Skip to content

Electrical Code

San Francisco County Municipal Code Art. 352 Rigid Polyvinyl Chloride Conduit [ ←] : Type

San Francisco County Municipal Code · 2026-09 edition · updated 2026-10-04 · San Francisco County

Cite as: San Francisco County Municipal Code Article 352 · Text as of 2026-10-04

PVC [ ←]
352.10 Revise Items (A) through (K) as follows: 352.10 Uses Permitted. The use of PVC conduit shall be permitted in accordance with 352.10(A) through (K). (A) [ ←] Reserved. (B) Encased in Concrete. PVC conduit shall be permitted embedded in concrete. The conduit may emerge not more than 3 inches from the concrete within wiring enclosures, otherwise metal raceways shall be provided where emerging from the concrete. (C) Corrosive Influences. PVC conduit shall be permitted in locations subject to severe corrosive influences as covered in 300.6 and where subject to chemicals for which the materials are specifically approved. (D) Cinders. PCV conduit shall be permitted in cinder fill. (E) [ ←] Reserved (F) [ ←] Reserved (G) [ ←] Reserved (H) Underground installations. For underground installations, PVC shall be permitted for direct burial and underground encased in concrete. See 300.5 and 305.15. (I) [ ←] Reserved (J) [ ←] Reserved (K) [ ←] Reserved

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — San Francisco County Municipal Code

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.