Title 24 · California Energy Code
Space‑conditioning, electrical equipment and demand‑management certification/efficiency
This hub summarizes Part 6 requirements for manufacturer certification, minimum efficiency, and demand‑management/control interoperability for HVAC and electrical equipment.
Last reviewed: July 6, 2026
Overview
This part of Title 24, Part 6 (the California Energy Code) sets mandatory certification and minimum‑performance rules for space‑conditioning (HVAC) equipment, electrical power‑distribution components, and demand‑management controls. Key mandatory sections include §110.2 (Manufacturer certification and efficiency requirements for space‑conditioning equipment), §110.11 (certification for electrical power distribution equipment), and §110.12 (demand‑management / demand‑response control requirements) . For nonresidential systems, required controls and zonal HVAC functions are also addressed in Subchapter 3 (for example §120.2) and the lighting/electrical controls chapters (for example §130.1) .
These provisions matter because they make certification and interoperable controls the baseline for compliance: manufacturers must declare equipment meets the listed efficiency and test methods, electrical distribution gear must be certified, and demand‑response devices must meet communications and control specifications (for example certified OpenADR VEN or Baseline Profile OpenADR 3.0 VEN) so buildings can participate reliably in utility/load‑management events . The code also ties these hardware and control requirements into acceptance and field‑verification procedures so installations are tested, documented, and reported for enforcement and performance compliance .
When planning or reviewing projects, focus on the certification declarations and directories required by §110.1–§110.2, the mandatory demand‑response capabilities and interfaces in §110.12 (and related nonresidential control programming in §120.2), and the installation/acceptance testing and certificates called out elsewhere in Part 6 and the Reference Appendices .
In this section
Code references
Grounded in the retrieved California Energy Code — click a citation to read the verbatim passage:
§ 110.1 High relevance — show source text
SECTION 110.1—MANDATORY REQUIREMENTS FOR APPLIANCES
(a) Any appliance regulated by the Appliance Efficiency Regulations, Title 20 California Code of Regulations, Section 1601 et seq., may be installed only if the appliance fully complies with Section 1608(a) of those regulations.
(b) Except for those circumstances described in Section 110.1(c), conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be verified utilizing data from either:
- The Energy Commission’s database of certified appliances maintained pursuant to Title 20 California Code of Regulations Section 1606, and which is available at: www.energy.ca.gov/appliances/database/ ; or
- An equivalent directory published by a federal agency; or
- An approved trade association directory as defined in Title 20 California Code of Regulations Section 1606(h).
(c) Conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be demonstrated either by default to the mandatory efficiency levels specified in Part 6 or by following procedures approved by the Commission pursuant to Section 10-109 of Title 24, Part 1, when:
- Data to verify conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards is not available pursuant to subdivision (b); or
- Field verification and diagnostic testing is required for compliance with Part 6 and the Energy Commission has not approved a field verification and diagnostic test protocol that is applicable to the appliance; or
- The appliance meets the requirements of Section 110.1(a) but has been site-modified in a way that affects its performance; or
2025 CALIFORNIA ENERGY CODE 39
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
- The U.S. Department of Energy has approved a waiver from federal test procedures, pursuant to 10 CFR Section 430.27 or Section 431.401 and that waiver fails to specify how the efficiency of the system shall be determined.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5
, 25402.8, and 25943, Public Resources Code.SECTION 110.2—MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
Certification by manufacturers. Any space-conditioning equipment listed in this section may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section.
