Los Angeles Building Code — LAMC Chapter IX § 91.9408 Quality Control

Los Angeles Building Code — LAMC Chapter IX · 2026-08 edition · updated 2026-09-23 · Los Angeles

Cite as: Los Angeles Building Code — LAMC Chapter IX § 91.9408 · Text as of 2026-09-23

(Amended by Ord. No. 182,850, Eff. 1/3/14.)

91.9408.1. General. All hillside building construction shall comply with the requirements specified in this section.

91.9408.2. Department Called Inspections. (Amended by Ord. No. 185,587, Eff. 7/16/18.) All anchors installed in accordance with LAMC Subsections 91.9406.2, 91.9406.3 and 91.9406.4 shall be inspected by the Department prior to installation of any construction which might restrict access to the anchors or prevent a visual inspection from the floor level above the anchors.

91.9408.3. Structural Observation by the Engineer or Architect of Record. (Amended by Ord. No. 185,587, Eff. 7/16/18.) The owner shall employ the engineer or architect of record, or other engineer or architect designated by the engineer or architect of record, to perform structural observations as required by CBC Section 1704.6.

91.9408.4. Anchor Installation. No installed anchor shall be covered prior to all required Department framing inspections and structural observation by the architect or engineer.