230.71 Maximum Number of Disconnects.
San Francisco Building Inspection Commission Codes · 2022 edition · updated 2026-08-28 · San Francisco
(A) General. The service disconnecting means for each service permitted by 230.2, or for each set of service-entrance conductors permitted by
← 230.40, Exception Nos. 1, 3, 4, or 5, shall consist of [ ] a single circuit breaker or switch and set of fuses.
For the purpose of this section, disconnecting means installed as part of listed equipment and used solely for the following shall not be considered a service disconnecting means:
(1) Power monitoring equipment
(2) Surge-protective device(s)
(3) Control circuit of the ground-fault protection system
(4) Power-operable service disconnecting means.
Exception No. 1:
a) Multi-Family Dwellings with a Maximum of (6) units, shall consist of not more than six switches or sets of circuit-breakers, or a combination of not more than six switches and sets of circuit breakers, mounted in a single enclosure, in a group of separate enclosures, or in or on a switchboard or in switchgear.
b) There shall be not more than six sets of disconnects per service grouped in any one location.
Exception No. 2: A Single Main Circuit Breaker or set of fuses shall be provided for each Dwelling Unit.
ARTICLE 250 – GROUNDING AND BONDING
Get a plain-English answer with a citation back to this text.
Ask AI about this code