(a) Efficiency. Equipment shall meet the applicable efficiency requirements in Tables 110.2-A through 110.2-L, subject to the following:
- If more than one efficiency standard is listed for any equipment in Tables 110.2-A through 110.2-L, the equipment shall meet all the applicable standards that are listed; and
- If more than one test method is listed in Tables 110.2-A through 110.2-L, the equipment shall comply with the applicable efficiency standard when tested with each listed test method; and
§ 110.0 High relevance — show source text
110.0 Systems and Equipment—General . . . . . . . . . . . . . . . 39
110.1 Mandatory Requirements for Appliances . . . . . . . . . 39
110.2 Mandatory Requirements for Space-Conditioning Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
110.3 Mandatory Requirements for Service Water-Heating Systems and Equipment . . . . . . . . . . . . . . . . . . . . . . . 52
110.4 Mandatory Requirements for Pool and Spa Systems and Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
110.5 Natural Gas Central Furnaces, Cooking Equipment, Pool and Spa Heaters, and Fireplaces: Pilot Lights Prohibited. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
110.6 Mandatory Requirements for Fenestration Products and Exterior Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
110.7 Mandatory Requirements to Limit Air Leakage . . . . 57
110.8 Mandatory Requirements for Insulation, Roofing Products and Radiant Barriers. . . . . . . . . . . . . . . . . . 57
110.9 Mandatory Requirements for Lighting Controls. . . . 59
110.10 Mandatory Requirements for Solar Readiness. . . . . 60
110.11 Mandatory Requirements for Electrical Power Distribution System . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
110.12 Mandatory Requirements for Demand Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
SUBCHAPTER 3 NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
120.0 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
120.1 Requirements for Ventilation and Indoor Air Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
120.2 Required Controls for Space-Conditioning Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
120.3 Requirements for Pipe Insulation . . . . . . . . . . . . . . . . 75
120.4 Requirements for Air Distribution System Ducts and Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
§ 2.0 High relevance — show source text
B. Certified to the Energy Commission as being capable of responding to a demand response signal from a certified OpenADR 2.0b or a certified Baseline Profile OpenADR 3.0 Virtual End Node by automatically implementing the control functions requested by the Virtual End Node for the equipment it controls. 2. All demand responsive controls shall be capable of communicating with the VEN using a wired or wireless bidirectional communication protocol.
Reserved.
When the demand response signal is disabled or unavailable, all demand responsive controls shall continue to perform all other control functions provided by the control.
Demand responsive control thermostats shall comply with Reference Joint Appendix 5 (JA5), Technical Specifications for Occupant Controlled Smart Thermostats. (b) Demand Responsive Zonal HVAC Controls. Nonresidential HVAC systems with DDC to the Zone level shall be programmed to allow centralized demand shed for noncritical zones as follows:
The controls shall have a capability to remotely increase the operating cooling temperature set points by 4 degrees or more in all noncritical zones on signal from a centralized contact or software point within an Energy Management Control System (EMCS).
The controls shall have a capability to remotely decrease the operating heating temperature set points by 4 degrees or more in all noncritical zones on signal from a centralized contact or software point within an EMCS.
The controls shall have capabilities to remotely reset the temperatures in all noncritical zones to original operating levels on signal from a centralized contact or software point within an EMCS.
The controls shall be programmed to provide an adjustable rate of change for the temperature increase, decrease, and reset.
The controls shall have the following features: A. Disabled. Disabled by authorized facility operators; and B. Manual control. Manual control by authorized facility operators to allow adjustment of heating and cooling set points globally from a single point in the EMCS; and C. Automatic Demand Shed Control. Upon receipt of a demand response signal, the space-conditioning systems shall conduct a centralized demand shed, as specified in Sections 110.12(b)1 and 110.12(b)2, for noncritical zones during the demand response period.
2025 CALIFORNIA ENERGY CODE 63
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
(c) Demand Responsive Lighting Controls. Buildings with nonresidential lighting systems having a total installed lighting power of 4,000 watts or greater that are subject to the requirements of Section 130.1(b) or 160.5(b)4B shall install controls that are capable of automatically reducing lighting power in response to a demand response signal.
- For compliance testing, the lighting controls shall demonstrate a 15-percent or greater reduction in lighting power as described in NA7.6.3. The controls may provide additional demand responsive functions or abilities.
