CFC · California Fire Code

Retrofit limits and additional requirements for existing Group I-2 (health-care)

If you’re retrofitting an existing health‑care area (Group I‑2, Condition 2), the California Fire Code caps what building floor levels you can place that use on based on the building’s type of construction — check **§ 1105.3** and **Table 1105.3** (and the table’s notes) to find the highest allowed floor, and remember you must still comply with §§ 1103 and 1104; the most restrictive rule controls.

Last reviewed: July 6, 2026

What the code requires — 2-4 sentences

Existing Group I-2 occupancies must meet the minimum fire-safety rules in § 1103, the means-of-egress rules in § 1104, and the additional egress/construction requirements of § 1105. The retrofit placement limit for Group I-2, Condition 2 is a floor‑level cap: Group I-2, Condition 2 shall not be located on a floor level higher than the floor level limitation in Table 1105.3 (see § 1105.3 and Table 1105.3) and the applicability statement in § 1105.2 controls which parts of Chapter 11 apply.

The single most important rule: Existing Group I-2, Condition 2 occupancies cannot be placed above the maximum floor level shown for their construction type in Table 1105.3 — check § 1105.3 and the table before planning a retrofit.

Requirements in detail

Scope and general rule

  • Per § 1105.1, existing Group I-2 must also comply with the minimum provisions in § 1103 and § 1104, and with the additional requirements in this Section (Chapter 11). Where Chapter 11 conflicts with the construction rules that applied at the time of original construction, the more restrictive requirement applies. § 1105.1 is the general anchor for applying the retrofit limits.

  • Applicability: § 1105.2 states that Sections 1105.3 through 1105.8, plus 1105.10 and 1105.11, apply to the existing Group I-2 fire area — i.e., these are the specific retrofit/alteration requirements to consult.

Floor‑level limitation (the operative rule)

  • § 1105.3: “Group I-2, Condition 2 shall not be located on a floor level higher than the floor level limitation in Table 1105.3 based on the type of construction.” The table (Table 1105.3) is the decision document that determines the highest floor level where Condition 2 is permitted.

Decision‑relevant table (quick reference)

The following condensed table translates the P/NP entries from Table 1105.3 into the highest allowed floor level for Group I-2, Condition 2 for each construction type and the two table note variants shown in the retrieved excerpt (the table references “Note b” and “Note c”; the full note text is not present in the retrieved extract — see the caveat below). Code reference: Table 1105.3 and § 1105.3.

Construction type Table note (as shown) Highest permitted floor level (based on P/NP in Table 1105.3) Code reference
IA Note b 4 or more (P at 1–4+) Table 1105.3; § 1105.3
IA Note c 4 or more Table 1105.3; § 1105.3
IB Note b 4 or more Table 1105.3; § 1105.3
IB Note c 4 or more Table 1105.3; § 1105.3
IIA Note b 3 Table 1105.3; § 1105.3
IIA Note c 1 Table 1105.3; § 1105.3
IIB Note b 2 Table 1105.3; § 1105.3
IIB Note c None permitted Table 1105.3; § 1105.3
IIIA Note b 2 Table 1105.3; § 1105.3
IIIA Note c 1 Table 1105.3; § 1105.3
IIIB Note b 1 Table 1105.3; § 1105.3
IIIB Note c None permitted Table 1105.3; § 1105.3
IV Note b 2 Table 1105.3; § 1105.3
IV Note c None permitted Table 1105.3; § 1105.3
VA Note b 2 Table 1105.3; § 1105.3
VA Note c None permitted Table 1105.3; § 1105.3
VB Note b 1 Table 1105.3; § 1105.3
VB Note c None permitted Table 1105.3; § 1105.3

Notes about the table:

  • The retrieved file shows the table entries and marks “P = Permitted; NP = Not Permitted” but the full text of the table footnotes (for example, what precisely “Note b” and “Note c” require) is not included in the snippet returned by the file search. Do not assume the meaning of the notes without consulting the full code text.

Interaction with other requirements

  • The retrofit floor‑level limit is one constraint; retrofits must also satisfy the minimum fire‑safety requirements in § 1103 and means‑of‑egress requirements in § 1104 (these are explicitly required by § 1105.1). If the building’s original construction rules were stricter, the more restrictive rule controls.

