Title 24 · California Energy Code

Reference Appendices (NA6, NA7, NA7.8) used for acceptance and test protocols

If a Code section points to a Reference Nonresidential Appendix (NA6, NA7, NA7.8), you must use that appendix’s calculation or test method and submit the required Certificate of Acceptance (or installation certificate) to the enforcement agency before occupancy — for example, NA6 is used for certain skylight defaults under § 110.6(a)2–4, and NA7 / NA7.8 supply the acceptance tests and reporting formats for HVAC, ducts, and outdoor lighting controls in §§ 120.5, 130.4 and related sections.

Last reviewed: July 6, 2026

What the code requires — 2-4 sentences

The California Energy Code uses the Reference Nonresidential Appendices NA6 and NA7 (and the lighting‑controls testing appendix NA7.8) to provide standardized methods and forms for computing default fenestration metrics and for performing and documenting acceptance testing of systems. When a provision in the body of the Code points to an appendix, that appendix’s test or calculation method must be used (for example, default skylight properties per § 110.6(a)2–4 and acceptance testing for many HVAC, lighting and other systems per § 120.5(a) and § 130.4).

The single most important rule: when the Code references a “Reference Nonresidential Appendix (NA#),” perform the specific test or calculation in that Appendix and provide the corresponding Certificate of Acceptance (or installation certificate) before an occupancy permit is issued.


Requirements in detail

Scope and purpose (what each appendix covers)

  • Reference Nonresidential Appendix NA6 — provides procedures for calculating default fenestration metrics (examples in the Code: default U‑factor, SHGC, VT for skylights and other fenestration when NFRC ratings are not available). It is invoked in exceptions to the fenestration requirements in § 110.6(a)2–4.

  • Reference Nonresidential Appendix NA7 — provides the Acceptance Requirements for Code Compliance and the specific test procedures (NA7.x) used to verify equipment and systems (HVAC, duct leakage, DOAS/HRV/ERV, compressors, refrigeration, elevators, compressed air, etc.) before occupancy. Many mandatory acceptance requirements in Part 6 and elsewhere in the Code point to NA7 (for example § 120.5(a) and § 160.3(d)).

  • Reference Nonresidential Appendix NA7.8 — provides the test procedure for outdoor lighting controls acceptance testing; the Code requires outdoor lighting controls be tested per NA7.8 before occupancy where applicable (see § 130.4 and related subsections).

Decision‑relevant dimensions and values

The table below collects decision thresholds and the Code sections that call the appendices (use the appendix test method named in the Code section).

Decision dimension / value How it matters Appendix or test Code Reference
Skylight area < 200 ft² Allows use of NA6 default calculations for U‑factor, SHGC, VT when NFRC is not used NA6 § 110.6(a)2–4
Site‑built fenestration (non‑residential) Must be certified per NA7 before occupancy; matching label certificate required NA7 (fenestration acceptance) § 110.6(a)6
Duct leakage ≤ 6% of nominal air handler airflow New duct systems that meet specific criteria must be sealed and verified by NA7.5.3 test NA7.5.3 § 120.5(a) and § 160.3(c)2H
Duct test applicability: constant‑volume single‑zone, < 5,000 ft² served, > 25% ducts outdoors/unconditioned These criteria determine whether the 6% leakage threshold and NA7.5.3 apply NA7.5.3 § 120.5(a) / § 160.3(c)2H
Outdoor lighting controls Must be acceptance‑tested per NA7.8 (tests for daylighting, shut‑off, demand response, outdoor controls grouped in NA7.6 & NA7.8) NA7.8 § 130.4 / § 130.5 / § 160.5(e)
Certified test technician requirements (CMATT / CLCATT) Certain acceptance tests must be performed by certified technicians and their ID must appear on the Certificate of Acceptance NA7 (reference for acceptance) and Part 1, § 10‑103 § 120.5(a); § 160.3(d); § 130.4(c); § 10‑103

How the appendices are used in practice

  • Where the body of the Code says “shall be tested in accordance with NA7.x” or “default … may be calculated as set forth in NA6,” you must:
    • Follow the exact test method or calculation in that NA section; and
    • Prepare and submit the required Certificate of Acceptance (or installation certificate) to the enforcement agency before an occupancy permit is issued. See the many body sections that require submission of a Certificate of Acceptance referencing NA7 (for example § 120.5(a) and § 130.4).

Exceptions & special cases

  • Manufacturer‑certified equipment exception: air economizers installed and factory‑tested/certified by the HVAC manufacturer are not required to undergo the NA7 functional test for air economizers. See the exceptions in § 120.5(a)4.

  • Healthcare facilities: Many acceptance testing requirements that reference NA7 exclude systems serving healthcare facilities; where healthcare rules apply alternate acceptance/testing requirements or OSHPD rules may take precedence (see exceptions to § 120.5 and other sections).

  • Fenestration alterations and re‑use: Reinstalled fenestration removed and reinstalled as part of an alteration may be excepted from some labeling/acceptance requirements (see exceptions to § 110.6). However, new site‑built fenestration in nonresidential buildings still requires certification per NA7.

  • Lighting specific subcases: Daylight responsive, shut‑off, demand response, and outdoor lighting controls are handled under NA7.6 series and NA7.8; certain multifamily common areas have separate cross‑references (see § 130.4 and § 160.5(e)).


Common mistakes

  • Removing temporary labels on fenestration before inspection. The Code requires a temporary label (or label certificate for site‑built products) not be removed before inspection — see § 110.6(a)5.

  • Assuming NA6 default values apply to all windows/skylights — NA6 defaults are explicitly invoked only in the circumstances shown in the body of the Code (for example, skylights with less than 200 ft²) — do not apply NA6 where NFRC ratings or other body‑section requirements govern. See § 110.6(a)2–4.

  • Failing to submit a Certificate of Acceptance (or a properly completed installation certificate) referencing the NA7 acceptance test — many sections state that the Certificate must be submitted to the enforcement agency before occupancy (see § 120.5(a) and § 130.4).

  • Testing by uncertified personnel: when the Code requires a CMATT or CLCATT under Part 1 § 10‑103, the acceptance testing must be performed by a certified technician and include their certification ID on the Certificate of Acceptance (see § 160.3(d) and § 130.4(c)).

  • Misinterpreting applicability thresholds (e.g., duct leakage testing criteria such as < 5,000 ft² served or > 25% ducts located outdoors/unconditioned) — confirm the body section first (e.g., § 120.5(a), § 160.3(c)2H) before applying NA7.5.3.


Worked example — small office skylight + duct system

Scenario: A small office installs a new skylight of 150 ft² and a new constant‑volume, single‑zone HVAC system that serves 3,200 ft² of conditioned floor area. Some ductwork runs through an unconditioned attic and accounts for 30% of the total duct surface area.

