Evaluation requirements and performance objectives
This page orients users to the CEBC rules for seismic evaluation, required performance objectives (Table 317.5), and the analysis and peer‑review paths used to show compliance.
Last reviewed: July 6, 2026
Overview
This part of the California Existing Building Code (CEBC) sets the mandatory seismic evaluation and, when required, retrofit performance objectives for existing buildings undergoing alteration, addition or repair. The chapter establishes when an evaluation is required, what minimum seismic performance levels must be met, and the relationship between the CEBC and ASCE 41 procedures used to demonstrate compliance (see §317.2–§317.5).
The code requires a registered design professional to evaluate an existing building’s seismic performance and, if it falls short of the prescribed performance levels (Table 317.5), to prepare retrofit or repair designs that meet the performance objectives; peer review and building-official acceptance are required for many analysis approaches (see §317.4, §317.5, §321 and §322).
For projects using the Performance Compliance Method (Chapter 13), the CEBC prescribes investigation, scoring and evaluation procedures (including Sections 1304–1305) that feed into acceptance and required remedial actions when safety or egress deficiencies are found. These performance methods are coordinated with the CEBC’s seismic evaluation chapters and with ASCE 41 Tiered procedures for structural and nonstructural components.
In this section
Code references
Grounded in the retrieved California Existing Building Code — click a citation to read the verbatim passage:
CEBC § 317.2 High relevance — show source text
317.2 Scope. All alterations, structurally connected additions and/or repairs to existing structures or portions thereof shall, at a minimum, be designed and constructed to resist the effects of seismic ground motions as provided in this section. The structural system shall be evaluated by a registered design professional and, if not meeting or exceeding the minimum seismic design performance requirements of this section, shall be retrofitted in compliance with these requirements.
Exception: Those structures for which Section 317.3 determines that assessment is not required, or for which Section 317.4 determines that retrofit is not needed, then only the requirements of Section 317.11 apply.
317.3 Applicability.
317.3.1 Existing state-owned buildings. [BSC, DSA-SS] For existing state-owned structures including all buildings owned by the University of California and the California State University, the requirements of Section 317 apply whenever the structure is to be retrofitted, repaired or modified and any of the following apply: 1. Total construction cost, not including cost of furnishings, fixtures and equipment, or normal maintenance, for the building exceeds 25 percent of the construction cost for the replacement of the existing building. The changes are cumulative for past modifications to the building that occurred after adoption of the 1995 California Building Code and did not require seismic retrofit.
3-16 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PROVISIONS FOR ALL COMPLIANCE METHODS
2. There are changes in risk category. 3. The modification to the structural components increases the seismic forces in or strength requirements of any structural component of the existing structure by more than 10 percent cumulative since the original construction, unless the component has the capacity to resist the increased forces determined in accordance with Section 319. If the building’s seismic base shear capacity has been increased since the original construction, the percent change in base shear may be calculated relative to the increased value.
4. Structural elements need repair where the damage has reduced the lateral-load-resisting capacity of the structural system by more than 10 percent. 5. Changes in live or dead load increase story shear by more than 10 percent.
317.3.2 Public school buildings. [DSA-SS] For public schools, the provisions of Section 317 apply when required in accordance with Sections 4-307 and 4-309(c) of the California Administrative Code.
317.3.3 Community college buildings. [DSA-SS/CC] For community colleges, the provisions of Section 317 apply when required in accordance with Sections 4-307 and 4-309(c) of the California Administrative Code.
317.4 Evaluation required. If the criteria in Section 317.3 apply to the project under consideration, the design professional of record shall provide an evaluation in accordance with Section 317 to determine the seismic performance of the building in its current configuration and condition. If the structure's seismic performance as required by Section 317.5 is evaluated as satisfactory and the peer reviewer(s), when Method B of Section 321 is used, concur, then no structural retrofit is required.
_**317.5 Minimum seismic design performance levels for structural and nonstructural components.
CEBC § 317.5 High relevance — show source text
When the evaluation indicates the building does not meet the required performance levels given in Table 317.5 for the risk category, then a retrofit and/or repair design shall be prepared that provides a structure that meets these performance objectives and reflects the appropriate consideration of existing conditions. Any approach to analysis and design is permitted to be used, provided that the approach shall be rational, shall be consistent with the established principals of mechanics and shall use the known performance characteristics of materials and assemblages under reversing loads typical of severe earthquake ground motions.