- For buildings where demand response controls are required, demand responsive controls shall control the general lighting in the spaces required to meet Section 130.1(b) or 160.5(b)4B.
- General lighting shall be reduced in a manner consistent with the requirements of Section 130.1(b) or 160.5(b)4B. Exception to Section 110.12(c): Spaces where a health or life safety statute, ordinance, or regulation does not permit the general lighting to be reduced are not required to install demand responsive controls and do not count toward the 4,000-watt threshold.
§ 25218.5 High relevance — show source text
(b) Certification Requirements for Manufactured Systems, Equipment, Appliances and Building Components.
- Appliances that are within the scope of Section 1601 of the Appliance Efficiency Regulations shall only be installed if they have been certified to the Energy Commission by the manufacturer, pursuant to the provisions of Title 20 California Code of Regulations, Section 1606; or
- Systems, equipment, appliances and building components that are required by Part 6 or the Reference Appendices to be certified to the Energy Commission, which are not appliances that are within the scope of Section 1601 of the Appliance Efficiency Regulations, shall only be installed if they are certified by the manufacturer in a declaration, executed under penalty of perjury under the laws of the State of California, that: A. All the information provided pursuant to the certification is true, complete, accurate and in compliance with all applicable requirements of Part 6; and B. The equipment, product, or device was tested using the test procedure specified in Part 6 if applicable
- The certification status of any system, equipment, appliance or building component shall be confirmed only by reference to: A. A directory published or approved by the Commission; or B. A copy of the application for certification from the manufacturer and the letter of acceptance from the Commission staff; or C. Written confirmation from the publisher of a Commission-approved directory that a device has been certified; or D. A Commission-approved label on the device.
Note: Part 6 does not require a builder, designer, owner, operator, or enforcing agency to test any certified device to determine its compliance with minimum specifications or efficiencies adopted by the Commission.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5
, 25402.8, and 25943, Public Resources Code.SECTION 110.1—MANDATORY REQUIREMENTS FOR APPLIANCES
(a) Any appliance regulated by the Appliance Efficiency Regulations, Title 20 California Code of Regulations, Section 1601 et seq., may be installed only if the appliance fully complies with Section 1608(a) of those regulations.
(b) Except for those circumstances described in Section 110.1(c), conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be verified utilizing data from either:
- The Energy Commission’s database of certified appliances maintained pursuant to Title 20 California Code of Regulations Section 1606, and which is available at: www.energy.ca.gov/appliances/database/ ; or
- An equivalent directory published by a federal agency; or
- An approved trade association directory as defined in Title 20 California Code of Regulations Section 1606(h).
(c) Conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be demonstrated either by default to the mandatory efficiency levels specified in Part 6 or by following procedures approved by the Commission pursuant to Section 10-109 of Title 24, Part 1, when:
- Data to verify conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards is not available pursuant to subdivision (b); or
- Field verification and diagnostic testing is required for compliance with Part 6 and the Energy Commission has not approved a field verification and diagnostic test protocol that is applicable to the appliance; or
§ 110.11 High relevance — show source text
110.11 Mandatory Requirements for Electrical Power Distribution System . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
110.12 Mandatory Requirements for Demand Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
SUBCHAPTER 3 NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
120.0 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
120.1 Requirements for Ventilation and Indoor Air Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
120.2 Required Controls for Space-Conditioning Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
120.3 Requirements for Pipe Insulation . . . . . . . . . . . . . . . . 75
120.4 Requirements for Air Distribution System Ducts and Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
120.5 Required Nonresidential Mechanical System Acceptance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
120.6 Mandatory Requirements for Covered
Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
120.7 Mandatory Requirements for Building Envelopes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
120.8 Nonresidential Building Commissioning. . . . . . . . . . 91
120.9 Mandatory Requirements for Commercial Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
120.10 Mandatory Requirements for Fans. . . . . . . . . . . . . . . . 93
SUBCHAPTER 4 NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL
POWER DISTRIBUTION SYSTEMS . . . . . . . . . . . . . . . . . . . . 95
130.0 Lighting Systems and Equipment, and Electrical Power Distribution Systems—General . . . . . . . . . . . 95
130.1 Mandatory Indoor Lighting Controls . . . . . . . . . . . . . . 96
130.2 Outdoor Lighting Controls and Equipment . . . . . . .100
§ 203.1.2 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A4 — RESIDENTIAL VOLUNTARY MEASURES
A4.203.1.2 Prerequisite options. In addition, a minimum of TWO of the efficiency measures specified in Sections A4.203.1.2.1 through A4.203.1.2.7 must be met.
