330.12 Uses Not Permitted.
San Francisco Building Inspection Commission Codes · 2022 edition · updated 2026-08-28 · San Francisco
Type MC cable shall not be used under either of the following conditions:
(1) Where subject to physical damage
Informational Note: See the 2022 San Francisco Electrical Code Section 300.4 (I) Subject to Physical Damage.
...
Exception: Type MC Cable #4 AWG or larger, installed in a lockable room dedicated solely to an electrical service and distribution equipment and accessible only to qualified personnel, shall be considered to have equivalent protection from physical damage when in-stalled in a neat and workman like manner, properly supported, and securely fastened in place.