Exception: Further consideration of the structure’s seismic performance may be waived by the enforcement agency if both the registered design professional and peer reviewer(s) conclude that the structural system can be expected to perform at least as well as required by the provisions of this section without completing an analysis of the structure’s compliance with these requirements. A detailed report shall be submitted to the responsible building official that presents the reasons and basis for this conclusion. This report shall be prepared by the registered design professional. The peer reviewer(s) shall concur in this conclusion and affirm to it in writing. The building official shall either approve this decision or require completion of the indicated work specified in this section prior to approval.
321.2 The approach, models, analysis procedures, assumptions on material and system behavior and conclusions shall be peer reviewed in accordance with the requirements of Section 322 and accepted by the peer reviewer(s).
Exceptions: 1. The enforcement agency may perform the work of peer review when qualified staff is available within the jurisdiction. 2. The enforcement agency may modify or waive the requirements for peer review when appropriate.
321.2.1 The approach used in the development of the design shall be acceptable to the peer reviewer and the enforcement agency and shall be the same method as used in the evaluation of the building. Approaches that are specifically tailored to the type of building, construction materials and specific building characteristics may be used, if they are acceptable to the independent peer reviewer. The use of Method A allowed procedures may also be used under Method B.
321.2.2 Any method of analysis may be used, subject to acceptance by the peer reviewer(s) and the building official. The general requirements given in ASCE 41, Chapters 6 and 7, shall be complied with unless exceptions are accepted by the peer reviewer(s) and building official. Use of other than ASCE 41 procedures in Method B requires building official concurrence before implementation.
321.2.3 Prior to implementation, the procedures, methods, material assumptions and acceptance/rejection criteria proposed by the registered design professional will be peer reviewed as provided in Section 322. Where nonlinear procedures are used, prior to any analysis, the representation of the seismic ground motion shall be reviewed and approved by the peer reviewer(s) and the building official.
[DSA-SS, DSA-SS/CC] For public school and community college projects, the representation of the seismic ground motion shall be reviewed and approved by the California Geological Survey.
321.2.4 The conclusions and design decisions shall be reviewed and accepted by the peer reviewer(s) and the building official.
SECTION 322 [BSC, DSA-SS & DSA-SS/CC]—PEER REVIEW REQUIREMENTS
CEBC § 41-23. High relevance — show source text
Exception: Evaluation procedure of Article 11, Chapter 6 of the California Administrative Code shall be used for seismic evalua- tion of NPC 2, NPC 3, NPC 4 or NPC 4D and NPC 5, where specific procedure is not outlined in ASCE 41-23. Administrative and permitting provisions outlined in Article 11, Chapter 6 of the California Administrative Code shall apply.
304A.3.4.8 NPC-4 or NPC 4D and NPC-5 using ASCE 41-23: Nonstructural components for Operational Nonstructural Perfor- mance Level (N-A) in ASCE 41-23 Table 2-2 or NPC-4/NPC 4D shall satisfy the requirements of the California Building Code for new construction. Nonstructural components for NPC-5 shall satisfy Operational Performance Level N-A/NPC-4/NPC 4D and California Building Code Section 1617A.1.40 Items 1 & 2.
304A.3.5 Modifications to ASCE 41-13 for SPC-2 and SPC-4D. The text of ASCE 41-13 shall be modified as indicated in Sections 304A.3.5.1 through 304A.3.5.17.
304A.3.5.1 ASCE 41-13 Section 1.1. Modify ASCE 41-13 Section 1.1 with the following:
Seismic evaluations shall be performed for performance objective specified in Section 304A.3.4 of this code (CEBC) using proce- dure of this standard (ASCE 41) as follows:
1. Structural components shall be evaluated in accordance with Tier 3 systematic evaluations procedure in Chapter 6. 2. Nonstructural components shall be evaluated in accordance with Chapter 13.
Exception: For general acute care hospitals, seismic evaluation shall be permitted to be in accordance with Chapter 6 of the California Administrative Code (CAC) when required by provisions of that chapter.