Steps and how the appendices apply:

  1. Skylight default properties: Because the skylight area is less than 200 ft², the Code allows the use of NA6 default calculation procedures for U‑factor, SHGC, and VT when NFRC ratings are unavailable; follow NA6 for the exact calculation method and document the result as allowed by § 110.6(a)2–4. (Note: the specific numeric defaults or formulas in NA6 are not included in the retrieved excerpts, so consult Appendix NA6 directly for the numeric procedure.)

  2. Duct leakage testing: The duct system is a constant volume single‑zone system, serves < 5,000 ft², and > 25% of the duct surface area is outdoors/unconditioned — so the duct system meets the criteria to be tested to a leakage rate not greater than 6% of the nominal air handler flow using the NA7.5.3 test procedure and report. Perform NA7.5.3 testing and include results on the Certificate of Acceptance required by § 120.5(a).

  3. Documentation and occupancy: Before an occupancy permit is granted, submit the Certificate of Acceptance showing the NA6 computation for the skylight (if used) and the NA7.5.3 duct leakage test result in accordance with the Code sections that require submission (for fenestration § 110.6(a)6 and for mechanical acceptance § 120.5(a)). If any acceptance testing must be done by a certified acceptance test technician (CMATT/CLCATT), ensure that certification ID is on the certificate per § 10‑103 rules.

(If you need the actual NA6 default numeric values or the exact test procedure steps from NA7.5.3/NA7.8, those are inside the Appendices themselves; the excerpts we have reference the appendices but do not reproduce the detailed numeric tables or step‑by‑step procedures. Consult NA6 and NA7.5.x/NA7.8 text for the exact formulas, instrumentation, and reporting formats.)


Related provisions

  • § 110.6(a)2–4 — Fenestration default metrics and exceptions that invoke NA6 for skylights and alterations.
  • § 110.6(a)5–6 — Labeling and fenestration acceptance requirements referencing NA7 for site‑built fenestration certification.
  • § 120.5(a) — Nonresidential mechanical system acceptance: lists many NA7.x test procedures (NA7.5.1–NA7.5.18).
  • § 120.6(c) — Parking garage ventilation system acceptance referencing NA7 (NA7.12).
  • § 130.4 — Lighting control acceptance and installation certificate requirements (invokes NA7.6 and NA7.8).
  • § 130.5 / § 160.5(e) — Further lighting control acceptance requirements and the requirement to test outdoor lighting controls per NA7.8.
  • § 160.3(d) — Multifamily mechanical acceptance requirements that reference NA7 testing (e.g., NA7.18 series).
  • § 10‑103 (Part 1) — Certification procedures for acceptance test technicians and submission of Certificates of Acceptance (CMATT / CLCATT requirements referenced in body sections that require NA7 testing).

Code references

Grounded in the retrieved California Energy Code — click a citation to read the verbatim passage:

  • § 110.6 Medium relevance — show source text

    Exception 1 to Section 110.6(a)2: If the fenestration product is a skylight in a building covered by the nonresidential standards with less than 200 square feet of skylight area, the default U -factor may be calculated as set forth in Reference Nonresidential Appendix NA6.

    Exception 2 to Section 110.6(a)2: If the fenestration product is an alteration consisting of any area replacement of glass in a skylight product in a building covered by the nonresidential standards, the default U -factor may be calculated as set forth in Reference Nonresidential Appendix NA6. 3. Solar heat gain coefficient SHGC. The fenestration product’s SHGC shall be rated in accordance with NFRC 200, or use the applicable default SHGC set forth in Table 110.6-B.

    Exception 1 to Section 110.6(a)3: If the fenestration product is a skylight in a building covered by the nonresidential standards with less than 200 square feet of skylight area, the default SHGC may be calculated as set forth in Reference Nonresidential Appendix NA6.

    Exception 2 to Section 110.6(a)3: If the fenestration product is an alteration consisting of any area replacement of glass in a skylight product in a building covered by the nonresidential standards, the default SHGC may be calculated as set forth in Reference Nonresidential Appendix NA6. 4. Visible transmittance (VT). The fenestration product’s VT shall be rated in accordance with NFRC 200 or ASTM E972. For tubular daylighting devices VT shall be rated using NFRC 203.

    Exception 1 to Section 110.6(a)4: If the fenestration product is a skylight in a building covered by the nonresidential standards with less than 200 square feet of skylight area, the default VT may be calculated as set forth in Reference Nonresidential Appendix NA6.

    Exception 2 to Section 110.6(a)4: If the fenestration product is an alteration consisting of any area; replacement of glass in a skylight product in a building covered by the nonresidential standards, the default VT may be calculated as set forth in Reference Nonresidential Appendix NA6. 5. Labeling. Fenestration products and exterior doors shall: A. Have a temporary label for manufactured fenestration products and exterior doors or a label certificate when the component modeling approach (CMA) is used and for site-built fenestration meeting the requirements of Section 10-111(a)1. The temporary label shall not be removed before inspection by the enforcement agency; and B. Have a permanent label or label certificate when the component modeling approach (CMA) is used and for sitebuilt fenestration meeting the requirements of Section 10-111(a)2 if the product is rated using NFRC procedures. 6. Fenestration acceptance requirements. Before an occupancy permit is granted site-built fenestration products in other than single-family buildings shall be certified as meeting the Acceptance Requirements for Code Compliance, as specified in the Reference Nonresidential Appendix NA7 to ensure that site-built fenestration meets Standards requirements, including a matching label certificate for product(s) installed and be readily accessible at the project location. A certificate of accep

    2025 CALIFORNIA ENERGY CODE 55

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

  • § 5.17. Medium relevance — show source text

    R. Occupant sensing zone controls shall be tested in accordance with NA7.5.17. 2. Multifamily dwelling units. Before an occupancy permit is granted, the following systems and equipment serving multifamily dwelling units shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. These systems and equipment shall also comply with the applicable requirements of Section 160.3(d)3. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements: A. Multifamily building central ventilation ducts subject to Section 160.2(b)2C shall be leak tested in accordance with NA7.18.3.

    B. Multifamily building central ventilation system heat recovery or energy recovery systems in multifamily buildings with four or more habitable stories shall be tested in accordance with NA7.18.4.

