical buildings and permits reasonably equivalent solutions; however, some projects (or additions) may still need regular code compliance per § 8-102.
What is the controlling standard — life safety or historic preservation?
Both: the CHBC balances preservation and safety by allowing alternatives that preserve historical features so long as they provide an adequate means of egress and do not create distinct hazards. See § 8-501.1 and § 8-501.2.
Should I get written approval from the enforcing agency for alternatives?
Yes — because the CHBC’s flexibility depends on the enforcing agency accepting reasonably equivalent alternatives, obtain written acceptance and keep the documentation.
More in California Historical Building Code
Ask about the CHBC
Get cited, plain-English answers on the California Historical Building Code for your project — any code section, any scenario.
Start Free Trial