304A.3.5.2 ASCE 41-13 Section 2.4 Seismic Hazard. Modify ASCE 41-13 Section 2.4 with the following:
Response spectra and acceleration time histories shall be constructed in accordance with 2016 California Building Code (CBC) Sections 1613A, 1616A, and 1803A.6 or equivalent provision in later versions of the CBC.
304A.3.5.3 ASCE 41-13 Section 6.2. Modify ASCE 41-13 Section 6.2 with the following:
Data Collection Requirements. The extent of data collection shall be at Comprehensive level for all structures, including struc- tures upgraded to SPC-4D. A testing program for materials properties shall be approved by the enforcement agent prior to
3A-6 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PROVISIONS FOR ALL COMPLIANCE METHODS
commencement of material testing work. Previously approved material test results shall be permitted to be used to satisfy part of the comprehensive data collection requirements.
Exception: Data collection at Usual level shall be permitted for structures with SPC-2 or lower target performance objective.
CEBC § 317.3.2 High relevance — show source text
2. There are changes in risk category. 3. The modification to the structural components increases the seismic forces in or strength requirements of any structural component of the existing structure by more than 10 percent cumulative since the original construction, unless the component has the capacity to resist the increased forces determined in accordance with Section 319. If the building’s seismic base shear capacity has been increased since the original construction, the percent change in base shear may be calculated relative to the increased value.
4. Structural elements need repair where the damage has reduced the lateral-load-resisting capacity of the structural system by more than 10 percent. 5. Changes in live or dead load increase story shear by more than 10 percent.
317.3.2 Public school buildings. [DSA-SS] For public schools, the provisions of Section 317 apply when required in accordance with Sections 4-307 and 4-309(c) of the California Administrative Code.
317.3.3 Community college buildings. [DSA-SS/CC] For community colleges, the provisions of Section 317 apply when required in accordance with Sections 4-307 and 4-309(c) of the California Administrative Code.
317.4 Evaluation required. If the criteria in Section 317.3 apply to the project under consideration, the design professional of record shall provide an evaluation in accordance with Section 317 to determine the seismic performance of the building in its current configuration and condition. If the structure's seismic performance as required by Section 317.5 is evaluated as satisfactory and the peer reviewer(s), when Method B of Section 321 is used, concur, then no structural retrofit is required.
317.5 Minimum seismic design performance levels for structural and nonstructural components. Following the notations of ASCE 41, the seismic requirements for design and assessment are based upon a prescribed Seismic Hazard Level (BSE-1N, BSE-2N, BSE-1E, BSE-R or BSE-C), a specified structural performance level (S-1 through S-5) and a nonstructural performance level (N-A through N-E). The minimum seismic performance criteria are given in Table 317.5 according to the Building Regulatory Authority and the Risk Category as determined in Chapter 16 of the California Building Code or by the regulatory authority. The building shall be evaluated in accordance with a Tier 3 Systematic Evaluation and Retrofit per ASCE 41 Chapter 6 for both the Level 1 and Level 2 performance levels, and the more restrictive requirements shall apply.
Exception: If the floor area of an addition is greater than the larger of 50 percent of the floor area of the original building or 1,000 square feet (93 m [2] ), then the Table 317.5 entries for BSE-R (or BSE-1E) and BSE-C are replaced by BSE-1N and BSE-2N, respectively.
|TABLE 317.5—SEISMIC PERFORMANCE REQUIREMENTS2,
CEBC § 304A.3.5.17 Medium relevance — show source text
Scope: For buildings located in Seismic Design Category F, verification of the interstory lateral displacements, the strength adequacy of the seismic force-resisting system and anchorage to the foundation shall be accomplished using the Nonlinear Dynamic Procedure.
304A.3.5.17 ASCE 41-13 Chapter 15 and 16. Not permitted by OSHPD.
304A.3.6 Modifications to ASCE 41-23. The text of ASCE 41-23 shall be modified as indicated in Sections 304A.3.6.1 through 304A.3.6.9.