A4.203.1.2.1 Roof deck insulation, or ducts in conditioned space. Meet one of the three options for the location of ducts and air handlers as well as insulation R -values and installation of a radiant barrier as specified in Title 24, Part 6, Section 150.1(c)9A or B:
Below roof deck insulation with a minimum R -value of 19; or,
Continuous above deck insulation with a minimum R-8 and with an air space present between the roofing and the roof deck; or,
All ducts and air handlers in conditioned space as specified in the Title 24, Part 6, Reference Appendix RA3.1.
A4.203.1.2.2 High performance walls. Meet the climate zone dependent U -factor or insulation R -value for either 2x6 or 2x4 framing as specified in Title 24, Part 6, Section 150.1(c)1B: maximum U -factor of 0.048.
A4.203.1.2.3 Compact hot water distribution system. Meet the requirements for installation of Compact Hot Water Distribution Systems specified in the Title 24, Part 6, Reference Appendix RA3.6.5.
A4.203.1.2.4 Drain water heat recovery. Meet the requirements for installation of Drain Water Heat Recovery specified in Title 24, Part 6, Reference Appendix RA4.4.21.
A4.203.1.2.5 High performance vertical fenestration. Meet the climate zone dependent U -factor and Solar Heat Gain Coefficient (SHGC) as rated in accordance with Title 24, Part 6, Section 110.6, and shall have a maximum U -factor of 0.21 in Climate Zones 1 − 16, maximum SHGC of 0.23 in Climate Zones 2, 4, and 6 − 14, and maximum SHGC of 0.20 in Climate Zone 15.
Exception to A4.203.1.2.5: Fenestration in Climate Zones 1, 3, 5, and 16 is not required to comply with the maximum SHGC requirements.
A4.203.1.2.6 Heat pump water heater demand management. For buildings with heat pump water heating, meet the requirements for installation of controls specified by Title 24, Part 6, Reference Appendix JA13.3.3.
A4.203.1.2.7 Battery storage system controls. For buildings with battery storage systems, meet the requirements for installation of controls specified by Title 24, Part 6, Reference Appendix JA12 for either the Time-of-Use Control or Advanced Demand Flexibility Control option.
§ 204.1.1 High relevance — show source text
A4.204.1.1 Altered space-conditioning system serving existing single-family dwelling units – mechanical cooling. When a space-conditioning system serving an existing single-family dwelling unit is altered in Climate Zones 1 through 14 and 16 by installation or replacement of an air conditioner, the altered system shall comply with either a or b below in addition to the requirements for installation specified by Title 24, Part 6, Sections 150.2(b)1E and 150.2(b)1F: a. A heat pump shall be the primary heating source and sized according to the system selection requirements specified by Title 24, Part 6 of Section 150.0(h)5. Supplemental heating may be provided by an existing gas furnace or existing electric resistance heating; or b. An air conditioner shall meet the following requirements: i. R-8 duct insulation for ducts located in unconditioned space; and ii. The duct system measured air leakage shall be equal to or less than 5 percent of the system air handler airflow as confirmed through field verification and diagnostic testing, per the requirements in Title 24, Part 6, Reference Residential Appendix Section RA3.1.4.3.1; and iii. Demonstrate, in every control mode, airflow greater than or equal to 400 CFM per ton of nominal cooling capacity through the return grilles, and an air-handling unit fan efficacy less than or equal to 0.35 W/CFM. The airflow rate and fan efficacy requirements in this section shall be confirmed through field verification and diagnostic testing, following the procedures outlined in Title 24, Part 6, Reference Residential Appendix RA3.3; and iv. In all climate zones refrigerant charge verification requirements shall meet the requirements in Title 24, Part 6 Section 150.2(b)1Fiib; and v. Vented attics shall have insulation installed to achieve a U -factor of 0.020 or insulation installed at the ceiling level shall result in an insulated thermal resistance of R-49 or greater for the insulation alone; and vi. Air seal all accessible areas of the ceiling plane between the attic and the conditioned space in accordance with the requirements in Title 24, Part 6 Section 150.2(b)1Jii.
