Chapter 3 — Wiring Methods and Materials

San Francisco Building Inspection Commission Codes Art. 340 Underground Feeder and Branch-Circuit Cable: Type Uf

San Francisco Building Inspection Commission Codes · 2026-08 edition · updated 2026-09-23 · San Francisco

Cite as: San Francisco Building Inspection Commission Codes Article 340 · Text as of 2026-09-23

340.10 Revise Item (1) as follows:

340.10 Uses Permitted. Type UF cable shall be permitted as follows:

(1) For use underground in systems not exceeding 50 volts, including direct burial in the earth. For underground requirements see 300.5.