304A.3.6.1 ASCE 41-23 Section 2.1. Modify ASCE 41-23 Section 2.1 with the following:
Seismic evaluations shall be performed for performance objective specified in Section 304A.3.4 of this code (CEBC) using proce- dure of this standard (ASCE 41-23) as follows:
1. Structural components shall be evaluated in accordance with Tier 3 systematic evaluations procedure in Chapter 6.
2. Nonstructural components shall be evaluated in accordance with Chapter 13.
Exception: For general acute care hospitals, seismic evaluation shall be permitted to be in accordance with Chapter 6 of the California Administrative Code (CAC) when required by provisions of that chapter.
304A.3.6.2 ASCE 41-23 Section 6.2. Modify ASCE 41-23 Section 6.2 with the following:
Data Collection Requirements. The extent of data collection shall be at Comprehensive level for all structures, including struc- tures upgraded to SPC-4D. A testing program for materials properties shall be approved by the enforcement agent prior to commencement of material testing work. Previously approved material test results shall be permitted to be used to satisfy part of the comprehensive data collection requirements.
3A-8 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PROVISIONS FOR ALL COMPLIANCE METHODS
Tension testing of reinforcing bars shall be in accordance with ASTM A615. All test specimens shall be the full section of the bar as rolled (8-in. gage length) and shall not be reduced.
At test sample locations, structural members, slabs and walls shall be repaired to a state that is equivalent to their original condition.
For buildings built under an OSHPD permit based on the 1976 or later edition of the CBC, where materials properties are shown on design drawings and original materials test data are available, no materials testing shall be required when approved by the enforcement agent.
304A.3.6.3 ASCE 41-23 Section 7.2.9.1. Modify ASCE 41-23 Section 7.2.9.1 with the following:
For the evaluation of one-story light-framed walls with or without hold-downs, ASCE 41-23 Equation 7-6 is permitted to be used. If Equation 7-6 is satisfied, no further evaluation or retrofit of the existing hold-down, if any, is required. If Equation 7-6 is not _satisfied, hold-down shall be provided or retrofitted using ASCE 41-23 Equations 7-39 and 7-40.
CEBC § 319.8. Medium relevance — show source text
unless it can be demonstrated that_ reduced capacity meets the requirements of Section 319.8. 2. The lateral loading to or strength requirement of existing structural components is not increased beyond their capacity. 3. New structural components are detailed and connected to the existing structural components as required by the California Building Code. 4. New or relocated nonstructural components are detailed and connected to existing or new structural components as required by the California Building Code. 5. A dangerous condition is not created.
Use of ASCE 41 Tier 1 and Tier 2 deficiency only retrofit procedures are pre-approved for use where Section 317.3 does not require an
assessment.
319.12.1 State-owned buildings. [BSC] Voluntary modifications to lateral force-resisting systems conducted in accordance with Appendix A of this code and the referenced standards of the California Building Code shall be permitted.
319.12.1.1 Design documents. [BSC] When Section 319.12 is the basis for structural modifications, the approved design documents must clearly state the scope of the seismic modifications and the accepted criteria for the design. The approved design documents must clearly have the phrase “The seismic requirements of the California Existing Building Code have not been checked to determine if these structural modifications meet the full seismic evaluation and strengthening requirements of Sections 317-322: the modifications proposed are to a different seismic performance standard than would be required in Section 319 if they were not voluntary as allowed in Section 319.12.”
3-20 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PROVISIONS FOR ALL COMPLIANCE METHODS
319.12.2 Public schools and community colleges. [DSA-SS, DSA-SS/CC] When Section 319.12 is the basis for structural modifications, the approved design documents must clearly indicate the scope of modifications and the acceptance criteria for the design.
SECTION 320 [BSC, DSA-SS & DSA-SS/CC]—METHOD A
320.1 General. The retrofit design shall employ the Linear Static or Linear Dynamic Procedures of ASCE 41, Section 7.4.1 or 7.4.2, and comply with the applicable general requirements of ASCE 41, Chapters 6 and 7. The earthquake hazard level and performance level given specified in Section 317.5 for the building’s risk category shall be used. Structures shall be designed for seismic forces coming from any horizontal direction.
SECTION 321 [BSC, DSA-SS & DSA-SS/CC]—METHOD B
321.1 The existing or retrofitted structure shall be demonstrated to have the capability to sustain the deformation response due to the specified earthquake ground motions and meet the seismic performance requirements of Section 317. The registered design professional shall provide an evaluation of the response of the existing structure in its modified configuration and condition to the ground motions specified. If the building’s seismic performance is evaluated as satisfactory and the peer reviewer(s) and the enforcement agency concurs, then no further structural retrofit and/or repair of the lateral load-resisting system is required.