Exception 1 to Section A4.204.1.1: Where the capacity of the existing main electrical service panel is insufficient to supply the electrical capacity of a heat pump and where the existing main electrical service panel is sufficient to supply a new or replacement air conditioner, as calculated according to the requirements of California Electrical Code Article 220.83 or 220.87. Documentation of electrical load calculations in accordance with Article 220 must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.
Exception 2 to Section A4.204.1.1: Where the required capacity of a heat pump to meet the system selection requirements of Section 150.0(h)5 is greater than or equal to 12,000 Btu/h more than the required capacity of an air conditioner to meet the design cooling load. Documentation of heating and cooling load calculations in accordance with 150.0(h) must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.
A4.204.1.2 Altered pool and/or spa heating for existing multifamily buildings. Alteration of an existing multifamily pool and/or spa heating system shall meet the following:
Heating source sizing. Heating systems or equipment for pools or spas shall meet one of the sizing requirements of Items 1 through 5 below: 1.
§ 10-109 Medium relevance — show source text
(b) Performance approach. A building complies with the performance approach if the energy consumption calculated for the proposed design building is no greater than the energy budget calculated for the standard design building using Commission-certified compliance software as specified by Sections 10-109(c) and 10-116.
- Energy budget. The energy budget is expressed in terms of source energy and long-term system cost (LSC). A. Long-term system cost (LSC). The LSC energy budget is determined by applying the mandatory and prescriptive requirements of the standard design to the proposed design building and has two components, the Efficiency LSC and the Total LSC.
i. The Efficiency LSC energy is the sum of the LSC energy for space-conditioning, water heating, mechanical ventilation, and the self-utilization credit.
ii. The Total LSC energy is the sum of the Efficiency LSC energy and LSC energy from the photovoltaic system, battery energy storage systems (BESS), lighting, demand flexibility, and other plug loads. B. Source energy. The source energy budget is determined by applying the mandatory and prescriptive requirements of the standard design to the proposed design building. The source energy is the total annual source energy. Exception to Section 150.1(b)1. A community shared solar electric generation system, or other renewable electric generation system, or community shared BESS, which provides dedicated power, utility energy reduction credits, or payments for energy bill reductions to the permitted building and is approved by the Energy Commission as specified in Title 24, Part 1, Section 10-115, may offset part or all of the solar electric generation system and demand flexibility Energy Design Rating required to comply with the Standards, as calculated according to methods established by the Commission in the Residential ACM Reference Manual.
- Compliance demonstration requirements for performance standards. A. Certificate of compliance and application for a building permit. The application for a building permit shall include documentation pursuant to Sections 10-103(a)1 and 10-103(a)2 which demonstrates, using an approved calculation method, that the building has been designed so that its energy consumption does not exceed the standard design energy budgets for the applicable climate zone. Exception to Section 150.1(b)2A Multiple orientation: A permit applicant may demonstrate compliance with the energy budget requirements of Section 150.1(a) and (b) for any orientation of the same building model if the documentation demonstrates that the building model with its proposed designs and features would comply in each of the four cardinal orientations.
