Section 515C — TEST OF ANCHORS IN UNREINFORCED MASONRY WALLS

515C.2 Direct Tension Testing of Existing Anchors and New Bolts.

San Francisco Building Inspection Commission Codes · 2022 edition · updated 2026-08-28 · San Francisco

The test apparatus shall be supported on the masonry wall. The distance between the anchor and the test apparatus support shall not be less than one-half the wall thickness for existing anchors and 75 percent of the embedment for new embedded bolts. Existing wall anchors shall be given a preload of 300 pounds (136.4 kg) prior to establishing a datum for recording elongation. The tension test load reported shall be recorded at 1/8 inch (3.18 mm) relative movement of the existing anchor and the adjacent masonry surface. New embedded tension bolts shall be subject to a direct tension load of not less than 2.5 times the design load but not less than 1,500 pounds (682 kg) for five minutes (10 percent deviation).