CEBC § 3-20 Medium relevance — show source text
3-20 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PROVISIONS FOR ALL COMPLIANCE METHODS
319.12.2 Public schools and community colleges. [DSA-SS, DSA-SS/CC] When Section 319.12 is the basis for structural modifications, the approved design documents must clearly indicate the scope of modifications and the acceptance criteria for the design.
SECTION 320 [BSC, DSA-SS & DSA-SS/CC]—METHOD A
320.1 General. The retrofit design shall employ the Linear Static or Linear Dynamic Procedures of ASCE 41, Section 7.4.1 or 7.4.2, and comply with the applicable general requirements of ASCE 41, Chapters 6 and 7. The earthquake hazard level and performance level given specified in Section 317.5 for the building’s risk category shall be used. Structures shall be designed for seismic forces coming from any horizontal direction.
SECTION 321 [BSC, DSA-SS & DSA-SS/CC]—METHOD B
321.1 The existing or retrofitted structure shall be demonstrated to have the capability to sustain the deformation response due to the specified earthquake ground motions and meet the seismic performance requirements of Section 317. The registered design professional shall provide an evaluation of the response of the existing structure in its modified configuration and condition to the ground motions specified. If the building’s seismic performance is evaluated as satisfactory and the peer reviewer(s) and the enforcement agency concurs, then no further structural retrofit and/or repair of the lateral load-resisting system is required.
When the evaluation indicates the building does not meet the required performance levels given in Table 317.5 for the risk category, then a retrofit and/or repair design shall be prepared that provides a structure that meets these performance objectives and reflects the appropriate consideration of existing conditions. Any approach to analysis and design is permitted to be used, provided that the approach shall be rational, shall be consistent with the established principals of mechanics and shall use the known performance characteristics of materials and assemblages under reversing loads typical of severe earthquake ground motions.
Exception: Further consideration of the structure’s seismic performance may be waived by the enforcement agency if both the registered design professional and peer reviewer(s) conclude that the structural system can be expected to perform at least as well as required by the provisions of this section without completing an analysis of the structure’s compliance with these requirements. A detailed report shall be submitted to the responsible building official that presents the reasons and basis for this conclusion. This report shall be prepared by the registered design professional. The peer reviewer(s) shall concur in this conclusion and affirm to it in writing. The building official shall either approve this decision or require completion of the indicated work specified in this section prior to approval.
321.2 The approach, models, analysis procedures, assumptions on material and system behavior and conclusions shall be peer reviewed in accordance with the requirements of Section 322 and accepted by the peer reviewer(s).
Exceptions: 1. The enforcement agency may perform the work of peer review when qualified staff is available within the jurisdiction. 2. The enforcement agency may modify or waive the requirements for peer review when appropriate.
CEBC § 304A.3.5.13 Medium relevance — show source text
304A.3.5.13 ASCE 41-13 Section 10.7.1.1. Modify ASCE 41-13 Section 10.7.1.1 with the following:
Monolithic Reinforced Concrete Shear Walls and Wall Segments. For nonlinear procedures, shear walls or wall segments with axial loads greater than 0.35 Po shall be included in the model as primary elements with appropriate strength and stiffness degrading properties assigned to those components subject to the approval of the enforcement agent. For linear procedures, the effects of deformation compatibility shall be investigated using moment-curvature section analyses and cyclic testing results of similar components to determine whether strengthening is necessary to maintain the gravity load-carrying capacity of that component.
Horizontal wall segments or spandrels reinforced similar to vertical wall segments or piers shall be classified as wall segments, not shear wall coupling beams, in Tables 10-19 through 10-22.
304A.3.5.14 ASCE 41-13 Section 10.12.3 Modify ASCE 41-13 Section 10.12.3 as follows:
Exception: Component actions that are deformation controlled are permitted to use their expected strengths for the accep- tance criteria.
304A.3.5.15 ASCE 41-13 Section 11.1. Modify ASCE 41-13 Section 11.1 by the following:
Scope: Unreinforced masonry walls (including unreinforced infill walls) and partitions are not permitted for General Acute Care (GAC) hospital buildings.