    1. When certification is required by Title 24, Part 1, Section 10-103.2, the acceptance testing specified by Section 160.3(d)1 and 2 shall be performed by a Certified Mechanical Acceptance Test Technician (CMATT). If the CMATT is operating as an employee, the CMATT shall be employed by a Certified Mechanical Acceptance Test Employer. The CMATT shall disclose on the Certificate of Acceptance a valid CMATT certification identification number issued by an approved Acceptance Test Technician Certification Provider. The CMATT shall complete all Certificate of Acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.
    TABLE 160.3-A—RETURN DUCT SIZING FOR SINGLE RETURN DUCT SYSTEMS Col2 Col3
    Return duct length shall not exceed 30 feet and shall contain no more than 180 degrees of bend. If the total bending exceeds 90 degrees, one bend
    shall be a metal elbow.
    Return grille devices shall be labeled in accordance with the requirements in Section 160.2(b)1Biv to disclose the grille's design airflow rate and a
    maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in
    accordance with AHRI Standard 680 for the design airflow rate for the return grille.
    Return duct length shall not exceed 30 feet and shall contain no more than 180 degrees of bend. If the total bending exceeds 90 degrees, one bend
    shall be a metal elbow.
    Return grille devices shall be labeled in accordance with the requirements in Section 160.2(b)1Biv to disclose the grille's design airflow rate and a
    maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in
    accordance with AHRI Standard 680 for the design airflow rate for the return grille.
    Return duct length shall not exceed 30 feet and shall contain no more than 180 degrees of bend. If the total bending exceeds 90 degrees, one bend
    shall be a metal elbow.
    Return grille devices shall be labeled in accordance with the requirements in Section 160.2(b)1Biv to disclose the grille's design airflow rate and a
    maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in
    accordance with AHRI Standard 680 for the design airflow rate for the return grille.
  • § 0.15 Medium relevance — show source text

    (c) Mandatory requirements for enclosed parking garages.

    Mechanical ventilation systems for enclosed parking garages where the total design exhaust rate for the garage is greater than or equal to 10,000 cfm shall conform to all of the following:

    1. Automatically detect contaminant levels and stage fans or modulate fan airflow rates to 50 percent or less of design capacity, provided acceptable contaminant levels are maintained.

    2. Have controls and/or devices that will result in fan motor demand of no more than 30 percent of design wattage at 50 percent of design airflow.

    3. CO shall be monitored with at least one sensor per 5,000 square feet, with the sensor located in the highest expected concentration locations, with at least two sensors per proximity zone. A proximity zone is defined as an area that is isolated from other areas either by floor or other impenetrable obstruction.

    4. CO concentration at all sensors is maintained at ≤ 25 ppm or less at all times.

    5. The ventilation rate shall be at least 0.15 cfm/ft [2] when the garage is scheduled to be occupied.

    6. The system shall maintain the garage at negative or neutral pressure relative to other occupiable spaces when the garage is scheduled to be occupied.

    7. CO sensors shall be:

    A. Certified by the manufacturer to be accurate within plus or minus 5 percent of measurement. B. Factory calibrated. C. Certified by the manufacturer to drift no more than 5 percent per year. D. Certified by the manufacturer to require calibration no more frequently than once a year.

    86 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS

    E. Monitored by a control system. The system shall have logic that automatically checks for sensor failure by the following means. Upon detection of a failure, the system shall reset to design ventilation rates and transmit an alarm to the facility operators. i. If any sensor has not been calibrated according to the manufacturer’s recommendations within the specified calibration period, the sensor has failed. ii. During unoccupied periods the system compares the readings of all sensors, e.g., if any sensor is more than 15 ppm above or below the average of all sensors for longer than four hours, the sensor has failed. iii. During occupied periods the system compares the readings of sensors in the same proximity zone, e.g., if the 30 minute rolling average for any sensor in a proximity zone is more than 15 ppm above or below the 30 minute rolling average for other sensor(s) in that proximity zone, the sensor has failed. 8. Parking garage ventilation system acceptance. Before an occupancy permit is granted for a parking garage system subject to Section 120.6(c), the following equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.12.

    Exception 1 to Section 120.6(c): Any garage, or portion of a garage, where more than 20 percent of the vehicles expected to be stored have nongasoline combustion engines.

    Exception 2 to Section 120.6(c): Additions and alterations to existing garages where less than 10,000 cfm of new exhaust capacity is being added.

  • § 5.1. Medium relevance — show source text

    (a) Before an occupancy permit is granted, the following equipment and systems shall be certified as meeting the Acceptance Requirements for Code Compliance, as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements:

    1. Outdoor air ventilation systems shall be tested in accordance with NA7.5.1.

    2. Constant volume, single zone unitary air conditioning and heat pump unit controls shall be tested in accordance with NA7.5.2.

    3. Duct systems that are subject to testing under Section 120.4(g)1, Section 141.0(b)2Di or Section 141.0(b)2Dii shall be tested in accordance with NA7.5.3.

    4. Air economizers, DOAS, HRV or ERV systems shall be tested in accordance with NA7.5.4. Exception 1 to Section 120.5(a)4: Air economizers installed by the HVAC system manufacturer and certified to the Commission as being factory calibrated and tested are not required to comply with the Functional Testing section of the air economizer controls acceptance test as described in NA7.5.4.2. Exception 2 to Section 120.5(a)4: The DOAS, HRV, or ERV unit that does not meet the exhaust air heat recovery ratio as specified in Section 140.4(q)1 or does not include bypass or control to disable energy recovery as specified in Section 140.4(q)2.

    5. Demand control ventilation systems required by Section 120.1(c)3 shall be tested in accordance with NA7.5.5.

    6. Supply fan variable flow controls shall be tested in accordance with NA7.5.6.

    7. Hydronic system variable flow controls shall be tested in accordance with NA7.5.7 and NA7.5.9.

    8. Boiler or chillers that require isolation controls as specified by Section 140.4(k)2 or 140.4(k)3 shall be tested in accordance with NA7.5.7.

    9. Hydronic systems with supply water temperature reset controls shall be tested in accordance with NA7.5.8.

    10. Automatic demand shed controls shall be tested in accordance with NA7.5.10.

    11. Fault Detection and Diagnostics (FDD) for Packaged Direct-Expansion Units shall be tested in accordance with NA7.5.11.

    12. Automatic fault detection and diagnostics (FDD) for air handling units and zone terminal units shall be tested in accordance with NA7.5.12.

    13. Distributed Energy Storage DX AC Systems shall be tested in accordance with NA7.5.13.

    14. Thermal Energy Storage (TES) Systems shall be tested in accordance with NA7.5.14.

    15. Supply air temperature reset controls shall be tested in accordance with NA7.5.15.

    16. Water-cooled chillers served by cooling towers with condenser water reset controls shall be tested in accordance with NA7.5.16.

    17. When an energy management control system is installed, it shall functionally meet all of the applicable requirements of Part 6.

    18. Occupant sensing zone controls shall be tested in accordance with NA7.5.17.

    19. Conductivity controls and overflow alarms for open and closed-circuit cooling towers shall be tested according to NA7.5.18.

