Earlier editions: 2026-09
Chapter 14 — FIRE PREVENTION›Article II — FIRE CODE
Mountain View Municipal Code Div. 9 Immersion Heaters
Mountain View Municipal Code · 2026-10 edition · updated 2026-10-04 · Mountain View
Cite as: Mountain View Municipal Code Division 9 · Text as of 2026-10-04
SEC. 14.20.05. - Immersion heaters.¶
A new subsection 603.10 of Section 603 (Electrical Equipment, Wiring and Hazards) is added to the 2025 California Fire Code to read as follows:
603.10 Immersion heaters. All electrical immersion heaters used in dip tanks, sinks, vats and similar operations shall be provided with approved overtemperature controls and low liquid level electrical disconnects. Manual reset of required protection devices shall be provided.
(Ord. No. 9.2025, § 8(Exh. C), 9/9/25.)