304A.3.5.16 ASCE 41-13 Section 14.1. Modify ASCE 41-13 Section 14.1 by the following:
Scope: For buildings located in Seismic Design Category F, verification of the interstory lateral displacements, the strength adequacy of the seismic force-resisting system and anchorage to the foundation shall be accomplished using the Nonlinear Dynamic Procedure.
304A.3.5.17 ASCE 41-13 Chapter 15 and 16. Not permitted by OSHPD.
304A.3.6 Modifications to ASCE 41-23. The text of ASCE 41-23 shall be modified as indicated in Sections 304A.3.6.1 through 304A.3.6.9.
304A.3.6.1 ASCE 41-23 Section 2.1. Modify ASCE 41-23 Section 2.1 with the following:
Seismic evaluations shall be performed for performance objective specified in Section 304A.3.4 of this code (CEBC) using proce- dure of this standard (ASCE 41-23) as follows:
1. Structural components shall be evaluated in accordance with Tier 3 systematic evaluations procedure in Chapter 6.
2. Nonstructural components shall be evaluated in accordance with Chapter 13.
Exception: For general acute care hospitals, seismic evaluation shall be permitted to be in accordance with Chapter 6 of the California Administrative Code (CAC) when required by provisions of that chapter.
304A.3.6.2 ASCE 41-23 Section 6.2. Modify ASCE 41-23 Section 6.2 with the following:
CEBC § 104.2.3.3 Medium relevance — show source text
[A] 104.2.3.3 Compliance with code intent. An alternative material, design or method of construction shall comply with the intent of the provisions of this code.
[A] 104.2.3.4 Equivalency criteria. An alternative material, design or method of construction shall, for the purpose intended, be not less than the equivalent of that prescribed in this code with respect to all of the following, as applicable:
Quality.
Strength.
Effectiveness.
Durability.
Safety, other than fire safety.
Fire safety.
[A] 104.2.3.5 Tests. Tests conducted to demonstrate equivalency in support of an alternative material, design or method of construction application shall be of a scale that is sufficient to predict performance of the end use configuration. Such tests shall be performed by a party acceptable to the code official.
[A] 104.2.3.5.1 Fire tests. Tests conducted to demonstrate equivalent fire safety in support of an alternative material, design or method of construction application shall be of a scale that is sufficient to predict fire safety performance of the end use configuration. Tests shall be performed by a party acceptable to the code official.
[A] 104.2.3.6 Reports. Supporting documentation, where necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall comply with Sections 104.2.3.6.1 and 104.2.3.6.2.
[A] 104.2.3.6.1 Evaluation reports. Evaluation reports shall be issued by an approved agency, and use of the evaluation report shall require approval by the code official for the installation. The alternate material, design or method of construction and product evaluated shall be within the scope of the code official’s recognition of the approved agency. Criteria used for the evaluation shall be identified within the report and, where required, provided to the code official.
[A] 104.2.3.6.2 Other reports. Reports not complying with Section 104.2.3.6.1 shall describe criteria, including but not limited to any referenced testing or analysis, used to determine compliance with code intent and justify code equivalence. The report shall be prepared by a qualified engineer, specialist, laboratory or fire safety specialty organization acceptable to the code official. The code official is authorized to require design submittals to be prepared by, and bear the stamp of, a registered design professional.
[A] 104.2.3.7 Peer review. The code official is authorized to require submittal of a peer review report in conjunction with a request to use an alternative material, design or method of construction, prepared by a peer reviewer that is approved by the code official.
[A] 104.2.4 Modifications. Where there are practical difficulties involved in carrying out the provisions of this code, the code official shall have the authority to grant modifications for individual cases, provided that the code official shall first find that one or more special individual reasons make the strict letter of this code impractical, and that the modification is in compliance with the intent and purpose of this code and that such modification does not lessen health, accessibility, life and fire safety, or structural requirements. The details of the written request for and action granting modifications shall be recorded and entered in the files of the department of building safety.
