Skip to content

Division 94

SEC. 91.9408. QUALITY CONTROL.

Los Angeles Building Code — LAMC Chapter IX · 2026-08 edition · updated 2026-09-09 · Los Angeles

(Amended by Ord. No. 182,850, Eff. 1/3/14.)

91.9408.1. General. All hillside building construction shall comply with the requirements specified in this section.

91.9408.2. Department Called Inspections. (Amended by Ord. No. 185,587, Eff. 7/16/18.) All anchors installed in accordance with LAMC Subsections 91.9406.2, 91.9406.3 and 91.9406.4 shall be inspected by the Department prior to installation of any construction which might restrict access to the anchors or prevent a visual inspection from the floor level above the anchors.

91.9408.3. Structural Observation by the Engineer or Architect of Record. (Amended by Ord. No. 185,587, Eff. 7/16/18.) The owner shall employ the engineer or architect of record, or other engineer or architect designated by the engineer or architect of record, to perform structural observations as required by CBC Section 1704.6.

91.9408.4. Anchor Installation. No installed anchor shall be covered prior to all required Department framing inspections and structural observation by the architect or engineer.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — Los Angeles Building Code — LAMC Chapter IX

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.