B. Field verification. When performance of installed features, materials, components, manufactured devices or systems above the minimum specified in Section 150.1(c) is necessary for the building to comply with Section 150.1(b), or is necessary to achieve a more stringent local ordinance, field verification shall be performed in accordance with the applicable requirements in the following subsections, and the results of the verification(s) shall be documented on applicable certificates of installation pursuant to Section 10-103(a)3 and applicable certificates of verification pursuant to Section 10-103(a)5. i. EER2/SEER2/CEER/HSPF2 Rating. When performance compliance requires installation of a space-conditioning system with a rating that is greater than the minimum rating required by Table 150.1-A or specified for the standard design, the installed system shall be field verified in accordance with the procedures specified in the applicable sections of Reference Residential Appendix RA3.4. ii. **Variable capacity heat pump (VCHP) compliance option.
§ 207.1.1 Medium relevance — show source text
**
A6.207.1.1 Efficiency.
A6.207.1.2 Controls for heat pumps with supplementary electric resistance heaters.
A6.207.1.3 Thermostats.
A6.207.1.4 Gas-and oil-fired furnace standby loss controls.||
|
|| |A6.207.2 Space conditioning systems.
A6.207.2.1 Supply air temperature reset controls.
A6.207.2.2 Electric resistance heating.
A6.207.2.3 Heat rejection systems.
A6.207.2.4 Hydronic system measures.
A6.207.2.5 Air distribution system duct leakage sealing.
A6.207.2.6 Variable air volume control for single zone systems.||
|
|| |A6.207.3 Service water-heating systems and equipment.
A6.207.3.1 Certification by manufacturers.
A6.207.3.2 Efficiency.
A6.207.3.3 Installation.||
|
|| |A6.207.4 Natural gas central furnaces, cooking equipment and pool and spa heaters.
Pilot lights prohibited.||||| |A6.207.5 Controls for space-conditioning systems.
A6.207.5.1 Thermostatic controls for each zone.
A6.207.5.2 Criteria for zonal thermostatic controls.
A6.207.5.3 Heat pump controls.
A6.207.5.4 Dampers for air supply and exhaust equipment.
A6.207.5.5 Automatic demand shed controls.||
|
|| |A6.207.6 Pipe insulation.||||| |SECTION A6.209 Lighting||||| |A6.209.1 Lighting control devices, ballasts and luminaires.
A6.209.1.1 All devices: Instructions and calibration.
A6.209.1.2 Indicator lights.
**A6.209.1.3 Automatic time switch control devices.§ 110.10 Medium relevance — show source text
(d) Documentation. A copy of the construction documents or a comparable document indicating the information from Sections 110.10(b) through 110.10(c) shall be provided to the occupant.
(e) Main electrical service panel.
- The main electrical service panel shall have a minimum busbar rating of 200 amps.
- The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a future solar electric installation. The reserved space shall be permanently marked as “For Future Solar Electric”.
Note: Authority: Sections 25213, 25218, 25218.5, 25402, 25402.1, and 25605, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, 25605, and 25943, Public Resources Code.
SECTION 110.11—MANDATORY REQUIREMENTS FOR ELECTRICAL POWER DISTRIBUTION SYSTEM
Certification by Manufacturers. Any electrical power distribution system equipment listed in this section may be installed only if the manufacture has certified to the Commission that the equipment complies with all the applicable requirements of this section.
62 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
(a) Low-voltage dry-type distribution transformer shall be certified by the Manufacturer as required by the Title 20 Appliance Efficiency Regulations.
EXCEPTION to Section 110.11(a):
autotransformer;
drive (isolation) transformer;
grounding transformer;
machine-tool (control) transformer;
nonventilated transformer;
rectifier transformer;
regulating transformer;
sealed transformer;
special-impedance transformer;
testing transformer;
transformer with tap range of 20 percent or more;
uninterruptible power supply transformer; or
welding transformer.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.