CEBC § 11-3 Medium relevance — show source text
1101 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
1102 Heights and Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
1103 Structural. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
1104 Energy Conservation. . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
CHAPTER 12 HISTORIC BUILDINGS . . . . . . . . . . . . . . . . . .12-1
xviii 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS. . 13-3
1301 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-3
1302 Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-3
1303 Acceptance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-4
1304 Investigation and Evaluation . . . . . . . . . . . . . . . . . . . 13-4
1305 Scoring and Evaluation . . . . . . . . . . . . . . . . . . . . . . . . 13-4
1306 Building Score . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-14
1307 Evaluation of Building Safety. . . . . . . . . . . . . . . . . . 13-16
CHAPTER 14 RELOCATED OR MOVED BUILDINGS . . . . . . 14-3
1401 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-3
1402 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-3
CHAPTER 15 CONSTRUCTION SAFEGUARDS . . . . . . . . . . 15-3
1501 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
1502 Owner’s Responsibility for Fire Protection . . . . . . . 15-3
1503 Sanitary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-4
CEBC § 319.1 Medium relevance — show source text
Buildings complying with the requirements of the exception in Section 319.1 are deemed to meet the seismic performance requirements of this section._
4. State-owned and state-leased essential services buildings are subject to the regulatory authority of DSA-SS per Section 1.9.2.1.|317.6 Retrofit required. Where the evaluation indicates the building does not meet the required performance objectives of this section, the owner shall take appropriate steps to ensure that the building’s structural system is retrofitted in accordance with the provisions of Section 317. Appropriate steps are either: 1) undertake the seismic retrofit as part of the additions, alterations and/or repairs of the structure; or 2) provide a plan, acceptable to the building official, to complete the seismic retrofit in a timely manner. The relocation or moving of an existing building is considered to be an alteration requiring filing of the plans and specifications approved by the building official.
317.7 The additions, alteration or repair to any existing building are permitted to be prepared in accordance with the structural and nonstructural requirements for a new building as given in the California Building Code, applied to the entire building.
317.8 The requirements of ASCE 41 Chapters 14 and 15 are to apply to the use of seismic isolation and passive energy systems, respectively, for the repair, voluntary lateral-force-resisting system modification or retrofit of an existing structure. When seismic isolation or passive energy dissipation is used, the project must have project peer review as prescribed in Section 322.
317.9 Any construction required by this chapter shall include structural observation by the registered design professional who is responsible for the structural design in accordance with Section 319.10.
2025 CALIFORNIA EXISTING BUILDING CODE 3-17
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PROVISIONS FOR ALL COMPLIANCE METHODS
317.10 Where Method B of Section 321 is used or is required by Section 319.7, the proposed method of building evaluation and design procedures must be accepted by the building official prior to the commencement of the work.
317.11 Voluntary lateral-force-resisting system modifications. Where the exception of Section 317.2 applies, modifications of existing structural components and additions of new structural components that are initiated for the purpose of improving the seismic performance of an existing structure and that are not required by other portions of this chapter are permitted under the requirements of Section 319.12.
SECTION 318 [BSC, DSA-SS & DSA-SS/CC]—DEFINITIONS
318.1 In addition to the definitions given in Section 202, for the purposes of Sections 317 through 323, certain terms are defined as follows:
[DSA-SS & DSA-SS/CC] For the purposes of Section 317 through 323, definitions of terms given in Section 4-207 or 4-314 of the California Administrative Code govern over those in Section 202.
ADDITION [BSC] means any work that increases the floor or roof area or the volume of enclosed space of an existing building, and is structurally attached to the existing building by connections that are required for transmitting vertical or horizontal loads between the addition and the existing structure.
CEBC § 1305.1.1 Medium relevance — show source text
1305.1.1 Fire safety. Included within the fire safety category are the structural fire resistance, automatic fire detection, fire alarm, automatic sprinkler system and fire suppression system features of the facility.
1305.1.2 Means of egress. Included within the means of egress category are the configuration, characteristics and support features for means of egress in the facility.
1305.1.3 General safety. Included within the general safety category are the fire safety parameters and the means of egress parameters.