  • § 6.4. Medium relevance — show source text
    1. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and
    2. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4.
    3. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5.

    (b) Lighting control installation certificate requirements. To be recognized for compliance with Part 6 an installation certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable:

    1. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6 it complies with the applicable requirements of Section 110.9; and complies with Reference Nonresidential Appendix NA7.7.1.

    2. Certification that when an energy management control system is installed to function as a lighting control required by Part 6 it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with Reference Nonresidential Appendix NA7.7.2.

    3. Reserved.

    4. Reserved.

    5. Certification that interlocked lighting systems used to serve an approved area comply with Section 140.6(a)1; and comply with Reference Nonresidential Appendix NA7.7.4.

    6. Certification that lighting controls installed to earn a lighting power adjustment factor (PAF) comply with Section 140.6(a)2; and comply with Reference Nonresidential Appendix NA7.7.5.

    2025 CALIFORNIA ENERGY CODE 101

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

    1. Certification that additional lighting wattage installed for a videoconference studio complies with Section 140.6(c)2Gvii; and complies with Reference Nonresidential Appendix NA7.7.6.

    (c) When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 130.4 shall be performed by a certified lighting controls acceptance test technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a certified lighting controls acceptance test employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved acceptance test technician certification provider. The CLCATT shall complete all certificate of acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.

    Note: Authority cited: Sections 25402, 25402.1 and 25213, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code .

    SECTION 130.5—ELECTRICAL POWER DISTRIBUTION SYSTEMS

  • § 7.13. Medium relevance — show source text

    A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA 7.13.

    (f) Mandatory requirements for elevators. Elevators shall meet the following requirements:

    1. The light power density for the luminaires inside the elevator cab shall be no greater than 0.6 watts per square foot. Exception to Section 120.6(f)1: Interior signal lighting and interior display lighting are not included in the calculation of lighting power density.

    2. Elevator cab ventilation fans for cabs without space conditioning shall not exceed 0.33 watts per cfm as measured at maximum speed.

    3. When the elevator cab is stopped and unoccupied with doors closed for over 15 minutes, the cab interior lighting and ventilation fans shall be switched off until elevator cab operation resumes.

    4. Lighting and ventilation shall remain operational in the event that the elevator cabin gets stuck when passengers are in the cabin.

    5. Elevator Lighting and Ventilation Control Acceptance. Before an occupancy permit is granted for elevators subject to 120.6(f), the following equipment and systems shall be certified as meeting the Acceptance Requirement for Code Compli

    88 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS

    ance, as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.14.

    Exception to Section 120.6(f): Elevators located in healthcare facilities.

    (g) Mandatory requirements for escalators and moving walkways .

    1. Escalators and moving walkways located in airports, hotels, and transportation function areas shall automatically slow to the minimum permitted speed in accordance with ASME A17.1/CSA B44 when not conveying passengers.
    2. Escalators and Moving Walkways Acceptance. Before an occupancy permit is granted for escalators and moving walkways subject to 120.6(g), the following equipment and systems shall be certified as meeting the Acceptance Requirement for Code Compliance, as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.15.

    (h) Mandatory requirements for controlled environment horticulture (CEH) spaces.

    1. Indoor growing, dehumidification. Dehumidification equipment shall be one of the following: A. Dehumidifiers subject to regulation under federal appliance standards tested in accordance with 10 CFR 430.23(z) and Appendix X or X1 to Subpart B of 10 CFR Part 430 as applicable, and complying with 10 CFR 430.32(v)2; B. Integrated HVAC system with on-site heat recovery designed to fulfill at least 75 percent of the annual energy for dehumidification reheat;

    C. Chilled water system with on-site heat recovery designed to fulfill at least 75 percent of the annual energy for dehumidification reheat; or

    D. Solid or liquid desiccant dehumidification system for system designs that require dew point of 50°F or less. 2. Indoor growing, electrical power distribution systems. Electrical power distribution systems serving CEH spaces shall be designed so that a measurement device is capable of monitoring the electrical energy usage of aggregate horticultural lighting load. 3.

  • § 5.3 Medium relevance — show source text

    (g) Duct sealing. Duct systems shall comply with Subsection 1 or 2 below:

    1. New duct systems that meet the criteria in Subsections A, B, C and D below shall be sealed to a leakage rate not to exceed 6 percent of the nominal air handler airflow rate as confirmed through acceptance testing, in accordance with Reference Nonresidential Appendix NA7.5.3; A. The duct system does not serve a healthcare facility; and B. The duct system provides conditioned air to an occupiable space for a constant volume, single zone, space-conditioning system; and C. The space-conditioning system serves less than 5,000 square feet of conditioned floor area; and D. The combined surface area of the ducts located outdoors or in unconditioned space is more than 25 percent of the total surface area of the entire duct system.
    2. New duct systems that are not subject to testing under Section 120.4(g)1 shall instead meet the duct leakage testing requirements of CMC Section 603.9.2.

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.

    SECTION 120.5—REQUIRED NONRESIDENTIAL MECHANICAL SYSTEM ACCEPTANCE

    Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 120.5(a) through 120.5(b).

    Exception to Section 120.5: Systems serving healthcare facilities.

    (a) Before an occupancy permit is granted, the following equipment and systems shall be certified as meeting the Acceptance Requirements for Code Compliance, as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements:

    1. Outdoor air ventilation systems shall be tested in accordance with NA7.5.1.

    2. Constant volume, single zone unitary air conditioning and heat pump unit controls shall be tested in accordance with NA7.5.2.

    3. Duct systems that are subject to testing under Section 120.4(g)1, Section 141.0(b)2Di or Section 141.0(b)2Dii shall be tested in accordance with NA7.5.3.

    4. Air economizers, DOAS, HRV or ERV systems shall be tested in accordance with NA7.5.4. Exception 1 to Section 120.5(a)4: Air economizers installed by the HVAC system manufacturer and certified to the Commission as being factory calibrated and tested are not required to comply with the Functional Testing section of the air economizer controls acceptance test as described in NA7.5.4.2. Exception 2 to Section 120.5(a)4: The DOAS, HRV, or ERV unit that does not meet the exhaust air heat recovery ratio as specified in Section 140.4(q)1 or does not include bypass or control to disable energy recovery as specified in Section 140.4(q)2.

    5. Demand control ventilation systems required by Section 120.1(c)3 shall be tested in accordance with NA7.5.5.

    6. Supply fan variable flow controls shall be tested in accordance with NA7.5.6.

  • § 6.4. Medium relevance — show source text

    F. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and G. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4. H. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5. 2. Lighting control installation certificate requirements. To be recognized for compliance with Part 6, an Installation Certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable: A. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6, it complies with the applicable requirements of Section 110.9 and complies with Reference Nonresidential Appendix NA7.7.1.