SECTION 110.12 — MANDATORY REQUIREMENTS FOR DEMAND MANAGEMENT
Buildings, other than healthcare facilities, that install or are required to install demand responsive controls shall comply with the applicable demand responsive control requirements of Sections 110.12(a) through 110.12(e). (a) Demand responsive controls.
- All demand responsive controls shall be either: A. A certified OpenADR 2.0a or OpenADR 2.0b Virtual End Node (VEN), as specified under Clause 11, Conformance, in the applicable OpenADR 2.0 Specification; or a certified Baseline Profile OpenADR 3.0 Virtual End Node; or
§ 170.0 Medium relevance — show source text
Exception to Section 170.0 (a)3: If a single development falls in more than one climate zone, all buildings in the subdivision or tract may be designed to meet the performance or prescriptive standards for the climate zone that contains 50 percent or more of the dwelling units.
NOTE: The Commission periodically updates, publishes and makes available to interested persons and local enforcement agencies precise descriptions of the climate zones, as specified in Reference Joint Appendix JA2—Weather/Climate Data.
NOTE: The requirements of Sections 170.1(a) through 170.2(e) apply to newly constructed buildings and Sections 180.1 and 180.2 specify changes to the requirements of Sections 170.1(a) through 170.2(e) that apply to additions or alterations.
NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .
SECTION 170.1—PERFORMANCE APPROACH
A building complies with the performance approach if the energy consumption calculated for the proposed design building is no greater than the energy budget calculated for the standard design building using Commission-certified compliance software as specified by Sections 10-109 and 10-116 and the Alternative Calculation Method Reference Manual.
(a) Energy budget. The energy budget is expressed in terms of long-term system cost (LSC) and source energy:
- Long-term system cost (LSC). The LSC energy budget is determined by applying the mandatory and prescriptive requirements of the standard design to the proposed design building and has two components, the Efficiency LSC and the Total LSC.
A. The Efficiency LSC energy is the sum of the LSC energy for space-conditioning, water heating, mechanical ventilation, lighting and the self-utilization credit. B. The Total LSC energy is the sum of the Efficiency LSC energy and LSC energy from the photovoltaic system, battery energy storage systems (BESS), and demand flexibility. 2. Source energy. The source energy budget is determined by applying the mandatory and prescriptive requirements of the standard design, except with a consumer gas or propane water heater, to the proposed design building.
Exception to Section 170.1(a): A community shared solar electric generation system, or other renewable electric generation system, and/or community shared BESS, that provides dedicated power, utility energy reduction credits or payments for energy bill reductions to the permitted building and is approved by the Energy Commission as specified in Title 24, Part 1, Section 10-115, may offset part or all of the solar electric generation system or BESS LSC energy required to comply with the standards, as calculated according to methods established by the Commission in the Nonresidential ACM Reference Manual.
(b) Compliance demonstration requirements for performance standards.
- Certificate of Compliance and Application for a Building Permit. The application for a building permit shall include documentation pursuant to Sections 10-103(a)1 and 10-103(a)2 that demonstrates, using an approved calculation method, that the building has been designed so that its source energy and LSC energy consumption do not exceed the standard design energy budgets for the applicable climate zone.
- Field verification of individual dwelling unit systems.
§ 1-2006 Medium relevance — show source text
- Fractional HVAC motors for fans. HVAC motors for fans that are less than 1 hp and [1] / 12 hp or greater shall be electronicallycommutated motors or shall have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1-2006 at full load rating conditions. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans may use sheave adjustments for airflow balancing in lieu of a varying motor speed. Exception 1 to Section 140.4(c)3: Motors in fan-coils and terminal units that operate only when providing heating to the space served. Exception 2 to Section 140.4(c)3: Motors in space conditioning equipment certified under Section 110.1 or 110.2.
Exception to Section 140.4(c): Fan system power caused solely by process loads.