Exceptions & special cases

  • The extracted material shows that Table 1105.3 uses footnotes (e.g., “Note b”, “Note c”) to qualify the permitted/ non‑permitted entries. The text of those notes is not present in the retrieved snippet; therefore the exact qualifying conditions (commonly things like presence/coverage of an automatic sprinkler system, or other special features) are not confirmed here. You must consult the full Table 1105.3 footnotes in the adopted CFC to determine which note applies to your project.

  • Applicability to Condition 2: the table and several rows are explicitly tied to Group I-2, Condition 2 (this condition may be defined or limited by adopting ordinance/legislation). The file excerpts include an explanatory footnote that the requirements “Only applies to Group I-2, Condition 2 occupancies as established by the adopting ordinance or legislation of the jurisdiction.” Confirm local adopting language before applying the table.

  • The Chapter directs that Sections 1105.31105.8, 1105.10, 1105.11 apply to the existing I-2 fire area; other subsections in Chapter 11 may add further specific retrofit obligations not reproduced in the retrieved excerpt.

(If you want, I can retrieve the missing table footnotes and the full text of § 1105.3 and adjacent subsections from your uploaded code file so we can resolve the Note b / Note c definitions exactly.)

Common mistakes

  • Assuming “P” entries apply without checking the table footnotes — the notes can change applicability (the retrieved text shows Note b/Note c but not their definitions).
  • Misclassifying the building’s type of construction (IA, IIB, IIIA, etc.). The floor‑level cap follows that construction type — get a verified construction‑type classification before applying Table 1105.3.
  • Forgetting to apply § 1105.1’s directive to also comply with § 1103 and § 1104; floor level permission does not waive fire‑safety or egress requirements.
  • Overlooking local adoption language: the table’s application to “Condition 2” may depend on local ordinances or legislation.

Worked example — concrete scenario

Scenario: an existing health‑care unit is classified as Group I-2, Condition 2 and the building is Type IIA construction.

  • Check Table 1105.3 entries for IIA:
    • Under the table row for IIA with Note b, the table entries are P, P, P, NP for floor levels 1, 2, 3, 4+ respectively — so the highest permitted floor level is 3.
    • Under Note c the row shows P, NP, NP, NP — highest permitted floor level is 1.

Application:

  • If the project meets the condition associated with Note b (see the full code for the note text), you may place the I-2 Condition 2 unit up to Level 3.
  • If the project falls under Note c, you are limited to Level 1 only.
  • In all cases you must still comply with § 1103 and § 1104, and apply the most‑restrictive rule where earlier construction rules are stricter, per § 1105.1.

Because the full note text isn’t in the retrieved snippet, do not use Note b / Note c conclusions until you confirm the note definitions in the full code (I can fetch and quote those footnotes if you want).

Related provisions

  • § 1105.1 — General requirements for existing Group I-2 (anchors requirement to § 1103 and § 1104).
  • § 1105.2 — Applicability of Sections 1105.3–1105.8, 1105.10 and 1105.11 to existing Group I-2 fire areas.
  • § 1105.3 — Construction: directs use of Table 1105.3 for floor level limitations.
  • Table 1105.3 — Floor level limitations for Group I-2, Condition 2 (P/NP entries and table notes).
  • For retrofit design coordination: see also the minimum fire safety and egress chapters referenced by § 1105.1§ 1103 and § 1104.

Code references

Grounded in the retrieved California Fire Code — click a citation to read the verbatim passage:

  • CFC § 1104.24 High relevance — show source text

    1104.24 Stairway floor number signs. Existing stairways shall be marked in accordance with Section 1023.9.

    1104.25 Egress path markings. Existing high-rise buildings of Group A, B, E, I, M and R-1 occupancies shall be provided with luminous egress path markings in accordance with Section 1025.

    Exception: Open, unenclosed stairwells in historic buildings designated as historic under a state or local historic preservation

    program.

    SECTION 1105 —CONSTRUCTION REQUIREMENTS FOR EXISTING GROUP I-2

    1105.1 General. Existing Group I-2 shall meet all of the following requirements:

    1. The minimum fire safety requirements in Section 1103.
    2. The minimum means of egress requirements in Section 1104.
    3. The additional egress and construction requirements in Section 1105.

    Where the provisions of this chapter conflict with the construction requirements that applied at the time of construction, the most restrictive provision shall apply.