    B. Certification that when an energy management control system is installed to function as a lighting control required by Part 6, it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 160, 170 and 180, and complies with Reference Nonresidential Appendix NA7.7.2. C. Certification that interlocked lighting systems used to serve an approved area comply with Section 170.2(e)2A and comply with Reference Nonresidential Appendix NA7.7.4. D. Certification that lighting controls installed to earn a lighting power adjustment factor (PAF) comply with Section 170.2(e)2B and comply with Reference Nonresidential Appendix NA7.7.5.

    E. Reserved.

    1. When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 160.5(e) shall be performed by a Certified Lighting Controls Acceptance Test Technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a Certified Lighting Controls Acceptance Test Employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved Acceptance Test Technician Certification Provider. The CLCATT shall complete all Certificate of Acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.

    NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .

    SECTION 160.6—MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEMS

    Multifamily buildings shall comply with the applicable requirements of Sections 160.6(a) through 160.6(e).

    (a) Service electrical metering. Each electrical service or feeder that provides power to the common use areas (interior and exterior) shall have a permanently installed metering system that measures electrical energy use in accordance with Table 160.6-A.

    Exception to Section 160.6(a): Service or feeder for which the utility company provides a metering system for the multifamily building that indicates instantaneous kW demand and kWh for a utility-defined period.

    232 2025 CALIFORNIA ENERGY CODE

  • § 0.05 Medium relevance — show source text

    Add 0.05 to any product with true divided lite (dividers through the panes).
    2. Translucent or transparent panels shall use glass block values when not rated by NFRC 100.
    3. Visible Transmittance (VT) shall be calculated by using Reference Nonresidential Appendix NA6.
    4. Windows with window film applied that is not rated by NFRC 100 shall use the default values from this table.|

    TABLE 110.6-B—DEFAULT SOLAR HEAT GAIN COEFFICIENT (SHGC) Col2 Col3 Col4 Col5 Col6
    FRAME TYPE PRODUCT GLAZING FENESTRATION PRODUCT SHGC FENESTRATION PRODUCT SHGC FENESTRATION PRODUCT SHGC
    FRAME TYPE PRODUCT GLAZING Single Pane2, 3
    SHGC
    Double Pane2, 3
    SHGC
    Glass Block1, 2
    SHGC
    Metal Operable Clear 0.80 0.70 0.70
    Metal Fixed Clear 0.83 0.73 0.73
    Metal Operable Tinted 0.67 0.59 NA
    Metal Fixed Tinted 0.68 0.60 NA
    Metal, thermal break Operable Clear NA 0.63 NA
    Metal, thermal break Fixed Clear NA 0.69 NA
    Metal, thermal break Operable Tinted NA 0.53 NA
    Metal, thermal break Fixed Tinted NA 0.57 NA
    Nonmetal Operable Clear 0.74 0.65 0.70
    Nonmetal Fixed Clear 0.76 0.67 0.67
    Nonmetal Operable Tinted 0.60 0.53 NA
    Nonmetal Fixed Tinted 0.63 0.55 NA
    1. Translucent or transparent panels shall use glass block values when not rated by NFRC 200.
    2. Visible Transmittance (VT) shall be calculated by using Reference Nonresidential Appendix NA6.
    3. Windows with window film applied that is not rated by NFRC 200 shall use the default values from this table.
    1. Translucent or transparent panels shall use glass block values when not rated by NFRC 200.
    2. Visible Transmittance (VT) shall be calculated by using Reference Nonresidential Appendix NA6.
    3. Windows with window film applied that is not rated by NFRC 200 shall use the default values from this table.
    1. Translucent or transparent panels shall use glass block values when not rated by NFRC 200.
    2. Visible Transmittance (VT) shall be calculated by using Reference Nonresidential Appendix NA6.
    3. Windows with window film applied that is not rated by NFRC 200 shall use the default values from this table.
    1. Translucent or transparent panels shall use glass block values when not rated by NFRC 200.
    2. Visible Transmittance (VT) shall be calculated by using Reference Nonresidential Appendix NA6.
    3.
  • § 160.3 Medium relevance — show source text

    (d) Mechanical acceptance testing.

    1. Common areas. Before an occupancy permit is granted, the following systems and equipment serving multifamily common areas shall be certified as meeting the Acceptance Requirements for Code Compliance, as specified by Reference Nonresidential Appendix NA7. These systems and equipment shall also comply with the applicable requirements of Section

    220 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS

    160.3(d)3. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements: A. Outdoor air ventilation systems shall be tested in accordance with NA7.5.1. B. Constant volume, single zone air conditioning and heat pump unit controls shall be tested in accordance with NA7.5.2. C. Duct systems shall be tested in accordance with NA7.5.3 where either: a. They are new duct systems; or b. They are part of an altered system. D. Air economizers, DOAS, HRV or ERV systems shall be tested in accordance with NA7.5.4. Exception to Section 160.3(d)1D: Air economizers installed by the HVAC system manufacturer and certified to the Commission as being factory calibrated and tested are not required to comply with the Functional Testing section of the Air Economizer Controls acceptance test as described in NA7.5.4.2. E. Demand control ventilation systems required by Section 160.2(c)3 shall be tested in accordance with NA7.5.5. F. Supply fan variable flow controls shall be tested in accordance with NA7.5.6. G. Hydronic system variable flow controls shall be tested in accordance with NA7.5.7 and NA7.5.9. H. Boilers or chillers that require isolation controls as specified by Section 170.2(c)4Iii or 170.2(c)4Iiii shall be tested in accordance with NA7.5.7.

    I. Hydronic systems with supply water temperature reset controls shall be tested in accordance with NA7.5.8.

    J. Automatic demand shed controls shall be tested in accordance with NA7.5.10.

    K. Fault detection and diagnostics (FDD) for packaged direct expansion units shall be tested in accordance with NA7.5.11. L. Automatic fault detection and diagnostics (FDD) for air handling units and zone terminal units shall be tested in accordance with NA7.5.12.

    M. Distributed energy storage DX AC systems shall be tested in accordance with NA7.5.13. N. Thermal energy storage (TES) systems shall be tested in accordance with NA7.5.14. O. Supply air temperature reset controls shall be tested in accordance with NA7.5.15. P. Water-cooled chillers served by cooling towers with condenser water reset controls shall be tested in accordance with NA7.5.16.

    Q. When an energy management control system is installed, it shall functionally meet all of the applicable requirements of Part 6.