1305.2 Evaluation process. The evaluation process specified herein shall be followed in its entirety to evaluate existing buildings in Groups A, B, E, F, M, R, S and U. For existing buildings in Group I-2, the evaluation process specified herein shall be followed and applied to each and every individual smoke compartment. Table 1306.1 shall be utilized for tabulating the results of the evaluation. References to other sections of this code or other codes indicate that compliance with those sections is required in order to gain credit in the evaluation herein outlined. In applying this section to a building with mixed occupancies, where the separation between the mixed occupancies does not qualify for any category indicated in Section 1305.2.16, the score for each occupancy shall be determined, and the lower score determined for each section of the evaluation process shall apply to the entire building or to each smoke compartment for Group I-2 occupancies.
Where the separation between the mixed occupancies qualifies for any category indicated in Section 1305.2.16, the score for each occupancy shall apply to each portion or smoke compartment of the building based on the occupancy of the space.
1305.2.1 Building height and number of stories. The value for building height and number of stories shall be the lesser value determined by the formula in Section 1305.2.1.1. Section 504 of the International Building Code shall be used to determine the allowable height and number of stories of the building. Subtract the actual building height from the allowable height and divide by 12.5 feet (3810 mm). Enter the height value and its sign (positive or negative) in Table 1306.1 under Safety Parameter 1305.2.1, Building Height, for fire safety, means of egress and general safety. The maximum score for a building shall be 10.
1305.2.1.1 Height formula. The following formulas shall be used in computing the building height value.
Equation 13-1 Height value, feet = (---------------------------------- [AH] ) – ( EBH - ) × CF 12.5
13-4 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PERFORMANCE COMPLIANCE METHODS
Equation 13-2 Height value, stories = ( AS – EBS ) × CF
where:
AH = Allowable height in feet (mm) from Section 504 of the International Building Code .
EBH = Existing building height in feet (mm).
AS = Allowable height in stories from Section 504 of the International Building Code .
EBS = Existing building height in stories.
CF = 1 if ( AH ) – ( EBH ) is positive.
CF = Construction-type factor shown in Table 1305.2.6(2) if ( AH ) – ( EBH ) is negative.
Frequently asked questions
When is a seismic evaluation required for an existing building?
If the project meets the applicability criteria in §317.3 (for example certain state-owned buildings, additions that exceed thresholds, or repairs that alter seismic capacity), the design professional must provide an evaluation per §317.4 to determine current seismic performance.
What performance objectives apply and where do I find them?
Minimum structural and nonstructural seismic performance levels are listed in Table 317.5 and described in §317.5; they reference seismic hazard levels (BSE‑1N, BSE‑2N, etc.) and ASCE 41 performance levels (S‑1 through S‑5 for structural, N‑A through N‑E for nonstructural). If evaluation shows noncompliance, retrofit or repair to meet those objectives is required.
Is peer review required for evaluations and methods of analysis?
Yes. The CEBC requires peer review of the analysis approach, models, assumptions and conclusions per §321.2 and the peer-review provisions in §322; enforcement agencies may perform, modify or waive peer review only where explicitly allowed.
More in California Existing Building Code
- Administration and Definitions (Scope, enforcement, code official duties, definitions)
- Provisions for All Compliance Methods (general requirements that apply to all compliance options; Chapter 3 / 3A)
- Seismic retrofit and evaluation (Appendix A and seismic provisions/sections for evaluation and retrofit)
- Referenced Standards and Appendices (Chapter 16 and Appendices A–E, Resource A)
- Repairs (Chapter 4 — repair-specific rules for materials, means of egress, structural, MEP, etc.)
- Alterations — Level 1, Level 2, Level 3 (technical requirements for each alteration level; Chapters 7–9)
- Change of Occupancy and Additions (requirements for occupancy changes and additions; Chapters 10–11)
- Compliance Methods — Prescriptive, Work Area, Performance (Chapters 5, 6–11, 13)
- Relocated Buildings (requirements for buildings moved or relocated; Chapter 14)
- Construction Safeguards (site safety, means of egress and life-safety during construction; Chapter 15)
Ask about the CEBC
Get cited, plain-English answers on the California Existing Building Code for your project — any code section, any scenario.
Start Free TrialRelated in the CEBC
Selecting seismic criteria and compliance methods (Method A / Method B / Appendix A)
Repair, damage assessment, and earthquake-damage retrofit rules
Retrofit design procedures, ASCE 41 modifications, and Appendix A guidance