(d) Space-conditioning zone controls. Each space-conditioning zone shall have controls designed in accordance with 1 or 2:
- Each space-conditioning zone shall have controls that prevent: A. Reheating; and B. Recooling; and C. Simultaneous provisions of heating and cooling to the same zone, such as mixing or simultaneous supply of air that has been previously mechanically heated and air that has been previously cooled, either by cooling equipment or by economizer systems; or
120 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE
COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY
- Zones served by variable air-volume systems that are designed and controlled to reduce, to a minimum, the volume of reheated, recooled, or mixed air are allowed only if the controls meet all of the following requirements: A. For each zone with direct digital controls (DDC): i. The volume of primary air that is reheated, recooled or mixed air supply shall not exceed the larger of: a. 50 percent of the peak primary airflow; or b. The design zone outdoor airflow rate as specified by Section 120.1(c)3. ii. The volume of primary air in the deadband shall not exceed the design zone outdoor airflow rate as specified by Section 120.1(c)3. iii. The first stage of heating consists of modulating the zone supply air temperature setpoint up to a maximum setpoint no higher than 95ºF while the airflow is maintained at the dead band flow rate. iv. The second stage of heating consists of modulating the airflow rate from the dead band flow rate up to the heating maximum flow rate. v. Control sequences of operation for reheat zones shall be in accordance with ASHRAE Guideline 36. B. For each zone without DDC, the volume of primary air that is reheated, re-cooled, or mixed air supply shall not exceed the larger of the following: i. 30 percent of the peak primary airflow; or ii. The design zone outdoor airflow rate as specified by Section 120.1(c)3.
Exception 1 to Section 140.4(d): Zones with special pressurization relationships or cross-contamination control needs.
Exception 2 to Section 140.4(d): Zones served by space-conditioning systems in which at least 75 percent of the energy for reheating, or providing warm air in mixing systems, is provided from a site-recovered or site-solar energy source.
Frequently asked questions
Do manufacturers have to certify HVAC equipment before installation?
Yes. Space‑conditioning equipment listed in §110.2 may be installed only if the manufacturer certifies compliance with the applicable efficiency standards and test methods specified in the tables and text of §110.2 .
What must demand‑response/demand‑management controls support?
Demand‑responsive controls must meet the code’s communication and functional requirements (for example certified OpenADR 2.0/3.0 VEN compatibility), and nonresidential HVAC and lighting controls must be capable of the centralized sheds, setpoint adjustments, or automatic lighting reductions described in §110.12 and related sections such as §120.2 and §130.1 .
Are there special acceptance or testing requirements tied to these rules?
Yes. Part 6 requires acceptance testing, field verification, and certificates of installation/acceptance for many space‑conditioning, control, and lighting systems (see the Reference Nonresidential/Residential Appendices and acceptance sections referenced by Part 6) to confirm the installed equipment and controls meet code requirements .
More in California Energy Code
- Compliance paths, energy budgets, performance modeling and forms/software requirements
- Controls, commissioning, demand-response, sensors, and field verification/diagnostic testing
- Domestic hot water systems, efficiency, controls and installation requirements
- Electrical infrastructure, EV charging readiness, load management and demand controls
- Envelope construction, insulation, fenestration and thermal performance
- HVAC systems, ventilation rates, ducting, controls and testing
- Interior and exterior lighting power, controls and daylighting requirements
- Mandatory measures, appliance efficiency and certification requirements
- Photovoltaic requirements, BESS (battery energy storage) sizing and SARA procedures
- Reference appendices, test procedures, product certification and labeling requirements
- Scope, applicability, definitions and administrative requirements
Ask about the California Energy Code
Get cited, plain-English answers on the California Energy Code for your project — any code section, any scenario.
Start Free TrialRelated in the California Energy Code
Manufacturer certification, scope and installation limits
Appliance efficiency verification, approved directories and exceptions
Covered processes, commercial refrigeration, acceptance testing and documentation
Mandatory measures, appliance efficiency and certification requirements
California Energy Code