§ 7148.2. SAME: MINIMUM DEPTH OF COVER.

Downey Municipal Code · 2026-07 edition · updated 2026-10-02 · Downey

The following minimum depths of cover below existing, or proposed, gutter grade shall be required for all underground pipelines within the roadway area:

  • a. Local streets (Up to 70' R/W Width)

    • (1) 24 inches for service pipelines.

    • (2) 30 inches for all pipelines transporting nonhazardous substances.

    • (3) 30 inches for electrical facilities.

    • (4) 42 inches for all pipelines transporting hazardous substances as defined in Section 7100.14 of this Code.

  • b. Major Highways (Above 70' R/W Width)

    • (1) 24 inches for service pipelines.

    • (2) 36 inches for pipelines transporting nonhazardous substances.

    • (3) 42 inches for electrical facilities.

    • (4) 42 inches for pipelines transporting hazardous substances as defined in Section 7100.14 of this Code.

(Added by Ord. 850, adopted 5-12-87)

§ 7148.2.2. SAME: SAME: EXEMPTION.

Underground cable TV and special telephone conduits shall have a minimum depth of cover of 18 inches below existing, or proposed, edge of gutter and be placed in existing roadways, as follows:

  • a. Mainline cable conduit in a four- to six-inch wide trench located adjacent to the concrete gutter, or three feet from the curb, or proposed curb, if no gutter exists.

  • b. Service cable conduits crossing the roadway from the mainline to serve users on the opposite side of local streets when installed by an acceptable boring method.

  • (Added by Ord. 850, adopted 5-12-87)