    1105.2 Applicability. The provisions of Sections 1105.3 through 1105.8, 1105.10 and 1105.11 shall apply to the existing Group I-2 fire area.

    1105.3 Construction. Group I-2, Condition 2 shall not be located on a floor level higher than the floor level limitation in Table 1105.3 based on the type of construction.

    11-18 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS

    TABLE 1105.3—FLOOR LEVEL LIMITATIONS FOR GROUP I-2, CONDITION 2 Col2 Col3 Col4 Col5 Col6
    CONSTRUCTION TYPE AUTOMATIC SPRINKLER SYSTEM ALLOWABLE FLOOR LEVELa ALLOWABLE FLOOR LEVELa ALLOWABLE FLOOR LEVELa ALLOWABLE FLOOR LEVELa
    CONSTRUCTION TYPE AUTOMATIC SPRINKLER SYSTEM 1 2 3 4 or more
    IA Note b P P P P
    IA Note c P P P P
    IB Note b P P P P
    IB Note c P P P P
    IIA Note b P P P NP
    IIA Note c P NP NP NP
    IIB Note b P P NP NP
    IIB Note c NP NP NP NP
    IIIA Note b P P NP NP
    IIIA Note c P NP NP NP
    IIIB Note b P NP NP NP
    IIIB Note c NP NP NP NP
    IV Note b P P NP NP
    IV Note c NP NP NP NP
    VA Note b P P NP NP
    VA Note c NP NP NP NP
    VB Note b P NP NP NP
    VB Note c NP NP NP NP
    P = Permitted; NP = Not Permitted.
    a.
  • CFC § 1207.1.8 High relevance — show source text

    Fire remediation 1207.1.8 Hazard mitigation analysis 1207.1.6 Large-scale fire test 1207.1.7 Mobile ESS 202, 1207.1, 1207.1.2,

    1207.10 Residential (R-3 and R-4) 1207.11 Stationary ESS 202, 1207 Walk-in units 202, 1207.1.7, 1207.4.12, 1207.4.6, 1207.4.8, 1207.4.9, 1207.5.2, 1207.5.2.1, 1207.5.4, 1207.5.5, 1207.5.6, 1207.6.1, 1207.6.3, 1207.9.4 Energy Systems Chapter 12, 1201.1, 1201.2 Electrical energy storage systems 1201.3, 1207 Emergency and standby power systems 1203

    Permits 105.5.14, 105.6.10, 105.6.21,

    105.6.6 Portable generators 1204, 3309 Solar and photovoltaic systems 1205 Stationary fuel cell power systems 1206 Entry, Right of 104.4 Equipment, Fueled 313 Equipment Platform Defined 202

    Guards required 1015.2 Escalator Openings (see Floor Openings and Shafts) Escape Openings 1031 ESFR Sprinklers (see Automatic Sprinklers) Ethylene Gas 2503

    Generators 2506

    Evacuation 115.2, 405, 2603.3.4, 2603.3.5 Evacuation Diagrams 403.9.1.1, 403.9.2.3 Evacuation Drills 405 Frequency 405.3, Table 405.3 Notification 405.7 Recall and reentry 405.10 Evacuation Plans 404

    Excess Flow Control

    Defined 202

    Excess Flow Valve

    Defined 202

    Exhausted Enclosure 202, 5003.8.5 Exhibit Gallery Occupancy load Table 1004.5 Exhibition Halls (Occupancy Group A-3)

    202

    Exhibits and Trade Shows 105.5.15 Existing Defined 202 Existing Buildings Chapter 11 Group I-2 1105 Outdoor occupancies 1106 Exit 1022 Configuration 1007 Defined 202

    Enclosure 1023

    Horizontal 1026 Number required 1006 Passageways 1024

    Ramps, interior and exterior 1023, 1027 Stairways, interior or exterior 1023, 1027 Stories 1004.2.3, 1006.3, 1017.3.1 Exit Access 101, 1016, 1017, 1018, 1019 Aisles 1018

    Atriums 1006.3.2, 1017.3.2, 1019.3 Balconies 1017.2.1, 1021 Common path 1006.2.1 Corridor 1020