  • § 120.6 Medium relevance — show source text

    B. Piping section average velocity. Compressor room interconnection and main header piping shall be sized so that at coincident peak flow conditions, the average velocity in the segment of pipe is no greater than 20 ft/sec. Compressor room interconnection and main header piping are the pipes that deliver compressed air from the compressor outlets to the inlet to the distribution piping. Each segment of distribution and service piping shall be sized so that at coincident peak flow conditions, the average velocity in the segment of pipe is no greater than 30 ft/sec. Distribution piping are pipes that deliver compressed air from the compressor room interconnection piping or main header piping to the service line piping. C. Piping total pressure drop. Piping shall be designed such that piping frictional pressure loss at coincident peak loads is less than 5 percent of operating pressure between the compressor and end use or end use regulator. 6. Compressed air system acceptance. Before an occupancy permit is granted for a compressed air system subject to Section 120.6(e), the equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA 7.13.

    (f) Mandatory requirements for elevators. Elevators shall meet the following requirements:

    1. The light power density for the luminaires inside the elevator cab shall be no greater than 0.6 watts per square foot. Exception to Section 120.6(f)1: Interior signal lighting and interior display lighting are not included in the calculation of lighting power density.

    2. Elevator cab ventilation fans for cabs without space conditioning shall not exceed 0.33 watts per cfm as measured at maximum speed.

    3. When the elevator cab is stopped and unoccupied with doors closed for over 15 minutes, the cab interior lighting and ventilation fans shall be switched off until elevator cab operation resumes.

    4. Lighting and ventilation shall remain operational in the event that the elevator cabin gets stuck when passengers are in the cabin.

    5. Elevator Lighting and Ventilation Control Acceptance. Before an occupancy permit is granted for elevators subject to 120.6(f), the following equipment and systems shall be certified as meeting the Acceptance Requirement for Code Compli

    88 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS

    ance, as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.14.

    Exception to Section 120.6(f): Elevators located in healthcare facilities.

  • § 110.6 Medium relevance — show source text

    Exception 2 to Section 110.6(a)4: If the fenestration product is an alteration consisting of any area; replacement of glass in a skylight product in a building covered by the nonresidential standards, the default VT may be calculated as set forth in Reference Nonresidential Appendix NA6. 5. Labeling. Fenestration products and exterior doors shall: A. Have a temporary label for manufactured fenestration products and exterior doors or a label certificate when the component modeling approach (CMA) is used and for site-built fenestration meeting the requirements of Section 10-111(a)1. The temporary label shall not be removed before inspection by the enforcement agency; and B. Have a permanent label or label certificate when the component modeling approach (CMA) is used and for sitebuilt fenestration meeting the requirements of Section 10-111(a)2 if the product is rated using NFRC procedures. 6. Fenestration acceptance requirements. Before an occupancy permit is granted site-built fenestration products in other than single-family buildings shall be certified as meeting the Acceptance Requirements for Code Compliance, as specified in the Reference Nonresidential Appendix NA7 to ensure that site-built fenestration meets Standards requirements, including a matching label certificate for product(s) installed and be readily accessible at the project location. A certificate of accep

    2025 CALIFORNIA ENERGY CODE 55

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS

    tance certifying that the fenestration product meets the acceptance requirements shall be completed, signed and submitted to the enforcement agency. Exception to Section 110.6(a): Fenestration products removed and reinstalled as part of a building alteration or addition.

    (b) Installation of field-fabricated fenestration and exterior doors. Field-fabricated fenestration and field-fabricated exterior doors may be installed only if the compliance documentation has demonstrated compliance for the installation using U factors from Table 110.6-A and SHGC values from Table 110.6-B. Field-fabricated fenestration and field-fabricated exterior doors shall be caulked between the fenestration products or exterior door and the building, and shall be weatherstripped.

    Exception to Section 110.6(b): Unframed glass doors and fire doors need not be weatherstripped or caulked.

    TABLE 110.6-A—DEFAULT FENESTRATION PRODUCT U-FACTORS Col2 Col3 Col4 Col5
    FRAME1,2 PRODUCT TYPE SINGLE PANE3, 4
    U-FACTOR
    DOUBLE PANE1, 3, 4
    U-FACTOR
    GLASS BLOCK2, 3
    U-FACTOR
    Metal Operable 1.28 0.79 0.87
    Metal Fixed 1.19 0.71 0.72
    Metal Greenhouse/garden window 2.26 1.40 NA
    Metal Glazed doors 1.25 0.77 NA
    Metal Skylight 1.98 1.3 NA
    Metal, thermal break Operable NA 0.66 NA
    Metal,
  • § 160.5 High relevance — show source text

    (e) Lighting control acceptance and installation certificate requirement. Multifamily common use areas shall comply with the applicable requirements of Sections 160.5(e)1 through 160.5(e)3.

    1. Lighting control acceptance requirements. Before an occupancy permit is granted, indoor and outdoor lighting controls serving the building, area or site and installed to comply with Section 160.5(b)4D, 160.5(b)4C, 160.5(b)4E, 160.5(c)2 or 170.2(e)1Aiij shall be certified as meeting the Acceptance Requirements for Code Compliance as specified by Reference Nonresidential Appendix NA7.6 and NA7.8. A Certificate of Acceptance shall be submitted to the enforcement agency under Section 10-103(a) of Part 1 that the equipment and systems meet the acceptance requirements:

    A. Reserved;

    B. Reserved; C. Daylight responsive controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.1; D. Lighting shut-OFF controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.2; E. Demand responsive lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.3; and

    F. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and G. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4. H. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5. 2. Lighting control installation certificate requirements. To be recognized for compliance with Part 6, an Installation Certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable: A. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6, it complies with the applicable requirements of Section 110.9 and complies with Reference Nonresidential Appendix NA7.7.1.

    B. Certification that when an energy management control system is installed to function as a lighting control required by Part 6, it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 160, 170 and 180, and complies with Reference Nonresidential Appendix NA7.7.2. C. Certification that interlocked lighting systems used to serve an approved area comply with Section 170.2(e)2A and comply with Reference Nonresidential Appendix NA7.7.4. D. Certification that lighting controls installed to earn a lighting power adjustment factor (PAF) comply with Section 170.2(e)2B and comply with Reference Nonresidential Appendix NA7.7.5.

    E. Reserved.

  • § 130.3 High relevance — show source text

    Exception to Section 130.3(a)2B: Outdoor signs in tunnels and large covered areas that are intended to be illuminated both day and night. 3. Demand responsive Electronic Message Center (EMC) control. See Section 110.12 for requirements for demand responsive EMC controls .

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.

    SECTION 130.4—LIGHTING CONTROL ACCEPTANCE AND INSTALLATION CERTIFICATE REQUIREMENTS

    Nonresidential buildings other than healthcare facilities and hotel/motel buildings shall comply with the applicable requirements of Sections 130.4(a) through 130.4(c). Healthcare facilities shall comply with the applicable acceptance and installation documentation requirements of OSHPD.

