Part 3 — Excavations›§ 7148. UNDERGROUND PIPELINES.
§ 7148.2. SAME: MINIMUM DEPTH OF COVER.
Downey Municipal Code · 2026-07 edition · updated 2026-10-02 · Downey
The following minimum depths of cover below existing, or proposed, gutter grade shall be required for all underground pipelines within the roadway area:
a. Local streets (Up to 70' R/W Width)
(1) 24 inches for service pipelines.
(2) 30 inches for all pipelines transporting nonhazardous substances.
(3) 30 inches for electrical facilities.
(4) 42 inches for all pipelines transporting hazardous substances as defined in Section 7100.14 of this Code.
b. Major Highways (Above 70' R/W Width)
(1) 24 inches for service pipelines.
(2) 36 inches for pipelines transporting nonhazardous substances.
(3) 42 inches for electrical facilities.
(4) 42 inches for pipelines transporting hazardous substances as defined in Section 7100.14 of this Code.
(Added by Ord. 850, adopted 5-12-87)
§ 7148.2.2. SAME: SAME: EXEMPTION.¶
Underground cable TV and special telephone conduits shall have a minimum depth of cover of 18 inches below existing, or proposed, edge of gutter and be placed in existing roadways, as follows:
a. Mainline cable conduit in a four- to six-inch wide trench located adjacent to the concrete gutter, or three feet from the curb, or proposed curb, if no gutter exists.
b. Service cable conduits crossing the roadway from the mainline to serve users on the opposite side of local streets when installed by an acceptable boring method.
(Added by Ord. 850, adopted 5-12-87)