  • California Fire Code High relevance — show source text


    (feet)|FAN|FAN|NAT|FAN|FAN|NAT|FAN|FAN|NAT|FAN|FAN|NAT|FAN|FAN|NAT| |HEIGHT
    _H _
    (feet)|LATERAL
    L
    (feet)**|Min|Max|Max|Min|Max|Max|Min|Max|Max|Min|Max|Max|Min|Max|Max| |6|0
    2
    4
    6|0
    53
    79
    93|698
    425
    419
    413|370
    285
    279
    273|0
    63
    93
    110|897
    543
    536
    530|470
    370
    362
    354|0
    75
    110
    128|1121
    675
    668
    661|570
    455
    445
    435|0
    103
    147
    171|1645
    982
    975
    967|850
    650
    640
    630|0
    138
    191
    219|2267
    1346
    1338
    1330|1170
    890
    880
    870| |8|0
    2
    5
    8|0
    50
    83
    99|780
    483
    473
    463|415
    322
    313
    303|0
    60
    99
    117|1006
    619
    607
    596|537
    418
    407
    396|0
    71
    115
    137|1261
    770
    758
    746|660
    515
    503
    490|0
    98
    154
    180|1858
    1124
    1110
    1097|970
    745
    733
    720|0
    130
    199
    231|2571
    1543
    1528
    1514|1320
    1020
    1010
    1000| |10|0
    2
    5
    10|0
    48
    81
    104|847
    533
    522
    504|450
    355
    346
    330|0
    57
    95
    122|1096
    684
    671
    651|585
    457
    446
    427|0
    68
    112
    142|1377
    852
    839
    817|720
    560
    547
    525|0
    93
    149
    187|2036
    1244
    1229
    1204|1060
    850
    829
    795|0
    124
    192
    238|2825
    1713
    1696
    1669|1450
    1130
    1105
    1080| |15|0
    2
    5

  • California Fire Code High relevance — show source text


    50
    83
    99|780
    483
    473
    463|415
    322
    313
    303|0
    60
    99
    117|1006
    619
    607
    596|537
    418
    407
    396|0
    71
    115
    137|1261
    770
    758
    746|660
    515
    503
    490|0
    98
    154
    180|1858
    1124
    1110
    1097|970
    745
    733
    720|0
    130
    199
    231|2571
    1543
    1528
    1514|1320
    1020
    1010
    1000| |10|0
    2
    5
    10|0
    48
    81
    104|847
    533
    522
    504|450
    355
    346
    330|0
    57
    95
    122|1096
    684
    671
    651|585
    457
    446
    427|0
    68
    112
    142|1377
    852
    839
    817|720
    560
    547
    525|0
    93
    149
    187|2036
    1244
    1229
    1204|1060
    850
    829
    795|0
    124
    192
    238|2825
    1713
    1696
    1669|1450
    1130
    1105
    1080| |15|0
    2
    5
    10
    15|0
    45
    76
    99
    115|970
    633
    620
    600
    580|525
    414
    403
    386
    373|0
    53
    90
    116
    134|1263
    815
    800
    777
    755|682
    544
    529
    507
    491|0
    63
    105
    135
    155|1596
    1019
    1003
    977
    953|840
    675
    660
    635
    610|0
    86
    140
    177
    202|2380
    1495
    1476
    1446
    1418|1240
    985
    967
    936
    905|0
    114
    182
    227
    257|3323
    2062
    2041
    2009
    1976|1720
    1350
    1327
    1289
    1250| |20|0
    2
    5
    10
    15
    20|0
    41
    73
    95
    111
    125|1057
    711
    697
    675
    654
    634|575
    470
    460
    443
    427
    410|0
    50
    86
    112
    129
    145|1384
    917
    902
    877
    853
    830|752
    612
    599
    576
    557
    537|0