    (a) Lighting and receptacle control acceptance requirements. Before an occupancy permit is granted, indoor and outdoor lighting and receptacle controls serving the building, area or site and installed to comply with Section 110.12, 120.6(h)5B, 130.1, 130.2, 130.5 or 140.6 shall be certified as meeting the Acceptance Requirements for Code Compliance as specified by the Reference Nonresidential Appendix NA7.6 and NA7.8. A Certificate of Acceptance shall be submitted to the enforcement agency under Section 10-103(a) of Part 1, that the equipment and systems meet the acceptance requirements:

    1. Reserved.

    2. Reserved.

    3. Daylight responsive controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.1;

    4. Lighting shut-OFF controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.2;

    5. Demand responsive lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.3; and

    6. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and

    7. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4.

    8. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5.

    (b) Lighting control installation certificate requirements. To be recognized for compliance with Part 6 an installation certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable:

    1. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6 it complies with the applicable requirements of Section 110.9; and complies with Reference Nonresidential Appendix NA7.7.1.

    2. Certification that when an energy management control system is installed to function as a lighting control required by Part 6 it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with Reference Nonresidential Appendix NA7.7.2.

    3. Reserved.

    4. Reserved.

  • § 160.5 Medium relevance — show source text

    Exception 3 to Section 160.5(c)2C: Lighting subject to a health or life safety statute, ordinance or regulation may have a minimum time-out period longer than 15 minutes or a minimum dimming level above 50 percent when necessary to comply with the applicable law.

    (d) Sign lighting controls. All sign lighting shall meet the requirements below as applicable:

    1. Indoor signs. All indoor sign lighting other than exit sign lighting shall be controlled with an automatic time-switch control or astronomical time-switch control.

    2. Outdoor signs. Outdoor sign lighting shall meet the following requirements as applicable: A. All outdoor sign lighting shall be controlled with a photocontrol in addition to an automatic time-switch control, or an astronomical time-switch control.

    Exception to Section 160.5(d)2A: Outdoor signs in tunnels, and signs in large permanently covered outdoor areas that are intended to be continuously lit, 24 hours per day and 365 days per year. B. All outdoor sign lighting that is ON both day and night shall be controlled with a dimmer that provides the ability to automatically reduce sign lighting power by a minimum of 65 percent during nighttime hours. Signs that are illuminated at night and for more than 1 hour during daylight hours shall be considered ON both day and night.

    2025 CALIFORNIA ENERGY CODE 231

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS

    Exception to Section 160.5(d)2B: Outdoor signs in tunnels and large covered areas that are intended to be illuminated both day and night. 3. Demand responsive electronic message center (EMC) control. See Section 110.12 for requirements for demand responsive EMC controls.

    (e) Lighting control acceptance and installation certificate requirement. Multifamily common use areas shall comply with the applicable requirements of Sections 160.5(e)1 through 160.5(e)3.

    1. Lighting control acceptance requirements. Before an occupancy permit is granted, indoor and outdoor lighting controls serving the building, area or site and installed to comply with Section 160.5(b)4D, 160.5(b)4C, 160.5(b)4E, 160.5(c)2 or 170.2(e)1Aiij shall be certified as meeting the Acceptance Requirements for Code Compliance as specified by Reference Nonresidential Appendix NA7.6 and NA7.8. A Certificate of Acceptance shall be submitted to the enforcement agency under Section 10-103(a) of Part 1 that the equipment and systems meet the acceptance requirements:

    A. Reserved;

    B. Reserved; C. Daylight responsive controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.1; D. Lighting shut-OFF controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.2; E. Demand responsive lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.3; and

    F. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and G. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4. H. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5. 2. **Lighting control installation certificate requirements.

  • § 120.6 Medium relevance — show source text

    D. New screw compressors with nominal electric motor power greater than 150 HP shall include the ability to automatically vary the compressor volume ratio (Vi) in response to operating pressures. 6. Infiltration barriers. Passageways between freezers and higher-temperature spaces, and passageways between coolers and nonrefrigerated spaces, shall have an infiltration barrier consisting of strip curtains, an automaticallyclosing door or an air curtain designed by the manufacturer for use in the passageway and temperature for which it is applied. Exception 1 to Section 120.6(a)6: Openings with less than 16 square feet of opening area. Exception 2 to Section 120.6(a)6: Dock doorways for trailers. 7. Refrigerated warehouse acceptance. Before an occupancy permit is granted for a new refrigerated warehouse, or before a new refrigeration system serving a refrigerated warehouse is operated for normal use, the following equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements: A. Electric resistance underslab heating systems shall be tested in accordance with NA7.10.1. B. Evaporators fan motor controls shall be tested in accordance with NA7.10.2. C. Evaporative condensers shall be tested in accordance with NA7.10.3.1.

    D. Air-Cooled condensers shall be tested in accordance with NA7.10.3.2.

    E. Adiabatic condensers shall be tested in accordance with NA7.10.3.3.

    F. Variable speed compressors shall be tested in accordance with NA7.10.4. G. Transcritical CO 2 refrigeration systems shall be tested in accordance with NA7.20.1. 8. Transcritical CO 2 gas coolers. New fan-powered gas coolers on all new transcritical CO 2 refrigeration systems shall conform to the following: A. Air-cooled gas coolers are prohibited in Climate Zones 9 through 15. B. Design leaving gas temperature for air-cooled gas coolers shall be less than or equal to the design dry-bulb temperature plus 6°F. Exception to Section 120.6(a)8B: Design leaving gas temperature for air-cooled gas coolers in Climate Zones 2, 4 and 8 shall be less than or equal to the design dry-bulb temperature plus 8°F.

    2025 CALIFORNIA ENERGY CODE 83

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS

    C. Design leaving gas temperature for adiabatic gas coolers necessary to reject the design total heat of rejection of a refrigeration system assuming dry mode performance shall be less than or equal to the design dry-bulb temperature plus 15°F. D. All gas cooler fans shall be continuously variable speed, with the speed of all fans serving a common condenser high side controlled in unison.

    E. While operating below the critical point, the gas cooler pressure shall be controlled in accordance with Section 120.6(a)4F.

  • § 140.9 Medium relevance — show source text

    Listed energy recovery devices with a sensible heat recovery effectiveness of not less than 40 percent on at least 50 percent of the total exhaust airflow; or iv. A minimum of 75 percent of makeup air volume that is:

    a. Unheated or heated to no more than 60°F; and

    b. Uncooled or cooled without the use of mechanical cooling.