  • California Fire Code High relevance — show source text


    2
    5
    10
    15|0
    45
    76
    99
    115|970
    633
    620
    600
    580|525
    414
    403
    386
    373|0
    53
    90
    116
    134|1263
    815
    800
    777
    755|682
    544
    529
    507
    491|0
    63
    105
    135
    155|1596
    1019
    1003
    977
    953|840
    675
    660
    635
    610|0
    86
    140
    177
    202|2380
    1495
    1476
    1446
    1418|1240
    985
    967
    936
    905|0
    114
    182
    227
    257|3323
    2062
    2041
    2009
    1976|1720
    1350
    1327
    1289
    1250| |20|0
    2
    5
    10
    15
    20|0
    41
    73
    95
    111
    125|1057
    711
    697
    675
    654
    634|575
    470
    460
    443
    427
    410|0
    50
    86
    112
    129
    145|1384
    917
    902
    877
    853
    830|752
    612
    599
    576
    557
    537|0
    59
    101
    130
    150
    167|1756
    1150
    1133
    1105
    1078
    1052|930
    755
    738
    710
    688
    665|0
    81
    135
    172
    195
    217|2637
    1694
    1674
    1641
    1609
    1578|1350
    1100
    1079
    1045
    1018
    990|0
    107
    174
    220
    248
    273|3701
    2343
    2320
    2282
    2245
    2210|1900
    1520
    1498
    1460
    1425
    1390| |30|0
    2
    5
    10
    15
    20
    30|0
    33
    69
    91
    105
    119
    149|1173
    826
    811
    788
    765
    743
    702|650
    535
    524
    507
    490
    473
    444|0
    42
    82
    107
    124
    139
    171|1548
    1072
    1055
    1028
    1002
    977
    929|855
    700
    688
    668
    648
    628
    594|0
    54
    96
    125
    143
    160
    195|1977
    1351
    1332
    1301
    1272
    1243
    1189|1060
    865
    851
    829
    807
    784
    745|0

  • CFC § 115.2 High relevance — show source text

    Evacuation 115.2, 405, 2603.3.4, 2603.3.5 Evacuation Diagrams 403.9.1.1, 403.9.2.3 Evacuation Drills 405 Frequency 405.3, Table 405.3 Notification 405.7 Recall and reentry 405.10 Evacuation Plans 404

    Excess Flow Control

    Defined 202

    Excess Flow Valve

    Defined 202

    Exhausted Enclosure 202, 5003.8.5 Exhibit Gallery Occupancy load Table 1004.5 Exhibition Halls (Occupancy Group A-3)

    202

    Exhibits and Trade Shows 105.5.15 Existing Defined 202 Existing Buildings Chapter 11 Group I-2 1105 Outdoor occupancies 1106 Exit 1022 Configuration 1007 Defined 202

    Enclosure 1023

    Horizontal 1026 Number required 1006 Passageways 1024

    Ramps, interior and exterior 1023, 1027 Stairways, interior or exterior 1023, 1027 Stories 1004.2.3, 1006.3, 1017.3.1 Exit Access 101, 1016, 1017, 1018, 1019 Aisles 1018

    Atriums 1006.3.2, 1017.3.2, 1019.3 Balconies 1017.2.1, 1021 Common path 1006.2.1 Corridor 1020

    Doors 1005.7, 1006.2, 1007, 1010,

    1022.2

    Intervening spaces 1016.2 Ramps 1019 Seating at tables 1030.13.1 Single exit 1006.2, 1006.3.3 Stairways 1019 Exit Discharge 202, 1023.12.1, 1023.3, 1024.4, 1028, 1029 Barriers 1023.8

    Courts 1029

    Horizontal exits 1028.2

    Lobbies 1028.2 Public way 1028.5 Termination 1023.3

    Vestibule 1028.2 Expanded Plastic Figure 3203.9(1), Figure 3203.9(2) Defined 202 Expanded Vinyl Wall or Ceiling Coverings 803.7, 803.8 Explosion Defined 202 Explosion Control 911, 2204.1, 2803.2, 2803.2.1, 2905.4, 5004.6, 5005.2.1.2, 5005.2.2.2, 5704.2.5, 5705.3.7.5.2, 5705.3.7.6.2, 5808.6, 6204.1.10, 6304.1.1,

    6704.1.6 Explosive Material Chapter 56 Buildings under construction or demolition 3308

    Defined 202 Explosives and Fireworks Chapter 56 Defined 202 Manufacture, assembly and testing 5605

  • CFC § 11-3 High relevance — show source text

    1101 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3

    1102 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3

    1103 Fire Safety Requirements for Existing Buildings. . . 11-3 1104 Means of Egress for Existing Buildings . . . . . . . . . .11-13 1105 Construction Requirements for Existing Group I-2 . . . . . . . . . . . . . . . . . . . . . . . . . .11-18 1106 Requirements for Outdoor Operations. . . . . . . . . .11-22 1107 Energy Storage Systems. . . . . . . . . . . . . . . . . . . . . . .11-23 1108 Group A Public Address System . . . . . . . . . . . . . . . . . 11-23 1109 through 1112 Reserved . . . . . . . . . . . . . . . . . . . . . . . . . 11-23 1113 Existing Group R-1 and Group R-2 Occupancies [SFM] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-23 1114 Existing High-Rise Buildings [SFM]. . . . . . . . . . . . . . . 11-25 1115 Existing Group I Occupancies [SFM]. . . . . . . . . . . . . . 11-28 1116 Existing Group L and Group H-8 Occupancies [SFM] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-28

    CHAPTER 12 ENERGY SYSTEMS . . . . . . . . . . . . . . . . . . . . .12-3

    1201 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-3

  • CFC § 1104.23 High relevance — show source text

    Where clear openings are provided, they shall be located so as to minimize the accumulation of smoke or toxic gases.

    1104.23 Minimum aisle width. The minimum clear width of aisles shall comply with the following:

    1. Forty-two inches (1067 mm) for stepped aisles having seating on each side.

    Exception: Thirty-six inches (914 mm) where the stepped aisle serves fewer than 50 seats. 2. Thirty-six inches (914 mm) for stepped aisles having seating on only one side.

    Exceptions:

    1. Thirty inches (760 mm) for catchment areas serving not more than 60 seats.

    2. Twenty-three inches (584 mm) between a stepped aisle handrail and seating where a stepped aisle does not serve more than five rows on one side.

    3. Twenty inches (508 mm) between a stepped aisle handrail or guard and seating where the aisle is subdivided by a mid-aisle handrail.

    4. Forty-two inches (1067 mm) for level or ramped aisles having seating on both sides.

    Exceptions:

    1. Thirty-six inches (914 mm) where the aisle serves fewer than 50 seats.
    2. Thirty inches (760 mm) where the aisle serves fewer than 15 seats and does not serve as part of an accessible route.
    3. Thirty-six inches (914 mm) for level or ramped aisles having seating on only one side.

    Exception: Thirty inches (760 mm) for catchment areas serving not more than 60 seats and not serving as part of an accessible route.

    1. In Group I-2, where aisles are used for movement of patients in beds, aisles shall comply with Section 1105.6.8.

    1104.24 Stairway floor number signs. Existing stairways shall be marked in accordance with Section 1023.9.

    1104.25 Egress path markings. Existing high-rise buildings of Group A, B, E, I, M and R-1 occupancies shall be provided with luminous egress path markings in accordance with Section 1025.

    Exception: Open, unenclosed stairwells in historic buildings designated as historic under a state or local historic preservation

    program.

    SECTION 1105 —CONSTRUCTION REQUIREMENTS FOR EXISTING GROUP I-2

    1105.1 General. Existing Group I-2 shall meet all of the following requirements:

    1. The minimum fire safety requirements in Section 1103.
    2. The minimum means of egress requirements in Section 1104.
    3. The additional egress and construction requirements in Section 1105.

    Where the provisions of this chapter conflict with the construction requirements that applied at the time of construction, the most restrictive provision shall apply.

    1105.2 Applicability. The provisions of Sections 1105.3 through 1105.8, 1105.10 and 1105.11 shall apply to the existing Group I-2 fire area.

    1105.3 Construction. Group I-2, Condition 2 shall not be located on a floor level higher than the floor level limitation in Table 1105.3 based on the type of construction.

    11-18 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS

    |TABLE 1105.3—FLOOR LEVEL LIMITATIONS FOR GROUP I-2,

  • CFC § 10-46 High relevance — show source text

    1023 Interior Exit Stairways and Ramps. . . . . . . . . . . . . .10-46 1024 Exit Passageways. . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-49 1025 Luminous Egress Path Markings. . . . . . . . . . . . . . . .10-50 1026 Horizontal Exits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-51

    1027 Exterior Exit Stairways and Ramps . . . . . . . . . . . . .10-52 1028 Exit Discharge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-53 1029 Egress Courts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-54 1030 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-54 1031 Emergency Escape and Rescue . . . . . . . . . . . . . . . .10-61 1032 Maintenance of the Means of Egress . . . . . . . . . . . .10-64