    Exception to Section 140.9(b)2B: Existing hoods not being replaced as part of an addition or alteration. 3. Kitchen exhaust system acceptance. Before an occupancy permit is granted for a commercial kitchen subject to Section 140.9(b), the following equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.11.

    Exception to Section 140.9(b): Healthcare facilities.

    (c) Prescriptive requirements for laboratory and factory exhaust systems.

    1. Airflow reduction requirements. Building laboratory exhaust systems shall be able to reduce zone exhaust and makeup airflow rates to the occupied and unoccupied minimum exhaust airflow rates based on demand and sensed occupancy as follows:

    A. Occupied minimum exhaust airflow. When occupant sensing controls sense occupants in the space, the minimum exhaust and makeup airflow rates shall be the greater of: i. User-defined airflow not to exceed 1.0 cfm/ft [2] (equivalent to 6 air changes per hour for a 10-foot high ceiling); or ii. The regulated minimum occupied circulation rate documented to comply with code, accreditation, or facility environmental health and safety department requirements; or iii. The minimum needed to maintain occupied pressurization. B. Unoccupied minimum exhaust airflow. Within 20 minutes of no occupancy being detected by any occupant sensors covering the space, the minimum exhaust and makeup airflow rates shall be the greater of: i. User-defined airflow not to exceed 0.67 cfm/ft [2] (equivalent to 4 air changes per hours for a 10-foot high ceiling);

    or

    ii. The regulated minimum unoccupied circulation rate documented to comply with code, accreditation, or facility environmental health and safety department requirements; or iii. The minimum needed to maintain unoccupied pressurization. C. Applicable equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the reference Nonresidential Appendix NA7.16. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in Nonresidential Appendix NA7.16.

    Exception to Section 140.9(c)1: New zones on an existing constant volume exhaust system. 2. Exhaust System Transfer Air. Conditioned supply air delivered to any space with mechanical exhaust shall comply with the requirements of Section 140.4(o). 3. Fan System Power Consumption. All newly installed fan exhaust systems serving a laboratory or factory with a design exhaust fan system airflow rate greater than 10,000 cfm shall meet Subsection A and either B, C, or D. Exhaust air in laboratories or factories includes all indoor air and gases removed by the exhaust system, including exhaust air from fume hoods, hazardous exhaust flows, or other manifolded exhaust streams. Exhaust fan system airflow rate is the total of the airflow rates entering the exhaust fans, which includes exhaust air and bypass air but does not include entrained or induced airflow downstream of the exhaust fans.

  • § 140.9 Medium relevance — show source text

    A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in Nonresidential Appendix NA7.16. 4. Fume Hood Automatic Sash Closure. Variable air volume laboratory fume hoods with vertical only sashes located in fume hood intensive laboratories, as described in Table 140.9-D, shall have an automatic sash closure system that complies with the following: A. The automatic sash closure system shall be capable of the following: i. The automatic sash closure system shall have a dedicated zone presence sensor that detects people in the area near the fume hood sash and automatically closes the sash within 5 minutes of no detection. ii. The automatic sash closure system shall have controls to prevent the sash from automatic closing when a force of no more than 10 lbs is detected.

    iii. The automatic sash closure system shall be equipped with an obstruction sensor that prevents the sash from automatic closing with obstructions in the sash opening. Obstruction sensor shall be capable of sensing transparent materials such as laboratory glassware. iv. The automatic sash closure system shall be capable of being configured in a manual open mode where once the sash is closed, detection of people in the area near the fume hood by the zone presence sensor does not open the fume hood sash. B. Fume Hood Automatic Sash Closure Acceptance. Before an occupancy permit is granted for the fume hoods subject to 140.9(c)4, the equipment and systems shall be certified as meeting the Acceptance Requirement for Code Compliance as specified by the Reference Nonresidential Appendix NA7. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.17.

    TABLE 140.9-D—FUME HOOD INTENSIVE LABORATORIES THRESHOLD (both must be true) Col2 Col3 Col4 Col5 Col6 Col7
    Occupied minimum ventilation ACH ≤ 4 > 4 and ≤ 6 > 6 and ≤ 8 > 8 and ≤ 10 > 10 and ≤ 12 > 12 and ≤ 14
    Hood density (linear feet per 10,000 ft3 of
    laboratory space)
    ≥ 6 ≥ 8 ≥ 10 ≥ 12 ≥ 14 ≥ 16
    1. Reheat limitation. Air handlers in buildings with greater than 20,000 cfm of laboratory exhaust that serve multiple spaceconditioning zones in laboratory spaces shall not mechanically cool air handler supply air below 80°F and shall not heat air

    144 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE

    COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY

    handler supply air above 50°F, and each zone shall include heating and cooling capacity to prevent cooling at the air handler and reheating at the zones. Exception 1 to Section 140.9(c)5: Additions or alterations to existing air-handling systems serving existing zones without heating and cooling capacity. Exception 2 to Section 140.9(c)5: Systems in Climate Zones 7 or 15.

Frequently asked questions

What exactly does NA6 contain?

NA6 contains the procedures and default calculations used where NFRC or other rating methods are not used for fenestration metrics (U‑factor, SHGC, VT) and is specifically called out for limited skylight and alteration cases in the body of the Code — see § 110.6(a)2–4. For the numeric formulas or tables, consult Appendix NA6 directly; the body sections only reference it.

When must I submit a Certificate of Acceptance?

Whenever a Code section says “shall be certified as meeting the Acceptance Requirements … as specified by Reference Nonresidential Appendix NA7,” a Certificate of Acceptance must be submitted to the enforcement agency before an occupancy permit is granted (examples include § 120.5(a) for mechanical systems and § 130.4 for lighting controls).

Do I always need a certified tester (CMATT / CLCATT)?

No — only when the particular acceptance testing requirement in the body of the Code references the Part 1 certification requirement (e.g., § 160.3(d) and § 130.4(c) indicate that certain acceptance tests must be performed by certified technicians and that the technician’s certification ID be on the Certificate of Acceptance). Check the specific body section that invokes NA7.x.

Are there exceptions for factory‑calibrated equipment?

Yes. For example, air economizers that are installed and factory‑certified by the HVAC manufacturer are exempt from the NA7 functional testing portion for air economizers per the exception in § 120.5(a)4.

Where do I find the exact NA7.8 test steps for outdoor lighting?

The Code body requires that outdoor lighting controls be tested per NA7.8 (see § 130.4 and related sections). The step‑by‑step test method and reporting format are in Appendix NA7.8 itself — consult that appendix for instrumentation, sampling, and reporting details.

More in California Energy Code

Ask about the California Energy Code

Get cited, plain-English answers on the California Energy Code for your project — any code section, any scenario.

Start Free Trial

Related in the California Energy Code