    CHAPTER 11 CONSTRUCTION REQUIREMENTS FOR

    EXISTING BUILDINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-3

    1101 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3

    1102 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3

    1103 Fire Safety Requirements for Existing Buildings. . . 11-3 1104 Means of Egress for Existing Buildings . . . . . . . . . .11-13 1105 Construction Requirements for Existing Group I-2 . . . . . . . . . . . . . . . . . . . . . . . . . .11-18 1106 Requirements for Outdoor Operations. . . . . . . . . .11-22 1107 Energy Storage Systems. . . . . . . . . . . . . . . . . . . . . . .11-23 1108 Group A Public Address System . . . . . . . . . . . . . . . . . 11-23 1109 _through 1112 Reserved . . . . . . . . . . . . . . . . . . . . . . . . .

  • CFC § 7.2 High relevance — show source text

    7.2|—|—|—|—|—|—|—|—|—|—|—|—|—|R|—|—|—|—|—|—|—|—|—| |1103.7.3|—|—|—|—|—|—|—|—|—|—|—|—|—|—|R|—|—|—|—|—|—|—|—| |1103.7.4|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|R|—|—|—|—|—|—|—| |1103.7.5|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|R|—|—|—|—| |1103.7.6|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|R|—|—|—| |1103.8|—|—|—|—|—|—|—|—|—|—|—|—|—|R|—|—|—|—|R|R|R|R|—| |1103.9|R|—|—|—|—|—|—|—|—|—|—|—|—|R|R|—|R|—|R|R|R|R|—| |1103.10|—|—|—|—|—|—|—|—|—|—|—|—|—|R|R|—|—|—|—|—|—|—|—| |1104|R|R|R|—|R|R|R|R|R|R|R|R|R|R|R|R|R|R|R|R|R|R|R| |1105|—|—|—|—|—|—|—|—|—|—|—|—|—|—|R|—|—|—|—|—|—|—|—| |1106|—|—|—|R|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—|—| |R = The building is required to comply.
    a.
    Existing buildings shall comply with the sections identified as “Required” (R) based on occupancy classification or use, or both, whichever is applicable.
    b.
    Only applies to Group I-2, Condition 2 occupancies as established by the adopting ordinance or legislation of the jurisdiction.
    c.
    Only applies to Group A-2 occupancies where alcoholic beverages are consumed.|R = The building is required to comply.
    a.
    Existing buildings shall comply with the sections identified as “Required” (R) based on occupancy classification or use, or both, whichever is applicable.
    b.
    Only applies to Group I-2, Condition 2 occupancies as established by the adopting ordinance or legislation of the jurisdiction.
    c.
    Only applies to Group A-2 occupancies where alcoholic beverages are consumed.|R = The building is required to comply.
    a.
    Existing buildings shall comply with the sections identified as “Required” (R) based on occupancy classification or use, or both, whichever is applicable.
    b.
    Only applies to Group I-2,

Frequently asked questions

What exactly does “Condition 2” mean for Group I-2?

“Condition 2” is a specific sub‑classification used in the code/adopting ordinance. The retrieved excerpts reference Condition 2 but do not include its definition — verify the full CFC/ local adopting ordinance to confirm whether your space qualifies.

Do automatic sprinklers always change the allowed floor level?

Table 1105.3 uses table notes (e.g., Note b/Note c) that commonly differentiate based on features such as sprinkler systems, but the retrieved snippet does not contain the full note text. Consult the full Table 1105.3 footnotes to confirm how sprinkler coverage affects the entry.

If my building was originally built under older rules, which rule applies?

Per § 1105.1, if Chapter 11 conflicts with the construction rules that applied when the building was built, the more restrictive provision applies. Always compare both sets and apply the stricter requirement.

Where can I find the missing footnotes to Table 1105.3?

The retrieved excerpt shows “Note b” and “Note c” but not their full wording. I can pull the full table with its footnotes from your uploaded code file (or you should consult the official CFC text) to resolve those conditions precisely.

Must I also meet § 1103 and § 1104 when the table permits a floor level?

Yes — § 1105.1 explicitly requires compliance with § 1103 (fire safety) and § 1104 (means of egress) in addition to the Table 1105.3 limits.

More in California Fire Code

Ask about the CFC

Get cited, plain-English answers on the California Fire Code for your project — any code section, any scenario.

Start Free Trial

Related in the CFC